Lennox International Inc Dave Lennox Signature Collection XP17 System HEAT PUMPS, 506586-01

Page 37

Y1 DEMAND

HIGH

 

PRESSURE

CLOSED

SWITCH (S4)

 

COMPRESSOR CONTACTOR ENERGIZED

OPEN

OPEN

COMPRESSOR CONTACTOR DE−ENERGIZED

COMPRESSOR ANTI−SHORT CYCLE TIMER BEGINS

INCREMENT

5−STRIKE

COUNTER1

LED ALERT

CODE / OR

MODERATE

ALERT 412

DISPLAYED

ANTI−SHORT CYCLE TIMER ENDS

COMPRESSOR CONTACTOR ENERGIZED

HIGH

PRESSURECLOSED

SWITCH (S4)

1If 5−strike counter has four or less strikes when Y1 demand is terminated or satisfied, the strike counter will reset to zero. In a icomfort Touch® thermostat enabled setup, the thermostat will terminate demand when the compressor contactor is de−energized. If demand is satisfied when alarm is not active, the 5−strike counter will reset.

2Lockouts can be reset by either cycling power off to the heat pump con- trol’s (A175) R terminal, or placing a jumper on the field test pins (E33) be- tween 1 to 2 seconds.

5−STRIKE

COUNTER

REACHES 5

WITHIN A SINGLE

Y1 DEMAND

HIGH

PRESSURE

SWITCH (S4)

LOCKOUT

LED ALERT

 

CODE / OR

SERVICE

CRITICAL

REQUIRED2

ALERT 413

 

CLEARED

 

SERVICE

REQUIRED2

OPEN

HIGH

PRESSURE SWITCH (S4)

WAITING FOR PRESSURE SWITCH TO CLOSE

LED ALERT

CODE / OR

CLOSED MODERATE ALERT 412 DISPLAYED

CLOSED

NORMAL

OPERATION

Figure 29. High Pressure Switch (S4) Sequence of Operation

Page 37

XP17 SERIES

Image 37
Contents General Table of ContentsHeat Pumps Side View Access View Unit Dimensions −− Inches mmModel Number Identification Base with Elongated LegsControl BOX Typical Unit Parts ArrangementOperating Service Valves Using Manifold Gauge SetShipping and Packing List Operating Ball Type Service Valve Operating Angle Type Service ValveTo Access Service Port Reinstall Stem Cap1DISCONNECT Power Recovering Refrigerant from Existing SystemRecovering Refrigerant 2CONNECT Manifold Gauge SETUnit Placement Placement, Slab Mounting and Stabilizing Unit Detail a Outside Unit PlacementStabilizing Unit on Uneven Surfaces Removing and Installing PanelsRoof Mounting Louvered Panel Removal Louvered Panel InstallationDetail C Detail D Detail aRefrigerant Line SET New or Replacement Line SetRefrigerant Line SET Alling Horizontal Runs Refrigerant Line SET From Vertical to HorizontalBrazing Connections 2CAP and Core Removal 1PIPING Panel Removal and Preparing Line SETFlow Nitrogen Wrap Service ValvesBraze Line SET 7PREPARATION for Next StepFlushing Line Set and Indoor Coil Flushing Line Set and Indoor CoilIndoor Expansion Valve Installation Installing Indoor Expansion ValveSensing Bulb Installation Equalizer Line InstallationLeak Test Leak Test Line Set and Indoor CoilS S S S Evacuating Line Set and Indoor Coil2INSTALL Thermostat Size Circuit and Install DisconnectElectrical 24VAC TransformerRoute Control Wires Ting 3A. Route Control Wires Ting4ROUTE High Voltage and Ground Wires Typical XP17 Wiring Heat Pump Control AGE Heat Pump Control A175 Jumpers and TerminalsHeat Pump Control A175 Jumper and Terminal Descriptions Flat metal jumper Field Control WiringFurnace Control Servicing Units Delivered Void of Charge Connections for Testing and ChargingUnit Start−Up System RefrigerantHeating Mode Indoor Airflow Check Cooling Mode Indoor Airflow CheckAdding or Removing Refrigerant Airflowindoor CoilSubcooling Charging Method Using HFC−410A Weigh In MethodAir Handler / Coil Match ups and Targeted Subcooling Values Psig Operating and Temperature PressuresDefrost System System OperationsUnit Sensors Resistor Location Sensor Temperature / Resistance RangeYES Defrost Calibration Sequence of OperationsS S Test Pin E33 FunctionsOr below Low Pressure S87 Switch OperationHigh Pressure Switch S4 Sequence of Operation Input Fault or Miswire Degrees Resistance Fahrenheit 136.3 2680 DS11 and DS14 ATUS, Fault Lockout LED Codes System Status, Fault and Lockout LED CodesResetting Fault and Lockout LED Codes DS15 and DS13 Ault Lockout LED CodesModerate Device Alert Status225ºF 107ºC Lockout Vice removed or Clears after Troubleshooting Field Configuration and TestingFAN Motor B4 Test Procedure FAN Motor Control A177 OPERATION,Fan Motor Control Stage LED Indicator Codes Fan Motor Control Error/Fault LED CodesFan Motor Control RPM, LED Code and DC Voltage Output Fan Motor Control Flash and Pause DurationsTOP Grille Adjustment TOP Grille or FAN Motor Mount Adjustment for FAN ClearanceFAN Motor Position Adjustment Demand BeginsFAN Motor Control A177 PULSE−WIDTH Modulation PWM Testing for External Power to Fan Motor Control Start StripTerminal FinishSnow Guard Top Cover MaintenanceHomeowner SunSource Home Energy System Cooling Mode XP17 Start−Up and Performance ChecklistHeating Mode START−UP Checks