Lennox International Inc 506586-01 Strip, Start, Terminal, Finish, Field Test

Page 50

HEAT PUMP CONTROL (A175) UNIT NOMINAL CAPACITY CODE CONFIGURATION

In a communicating system, if the room thermostat is indicating either a error code 313, indoor and outdoor unit

capacity mismatch error code, or error code 34, must program unit capacity for outdoor unit. Use the procedure provided in figure 36 to set the unit nominal capacity code.

START

Set room thermostat

to OFF

Go to control terminal

strip

Remove R wire

from control (24 volt

AC power)

 

 

 

 

 

 

 

icomfort®

 

 

Non − icomfort®

enabled

 

 

enabled

Remove control

 

 

Remove control

wires from i+ and

 

 

wire from Y1

i− terminals

 

 

terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DS14 (Red)

DS11 (Green)

Field Test

STRIP

 

(E33)

TERMINAL

DS12

 

Communicating

 

Status Indicator

 

Sensor harness

 

must be attached

 

to air conditioner

 

control.

 

FINISH

Connect R wire to control (24 volt AC power)

Reconnect any control

wiring previously

removed.

Remove R wire from air conditioner control (24 volt AC power)

Place jumper on

 

 

FIELD TEST

 

 

(E33 pins)

 

Place jumper on FIELD

 

 

 

 

TEST (E33 pins) within 2 to 4

 

 

seconds after removal

Connect R wire to control

 

 

(24 volt AC power)

 

 

 

 

The control´s DS11 and DS14 LEDs will

 

 

start blinking the Unit Nominal Code at

 

 

three (3) second intervals starting at 1−ton

Status LED lights DS11

 

through to 6−ton. If a code is not selected,

and DS14 will blink and

 

the control will cycle one more time

then on continuously.

 

through the codes before defaulting back

Once both LEDs are on

 

to the idle mode (simultaneous slow

continuously then remove

 

flash).

jumper immediately from

 

 

E33.

 

 

If jumper is not removed

 

 

immediately from E33, then DS11

 

 

and DS14 LEDs will resume

 

Long blink ON red LED (DS14) to indicate

blinking again.

 

 

tonnage and solid ON green LED (DS11)

 

 

 

 

to indicate ½ tonnage.

YES

 

 

Jumper

 

removed

 

successfully

 

Remove R wire

NO

 

from control (24 volt

 

 

 

AC power)

 

 

When the required Unit Capacity Code

is displaying on the LEDs, remove FIELD TEST jumper from pins (E33). LEDs will continue to display the selected unit capacity code for two (2) minutes before defaulting back to the idle mode {simultaneous slow flash}, or until the 24 volt power is cycled to the air conditioner control.

 

 

 

 

DS11

 

 

 

 

 

Green

DS14

 

 

Model

Size

LED

Red LED

 

 

−012

1−ton

OFF

1 long flash

 

 

 

 

−018

1.5−ton

ON

1 long flash

 

 

−024

2−ton

OFF

2 long flashes

 

 

−030

2.5−ton

ON

2 long flashes

 

 

−036

3−ton

OFF

3 long flashes

 

 

−042

3.5−ton

ON

3 long flashes

 

 

 

 

−048

4−ton

OFF

4 long flashes

 

 

−054

4.5−ton

ON

4 long flashes

 

 

−060

5−ton

OFF

5 long flashes

 

 

−066

5.5−ton

ON

5 long flashes

 

 

−072

6.0−ton

OFF

6 long flashes

 

 

 

 

 

 

Figure 36. Heat Pump Control (A175) Unit Nominal Capacity Code Configuration

Page 50

506586−01 10/10

Image 50
Contents Heat Pumps Table of ContentsGeneral Model Number Identification Unit Dimensions −− Inches mmSide View Access View Base with Elongated LegsTypical Unit Parts Arrangement Control BOXShipping and Packing List Using Manifold Gauge SetOperating Service Valves To Access Service Port Operating Angle Type Service ValveOperating Ball Type Service Valve Reinstall Stem CapRecovering Refrigerant Recovering Refrigerant from Existing System1DISCONNECT Power 2CONNECT Manifold Gauge SETUnit Placement Detail a Outside Unit Placement Placement, Slab Mounting and Stabilizing UnitRoof Mounting Removing and Installing PanelsStabilizing Unit on Uneven Surfaces Detail C Louvered Panel InstallationLouvered Panel Removal Detail D Detail aNew or Replacement Line Set Refrigerant Line SETRefrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections 1PIPING Panel Removal and Preparing Line SET 2CAP and Core RemovalBraze Line SET Wrap Service ValvesFlow Nitrogen 7PREPARATION for Next StepFlushing Line Set and Indoor Coil Flushing Line Set and Indoor CoilSensing Bulb Installation Installing Indoor Expansion ValveIndoor Expansion Valve Installation Equalizer Line InstallationLeak Test Line Set and Indoor Coil Leak TestEvacuating Line Set and Indoor Coil S S S SElectrical Size Circuit and Install Disconnect2INSTALL Thermostat 24VAC Transformer4ROUTE High Voltage and Ground Wires 3A. Route Control Wires TingRoute Control Wires Ting Typical XP17 Wiring Heat Pump Control A175 Jumpers and Terminals Heat Pump Control AGEHeat Pump Control A175 Jumper and Terminal Descriptions Field Control Wiring Flat metal jumperFurnace Control Unit Start−Up Connections for Testing and ChargingServicing Units Delivered Void of Charge System RefrigerantAdding or Removing Refrigerant Cooling Mode Indoor Airflow CheckHeating Mode Indoor Airflow Check Airflowindoor CoilUsing HFC−410A Weigh In Method Subcooling Charging MethodAir Handler / Coil Match ups and Targeted Subcooling Values Operating and Temperature Pressures PsigSystem Operations Defrost SystemResistor Location Sensor Temperature / Resistance Range Unit SensorsDefrost Calibration Sequence of Operations YESTest Pin E33 Functions S SLow Pressure S87 Switch Operation Or belowHigh Pressure Switch S4 Sequence of Operation Input Fault or Miswire Degrees Resistance Fahrenheit 136.3 2680 Resetting Fault and Lockout LED Codes System Status, Fault and Lockout LED CodesDS11 and DS14 ATUS, Fault Lockout LED Codes DS15 and DS13 Ault Lockout LED CodesAlert Status Moderate Device225ºF 107ºC Lockout Vice removed or Clears after FAN Motor B4 Test Procedure Field Configuration and TestingTroubleshooting FAN Motor Control A177 OPERATION,Fan Motor Control RPM, LED Code and DC Voltage Output Fan Motor Control Error/Fault LED CodesFan Motor Control Stage LED Indicator Codes Fan Motor Control Flash and Pause DurationsFAN Motor Position Adjustment TOP Grille or FAN Motor Mount Adjustment for FAN ClearanceTOP Grille Adjustment Demand BeginsFAN Motor Control A177 PULSE−WIDTH Modulation PWM Testing for External Power to Fan Motor Control Terminal StripStart FinishMaintenance Snow Guard Top CoverHomeowner SunSource Home Energy System Heating Mode XP17 Start−Up and Performance ChecklistCooling Mode START−UP Checks