Lennox International Inc Dave Lennox Signature Collection XP17 System HEAT PUMPS Demand Begins

Page 47

DEMAND

BEGINS

MISMATCHED

RPM

CRC FAILURE

DEFAULT FAN MOTOR SPEED

USED

DEFAULT FAN MOTOR SPEED USED

LED CONTINUOUS FAST

FLASH

LED CONSTANT ON

REPLACE FAN MOTOR CONTROL BOARD

REPLACE FAN MOTOR CONTROL BOARD

YES

SINGLE STAGE

OR EDA

OPERATION

NO

DEMAND

ENDED

ECM1/Y1

ONLY OR ECM2/Y2

ONLY

FAN MOTOR RPM SET PER JUMPER SETTINGS

STAGE LED INDICATOR: ONE SLOW FLASH AND ONE SHORT PAUSE FOR SINGLE STAGE OR EDA OPERATION

LED RPM INDICATOR:

EXAMPLE: (2−TON

UNIT) – 5 SLOW

FLASHES AND ONE

LONG PAUSE

Figure 32. Fan Motor Control One Stage LED Sequence of Operation

TOP GRILLE OR FAN MOTOR MOUNT ADJUSTMENT FOR FAN CLEARANCE

Sometimes during shipping, either the fan motor mounting or top grille may become out of alignment. This may cause the fan motor blade to not clear the orifice ring. If this situation occurs, simply adjust either or both the fan motor mount or top grille positions to allow proper clearance. The top grille four fastener insertion points to the plastic top and motor mount locations are larger than the fasteners used to secure the grille and fan motor mounts. Use the procedures provided in figure 33 to adjust for fan clearance.

GRILLE MOUNTING

PUSHPOINTS FORWARD

PUSH

FORWARD

FASTENER

INSERTION POINT

FAN MOTOR MOUNTING POINTS

The four mounting point holes that secure the top grille to the plastic top are larger than the fasteners used to secure the grille. this is also true for the four fasteners securing the fan motor to the top grille. To provide more clearance, preform either or both of the following procedures.

TOP GRILLE ADJUSTMENT

loosen the four grille mounting fasteners and push the grille forward. tighten mounting hardware. if there is still insufficient clearance proceed to Fan Motor Position Adjustment.

FAN MOTOR POSITION ADJUSTMENT

Loosen the four fan motor grille mounting fasteners and push the fan motor forward. tighten mounting hardware.

GRILLE MOUNTING POINTS

ORIFICE RING

Figure 33. Fan Blade Clearance Adjustment

Page 47

XP17 SERIES

Image 47
Contents Heat Pumps Table of ContentsGeneral Base with Elongated Legs Unit Dimensions −− Inches mmSide View Access View Model Number IdentificationControl BOX Typical Unit Parts ArrangementShipping and Packing List Using Manifold Gauge SetOperating Service Valves Reinstall Stem Cap Operating Angle Type Service ValveOperating Ball Type Service Valve To Access Service Port2CONNECT Manifold Gauge SET Recovering Refrigerant from Existing System1DISCONNECT Power Recovering RefrigerantUnit Placement Placement, Slab Mounting and Stabilizing Unit Detail a Outside Unit PlacementRoof Mounting Removing and Installing PanelsStabilizing Unit on Uneven Surfaces Detail D Detail a Louvered Panel InstallationLouvered Panel Removal Detail CRefrigerant Line SET New or Replacement Line SetRefrigerant Line SET Alling Horizontal Runs Refrigerant Line SET From Vertical to HorizontalBrazing Connections 2CAP and Core Removal 1PIPING Panel Removal and Preparing Line SET7PREPARATION for Next Step Wrap Service ValvesFlow Nitrogen Braze Line SETFlushing Line Set and Indoor Coil Flushing Line Set and Indoor CoilEqualizer Line Installation Installing Indoor Expansion ValveIndoor Expansion Valve Installation Sensing Bulb InstallationLeak Test Leak Test Line Set and Indoor CoilS S S S Evacuating Line Set and Indoor Coil24VAC Transformer Size Circuit and Install Disconnect2INSTALL Thermostat Electrical4ROUTE High Voltage and Ground Wires 3A. Route Control Wires TingRoute Control Wires Ting Typical XP17 Wiring Heat Pump Control AGE Heat Pump Control A175 Jumpers and TerminalsHeat Pump Control A175 Jumper and Terminal Descriptions Flat metal jumper Field Control WiringFurnace Control System Refrigerant Connections for Testing and ChargingServicing Units Delivered Void of Charge Unit Start−UpAirflowindoor Coil Cooling Mode Indoor Airflow CheckHeating Mode Indoor Airflow Check Adding or Removing RefrigerantSubcooling Charging Method Using HFC−410A Weigh In MethodAir Handler / Coil Match ups and Targeted Subcooling Values Psig Operating and Temperature PressuresDefrost System System OperationsUnit Sensors Resistor Location Sensor Temperature / Resistance RangeYES Defrost Calibration Sequence of OperationsS S Test Pin E33 FunctionsOr below Low Pressure S87 Switch OperationHigh Pressure Switch S4 Sequence of Operation Input Fault or Miswire Degrees Resistance Fahrenheit 136.3 2680 DS15 and DS13 Ault Lockout LED Codes System Status, Fault and Lockout LED CodesDS11 and DS14 ATUS, Fault Lockout LED Codes Resetting Fault and Lockout LED CodesModerate Device Alert Status225ºF 107ºC Lockout Vice removed or Clears after FAN Motor Control A177 OPERATION, Field Configuration and TestingTroubleshooting FAN Motor B4 Test ProcedureFan Motor Control Flash and Pause Durations Fan Motor Control Error/Fault LED CodesFan Motor Control Stage LED Indicator Codes Fan Motor Control RPM, LED Code and DC Voltage OutputDemand Begins TOP Grille or FAN Motor Mount Adjustment for FAN ClearanceTOP Grille Adjustment FAN Motor Position AdjustmentFAN Motor Control A177 PULSE−WIDTH Modulation PWM Testing for External Power to Fan Motor Control Finish StripStart TerminalSnow Guard Top Cover MaintenanceHomeowner SunSource Home Energy System START−UP Checks XP17 Start−Up and Performance ChecklistCooling Mode Heating Mode