Lennox International Inc 506586-01 Adding or Removing Refrigerant, Airflowindoor Coil

Page 28

ADDING OR REMOVING REFRIGERANT

This system uses HFC−410A refrigerant which operates at much higher pressures than HCFC−22. The pre−installed liquid line filter drier is approved for use with HFC−410A only. Do not replace it with components designed for use with HCFC−22.

COOLING MODE INDOOR AIRFLOW CHECK

Check airflow using the Delta−T (DT) process using the illustration in figure 20.

HEATING MODE INDOOR AIRFLOW CHECK

Blower airflow (CFM) may be calculated by energizing electric heat and measuring:

STemperature rise between the return air and supply air temperatures at the indoor coil blower unit,

SMeasuring voltage supplied to the unit,

SMeasuring amperage being drawn by the heat unit(s).

Then, apply the measurements taken in following formula to determine CFM:

Amps x Volts x 3.41

CFM =

1.08 x Temperature rise (F)

AIRFLOWINDOOR COIL

 

 

DT

TEMPERATURE OF AIR

 

 

 

80 24 24 24 23 23 22 22 22 20 19 18 17 16 15

ENTERING INDOOR COIL ºF

 

 

DRY−BULB

78 23 23 23 22 22 21 21 20 19 18 17 16 15 14

 

76 22 22 22 21 21 20 19 19 18 17 16 15 14 13

 

 

 

 

74 21 21 21 20 19 19 18 17 16 16 15 14 13 12

A

 

72 20 20 19 18 17 17 16 15 15 14 13 12 11 10

 

 

70 19 19 18 18 17 17 16 15 15 14 13 12 11 10

WET−BULB ºF

57 58 59 60 61 62 63 64 65 66 67 68 69 70

DRY

 

 

B

BULB

 

 

 

C TDROP

53º

19º

AIR FLOW

AIR FLOW

A

72º

B

64º

All temperatures are expressed in ºF

INDOOR COIL

DRY BULB

 

 

 

 

 

 

 

 

WET BULB

Use the following procedure to adjust for optimal air flow across the indoor coil:

1. DETERMINE THE DESIRED DT

 

 

TURE USING DRY BULB (A) AND WET BULB (B). DT IS THE INTERSECTING VALUE

OF A AND B IN THE TABLE (SEE TRIANGLE).

 

 

2. Find temperature drop across coil

 

A and C). Temperature Drop Formula:

(TDrop) = A minus C.

 

 

 

 

 

3. Determine if fan needs adjustment

ference between the measured TDrop and the desired DT (TDropDT) is within +3º, no adjustment

is needed. See example below:

 

 

 

 

 

 

ASSUME DT = 15 AND A TEMP. = 72º, THESE C TEMPERATURES WOULD NECESSITATE STATED ACTIONS:

TDROP

DT

=

ºF

ACTION

 

Changing air flow affects all temperatures; recheck temperatures to

 

 

 

 

 

 

 

 

53º

19

15

=

4

INCREASE THE AIRFLOW

confirm that the temperature drop and DT are within +3º.

58º

14

15

=

−1

(WITHIN +3º RANGE) NO CHANGE

 

62º

10

15

=

−5

DECREASE THE AIRFLOW

 

4.ADJUST THE FAN SPEED

Figure 20. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart Formula

Page 28

506586−01 10/10

Image 28
Contents General Table of ContentsHeat Pumps Unit Dimensions −− Inches mm Side View Access ViewModel Number Identification Base with Elongated LegsTypical Unit Parts Arrangement Control BOXOperating Service Valves Using Manifold Gauge SetShipping and Packing List Operating Angle Type Service Valve Operating Ball Type Service ValveTo Access Service Port Reinstall Stem CapRecovering Refrigerant from Existing System 1DISCONNECT PowerRecovering Refrigerant 2CONNECT Manifold Gauge SETUnit Placement Detail a Outside Unit Placement Placement, Slab Mounting and Stabilizing UnitStabilizing Unit on Uneven Surfaces Removing and Installing PanelsRoof Mounting Louvered Panel Installation Louvered Panel RemovalDetail C Detail D Detail aNew or Replacement Line Set Refrigerant Line SETRefrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections 1PIPING Panel Removal and Preparing Line SET 2CAP and Core RemovalWrap Service Valves Flow NitrogenBraze Line SET 7PREPARATION for Next StepFlushing Line Set and Indoor Coil Flushing Line Set and Indoor CoilInstalling Indoor Expansion Valve Indoor Expansion Valve InstallationSensing Bulb Installation Equalizer Line InstallationLeak Test Line Set and Indoor Coil Leak TestEvacuating Line Set and Indoor Coil S S S SSize Circuit and Install Disconnect 2INSTALL ThermostatElectrical 24VAC TransformerRoute Control Wires Ting 3A. Route Control Wires Ting4ROUTE High Voltage and Ground Wires Typical XP17 Wiring Heat Pump Control A175 Jumpers and Terminals Heat Pump Control AGEHeat Pump Control A175 Jumper and Terminal Descriptions Field Control Wiring Flat metal jumperFurnace Control Connections for Testing and Charging Servicing Units Delivered Void of ChargeUnit Start−Up System RefrigerantCooling Mode Indoor Airflow Check Heating Mode Indoor Airflow CheckAdding or Removing Refrigerant Airflowindoor CoilUsing HFC−410A Weigh In Method Subcooling Charging MethodAir Handler / Coil Match ups and Targeted Subcooling Values Operating and Temperature Pressures PsigSystem Operations Defrost SystemResistor Location Sensor Temperature / Resistance Range Unit SensorsDefrost Calibration Sequence of Operations YESTest Pin E33 Functions S SLow Pressure S87 Switch Operation Or belowHigh Pressure Switch S4 Sequence of Operation Input Fault or Miswire Degrees Resistance Fahrenheit 136.3 2680 System Status, Fault and Lockout LED Codes DS11 and DS14 ATUS, Fault Lockout LED CodesResetting Fault and Lockout LED Codes DS15 and DS13 Ault Lockout LED CodesAlert Status Moderate Device225ºF 107ºC Lockout Vice removed or Clears after Field Configuration and Testing TroubleshootingFAN Motor B4 Test Procedure FAN Motor Control A177 OPERATION,Fan Motor Control Error/Fault LED Codes Fan Motor Control Stage LED Indicator CodesFan Motor Control RPM, LED Code and DC Voltage Output Fan Motor Control Flash and Pause DurationsTOP Grille or FAN Motor Mount Adjustment for FAN Clearance TOP Grille AdjustmentFAN Motor Position Adjustment Demand BeginsFAN Motor Control A177 PULSE−WIDTH Modulation PWM Testing for External Power to Fan Motor Control Strip StartTerminal FinishMaintenance Snow Guard Top CoverHomeowner SunSource Home Energy System XP17 Start−Up and Performance Checklist Cooling ModeHeating Mode START−UP Checks