Lennox International Inc Dave Lennox Signature Collection XP17 System HEAT PUMPS Unit Placement

Page 7

CLEARANCE ON ALL SIDES

MINIMUM CLEARANCE

ABOVE UNIT

6 (152)

ACCESS PANEL

CONTROL PANEL ACCESS

LOCATION 30 (762)

12 (305)

 

 

LINE SET

36 (914)

CONNECTIONS

NOTES:

SCLEARANCE TO ONE OF THE OTHER THREE SIDES MUST BE 36 INCHES (914MM).

SCLEARANCE TO ONE OF THE REMAINING TWO SIDES MAY BE 12 INCHES (305MM) AND THE FINAL SIDE MAY BE 6 INCHES (152MM).

48 (1219)

MINIMUM CLEARANCE BETWEEN

TWO UNITS

24 (610)

ACCESS PANEL

LINE SET

CONNECTIONS

REAR VIEW OF UNIT

Figure 4. Installation Clearances

Unit Placement

CAUTION

In order to avoid injury, take proper precaution when lift- ing heavy objects.

See Unit Dimensions on page 3 for sizing mounting slab, platforms or supports. Refer to figure 4 for mandatory installation clearance requirements.

POSITIONING CONSIDERATIONS

Consider the following when positioning the unit:

SSome localities are adopting sound ordinances based on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.

SWhen possible, do not install the unit directly outside a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 5, detail A.

PLACING UNIT ON SLAB

When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 5, detail B.

NOTE If necessary for stability, anchor unit to slab as described in figure 5, detail D.

ELEVATING THE UNIT

Units are outfitted with elongated support feet as illustrated in figure 5, detail C.

If additional elevation is necessary, raise the unit by extending the height of the unit support feet. This may be achieved by using a 2 inch (50.8mm) Schedule 40 female threaded adapter.

The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2−inch (50.8mm) Schedule 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit.

NOTE eep the height of ext enders short enough to

ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights.

Page 7

XP17 SERIES

Image 7
Contents General Table of ContentsHeat Pumps Base with Elongated Legs Unit Dimensions −− Inches mmSide View Access View Model Number IdentificationControl BOX Typical Unit Parts ArrangementOperating Service Valves Using Manifold Gauge SetShipping and Packing List Reinstall Stem Cap Operating Angle Type Service ValveOperating Ball Type Service Valve To Access Service Port2CONNECT Manifold Gauge SET Recovering Refrigerant from Existing System1DISCONNECT Power Recovering RefrigerantUnit Placement Placement, Slab Mounting and Stabilizing Unit Detail a Outside Unit PlacementStabilizing Unit on Uneven Surfaces Removing and Installing PanelsRoof Mounting Detail D Detail a Louvered Panel InstallationLouvered Panel Removal Detail CRefrigerant Line SET New or Replacement Line SetRefrigerant Line SET Alling Horizontal Runs Refrigerant Line SET From Vertical to HorizontalBrazing Connections 2CAP and Core Removal 1PIPING Panel Removal and Preparing Line SET7PREPARATION for Next Step Wrap Service ValvesFlow Nitrogen Braze Line SETFlushing Line Set and Indoor Coil Flushing Line Set and Indoor CoilEqualizer Line Installation Installing Indoor Expansion ValveIndoor Expansion Valve Installation Sensing Bulb InstallationLeak Test Leak Test Line Set and Indoor CoilS S S S Evacuating Line Set and Indoor Coil24VAC Transformer Size Circuit and Install Disconnect2INSTALL Thermostat ElectricalRoute Control Wires Ting 3A. Route Control Wires Ting4ROUTE High Voltage and Ground Wires Typical XP17 Wiring Heat Pump Control AGE Heat Pump Control A175 Jumpers and TerminalsHeat Pump Control A175 Jumper and Terminal Descriptions Flat metal jumper Field Control WiringFurnace Control System Refrigerant Connections for Testing and ChargingServicing Units Delivered Void of Charge Unit Start−UpAirflowindoor Coil Cooling Mode Indoor Airflow CheckHeating Mode Indoor Airflow Check Adding or Removing RefrigerantSubcooling Charging Method Using HFC−410A Weigh In MethodAir Handler / Coil Match ups and Targeted Subcooling Values Psig Operating and Temperature PressuresDefrost System System OperationsUnit Sensors Resistor Location Sensor Temperature / Resistance RangeYES Defrost Calibration Sequence of OperationsS S Test Pin E33 FunctionsOr below Low Pressure S87 Switch OperationHigh Pressure Switch S4 Sequence of Operation Input Fault or Miswire Degrees Resistance Fahrenheit 136.3 2680 DS15 and DS13 Ault Lockout LED Codes System Status, Fault and Lockout LED CodesDS11 and DS14 ATUS, Fault Lockout LED Codes Resetting Fault and Lockout LED CodesModerate Device Alert Status225ºF 107ºC Lockout Vice removed or Clears after FAN Motor Control A177 OPERATION, Field Configuration and TestingTroubleshooting FAN Motor B4 Test ProcedureFan Motor Control Flash and Pause Durations Fan Motor Control Error/Fault LED CodesFan Motor Control Stage LED Indicator Codes Fan Motor Control RPM, LED Code and DC Voltage OutputDemand Begins TOP Grille or FAN Motor Mount Adjustment for FAN ClearanceTOP Grille Adjustment FAN Motor Position AdjustmentFAN Motor Control A177 PULSE−WIDTH Modulation PWM Testing for External Power to Fan Motor Control Finish StripStart TerminalSnow Guard Top Cover MaintenanceHomeowner SunSource Home Energy System START−UP Checks XP17 Start−Up and Performance ChecklistCooling Mode Heating Mode