Lennox International Inc 506586-01 installation instructions Leak Test Line Set and Indoor Coil

Page 18

IMPORTANT

The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.

Leak Test Line Set and Indoor Coil

IMPORTANT

Leak detector must be capable of sensing HFC refrigerant.

IMPORTANT

If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity.

Failure to properly flush the system per the instructions below will void the warranty.

WARNING

When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).

WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.

Failure to follow this warning may result in personal injury or death.

1CONNECT GAUGE SET

AConnect an HFC−410A manifold gauge set high pressure hose to the vapor valve service port.

NOTE , the high pressure hose is connected to

the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.

BWith both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set.

NOTE Later in the procedure, the HFC−410A container will be replaced by the nitrogen container.

LOW

B

HIGH

MANIFOLD GAUGE SET

OUTDOOR UNIT

A

TO VAPOR

SERVICE VALVE

NITROGEN

HFC−410A

2TEST FOR LEAKS

After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:

A With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC−410A cylinder (vapor only).

B Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.

C Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.

D Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.

E After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector.

F After leak testing disconnect gauges from service ports.

Figure 13. Leak Test

Page 18

506586−01 10/10

Image 18
Contents Table of Contents GeneralHeat Pumps Model Number Identification Unit Dimensions −− Inches mmSide View Access View Base with Elongated LegsTypical Unit Parts Arrangement Control BOXUsing Manifold Gauge Set Operating Service ValvesShipping and Packing List To Access Service Port Operating Angle Type Service ValveOperating Ball Type Service Valve Reinstall Stem CapRecovering Refrigerant Recovering Refrigerant from Existing System1DISCONNECT Power 2CONNECT Manifold Gauge SETUnit Placement Detail a Outside Unit Placement Placement, Slab Mounting and Stabilizing UnitRemoving and Installing Panels Stabilizing Unit on Uneven SurfacesRoof Mounting Detail C Louvered Panel InstallationLouvered Panel Removal Detail D Detail aNew or Replacement Line Set Refrigerant Line SETRefrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections 1PIPING Panel Removal and Preparing Line SET 2CAP and Core RemovalBraze Line SET Wrap Service ValvesFlow Nitrogen 7PREPARATION for Next StepFlushing Line Set and Indoor Coil Flushing Line Set and Indoor CoilSensing Bulb Installation Installing Indoor Expansion ValveIndoor Expansion Valve Installation Equalizer Line InstallationLeak Test Line Set and Indoor Coil Leak TestEvacuating Line Set and Indoor Coil S S S SElectrical Size Circuit and Install Disconnect2INSTALL Thermostat 24VAC Transformer3A. Route Control Wires Ting Route Control Wires Ting4ROUTE High Voltage and Ground Wires Typical XP17 Wiring Heat Pump Control A175 Jumpers and Terminals Heat Pump Control AGEHeat Pump Control A175 Jumper and Terminal Descriptions Field Control Wiring Flat metal jumperFurnace Control Unit Start−Up Connections for Testing and ChargingServicing Units Delivered Void of Charge System RefrigerantAdding or Removing Refrigerant Cooling Mode Indoor Airflow CheckHeating Mode Indoor Airflow Check Airflowindoor CoilUsing HFC−410A Weigh In Method Subcooling Charging MethodAir Handler / Coil Match ups and Targeted Subcooling Values Operating and Temperature Pressures PsigSystem Operations Defrost SystemResistor Location Sensor Temperature / Resistance Range Unit SensorsDefrost Calibration Sequence of Operations YESTest Pin E33 Functions S SLow Pressure S87 Switch Operation Or belowHigh Pressure Switch S4 Sequence of Operation Input Fault or Miswire Degrees Resistance Fahrenheit 136.3 2680 Resetting Fault and Lockout LED Codes System Status, Fault and Lockout LED CodesDS11 and DS14 ATUS, Fault Lockout LED Codes DS15 and DS13 Ault Lockout LED CodesAlert Status Moderate Device225ºF 107ºC Lockout Vice removed or Clears after FAN Motor B4 Test Procedure Field Configuration and TestingTroubleshooting FAN Motor Control A177 OPERATION,Fan Motor Control RPM, LED Code and DC Voltage Output Fan Motor Control Error/Fault LED CodesFan Motor Control Stage LED Indicator Codes Fan Motor Control Flash and Pause DurationsFAN Motor Position Adjustment TOP Grille or FAN Motor Mount Adjustment for FAN ClearanceTOP Grille Adjustment Demand BeginsFAN Motor Control A177 PULSE−WIDTH Modulation PWM Testing for External Power to Fan Motor Control Terminal StripStart FinishMaintenance Snow Guard Top CoverHomeowner SunSource Home Energy System Heating Mode XP17 Start−Up and Performance ChecklistCooling Mode START−UP Checks