Slant/Fin J-390 installation instructions III. Initial Start, Instructions, Safety Information

Page 35

Jaguar Model J-390

35

 

 

 

III. INITIAL START

Safe lighting and other performance criteria were met when testing various gas manifold and control assemblies used on the Jaguar J-390 boiler under the ANSI Z21.13 - latest edition.

Instructions

Follow the lighting instructions in this manual. These instructions are also attached to the boiler.

TURN 90˚

TO OPEN

TURN 90˚

TO CLOSE

GAS SUPPLY SHUTOFF VALVE

GAS SUPPLY SHUTOFF VALVE

IN "OPEN" POSITION

IN "CLOSED" POSITION

Figure 24. Gas supply shutoff valve operation.

SAFETY INFORMATION

For Your Safety Read Before Operating

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

A.This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. DO NOT try to light the burner by hand.

B.BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS:

DO NOT try to light any appliance.

DO NOT touch any electric switch: DO NOT use any phone in your building.

Immediately call you gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

C.Use only your hand to turn the gas supply shut-off valve. Never use tools. If the supply shut-off valve will not turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D.DO NOT use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

OPERATING INSTRUCTIONS

1.STOP! Read the safety information above.

2.Set the thermostat to lowest setting.

3.Turn off all electric power to the appliance.

4.This appliance is equipped with an ignition device which automatically lights the burner. DO NOT try to light the burner by hand.

5.Open the gas supply shut-off valve, by turning the handle to be parallel to the gas piping (See Figure 24).

6.Wait five (5) minutes (longer for propane) to clear out any gas, then smell for gas, including near the floor. If you then smell gas, STOP! Follow “B” in the safety information above on this page. If you don’t smell gas, go to next step.

7.Turn on all electric power to the appliance.

8.Set thermostat to desired setting.

If the appliance will not operate, follow the instructions “To Turn Off Gas to Appliance” and call your service technician or gas supplier.

TO TURN OFF GAS TO APPLIANCE

1.Set thermostat to lowest setting.

2.Turn off all electric power to the appliance if service is to be performed.

3.Close the gas supply shut off valve, by turning the handle to be perpendicular to the gas piping. (See Figure 24).

Image 35
Contents Installation and Operating Instructions Jaguar J-390 Boiler Ratings and DimensionsLocation and identification of parts Location and Identification of PartsMinimum Clearances from Combustible Constructions SafetyBoiler Location Boiler FoundationProducts to Avoid NON-DIRECT Vent InstallationDirect Vent Installation Contamination PreventionVent and AIR Intake Materials Flue GAS Venting RequirementsVent and AIR Intake Restrictions PVC/CPVC Pipe General Assembly MethodNON-DIRECT Vent Vertical Venting Venting InstallationSidewall Venting NON-DIRECT Vent Vent Termination Location and Clearances10 MAX Jaguar J-390 NON-DIRECT VENT, Sidewall VentingFT. MIN Jaguar J-390 NON-DIRECT VENT, Venting Through a RoofFT. MIN Thick Wall Jaguar J-390 Direct VENT, Sidewall VentingDIA PVC/CPVC Pipe for Vent Combustion Screw Jaguar Model J-390 FT. MIN Direct Vent Venting and AIR Intake Through a RoofGAS Piping Venting and AIR Intake System Regular InspectionCondensate Removal System Commonwealth of Massachusetts Special RequirementOutdoor AIR Sensor Electrical WiringSpace Heating Thermostats Domestic HOT Water Tank Thermostat101112 Boiler Control 120V 3 4 5 6 7 3 4 5 6 7 Thermostat Water Piping Water Outlet Piping Feet w.c JaguarTank Piping Zoning with circulators Zoning with zone valves Piping a heating-cooling system to the boiler and a chiller Before Firing BOILER, make these checks View and Changing TemperaturesViewing and changing system setting Operating Instructions Filling and Venting Water SystemsBoiler Operation Status Jaguar Boiler Display BoardIf outdoor sensor is used Viewing and Changing TemperaturesBoiler model selection, value is 5 for model J-390 Water To Turn OFF GAS to Appliance Safety InformationIII. Initial Start InstructionsJaguar Model J-390 Sequence of Operation IV. Check Combustion and Fuel Input Rate Gas valve adjustmentCheck for gas leaks Safety CheckControl Safety Shutdown test VI. Diagnostic Error Codes19, 42 Going to the sensor, or replace the sensor. If no sen If Replacement Parts are Needed Care and MaintenanceGeneral Maintenance III. CleaningGeneral Troubleshooting Guide for Service Personnel Jaguar Model J-390 SLANT/FIN CORPORATION, Greenvale, N.Y Phone 516