Jaguar Model J-390

V. SAFETY CHECK

A.Check for gas leaks:

Using soap solution, check for gas leaks from meter to gas valve including all pipes and fittings and gas valve connections. Use liquid soap solution for all gas testing. DO NOT use open flame.

B.Thermostat Test:

Set thermostat setting to low enough to end call for heat. Gas valve should close and burner should stop firing. Blower and circulator pump should go into a post purge, then shut off.

C.Control Safety Shutdown test:

With the burner firing, disconnect the spark cable from the spark ignitor. Gas valve should close and burner should stop firing. The boiler will try for ignition three times after this, then should lock out with an “A 01” error shown on the display. Reconnect the spark cable to the spark ignitor, and press the “Reset” button to return to normal operation.

VI. DIAGNOSTIC ERROR CODES

WARNING: Only a trained, experienced service technician should perform troubleshooting. Turn off all electric power to the boiler before service.

A.LOCKOUT ERRORS: Indicated by an “A” in the mode display. The reset button must be pressed to clear the error and retry operation. The temperature display shows the error code.

ERROR CODE

INDICATION

REMEDY

 

 

 

 

 

Check for steady sparking at electrodes. If spark not

01

Ignition Failure - 3 unsuccessful

steady - check spark gap to be .125”, clean or replace

spark ignitor, check power supply voltage and grounding.

 

ignition attempts in a row.

If spark is steady - check for proper gas supply pressure.

 

 

 

 

Check combustion, if able to ignite, or replace gas valve.

 

 

 

 

Flame Failure - 3 losses of flame

Check for proper combustion, at both max. and min.

02

input firing rates. If combustion is within the range

signal during one demand.

specified on page 37, clean or replace spark ignitor,

 

 

 

check power supply voltage and grounding.

 

 

 

03

 

Check to see if the water outlet temperature reaches

Water High Limit Open

203˚F. If it does, replace the water outlet 12k ohm

 

 

sensor. If it does not, replace the water high limit switch.

 

 

 

04, 05, 09, 10,

 

Replace control board. Make sure the proper boiler

12, 13, 14, 15,

Control Failure

model selection and confirmation code is entered.

16, 18, 32

 

See Table 5 on page 33.

 

 

 

 

 

19, 20

 

If a flame is still observed after a call for heat is stopped,

Flame Detected at Wrong Time

replace the gas valve. If the burner seems to be shutting

 

 

down properly, replace the spark ignitor.

 

 

 

33

Fan Failure - RPM error

Check wire harness connections going to the blower.

Replace blower.

 

 

 

 

 

Image 38
Contents Installation and Operating Instructions Ratings and Dimensions Jaguar J-390 BoilerLocation and Identification of Parts Location and identification of partsBoiler Foundation SafetyBoiler Location Minimum Clearances from Combustible ConstructionsContamination Prevention NON-DIRECT Vent InstallationDirect Vent Installation Products to AvoidFlue GAS Venting Requirements Vent and AIR Intake MaterialsPVC/CPVC Pipe General Assembly Method Vent and AIR Intake RestrictionsVent Termination Location and Clearances Venting InstallationSidewall Venting NON-DIRECT Vent NON-DIRECT Vent Vertical VentingJaguar J-390 NON-DIRECT VENT, Sidewall Venting 10 MAXJaguar J-390 NON-DIRECT VENT, Venting Through a Roof FT. MINFT. MIN Jaguar J-390 Direct VENT, Sidewall Venting Thick WallDIA PVC/CPVC Pipe for Vent Combustion Screw Jaguar Model J-390 Direct Vent Venting and AIR Intake Through a Roof FT. MINCommonwealth of Massachusetts Special Requirement Venting and AIR Intake System Regular InspectionCondensate Removal System GAS PipingDomestic HOT Water Tank Thermostat Electrical WiringSpace Heating Thermostats Outdoor AIR Sensor101112 Boiler Control 120V 3 4 5 6 7 3 4 5 6 7 Thermostat Water Piping Water Outlet Piping Feet w.c JaguarTank Piping Zoning with circulators Zoning with zone valves Piping a heating-cooling system to the boiler and a chiller Operating Instructions Filling and Venting Water Systems View and Changing TemperaturesViewing and changing system setting Before Firing BOILER, make these checksJaguar Boiler Display Board Boiler Operation StatusViewing and Changing Temperatures If outdoor sensor is usedBoiler model selection, value is 5 for model J-390 Water Instructions Safety InformationIII. Initial Start To Turn OFF GAS to ApplianceJaguar Model J-390 Sequence of Operation Gas valve adjustment IV. Check Combustion and Fuel Input RateVI. Diagnostic Error Codes Safety CheckControl Safety Shutdown test Check for gas leaks19, 42 Going to the sensor, or replace the sensor. If no sen III. Cleaning Care and MaintenanceGeneral Maintenance If Replacement Parts are NeededGeneral Troubleshooting Guide for Service Personnel Jaguar Model J-390 SLANT/FIN CORPORATION, Greenvale, N.Y Phone 516