B.BLOCKING ERRORS: Indicated by an “E” in the mode display. Operation is automatically restored, once the condition returns to normal or is fixed. The temperature display shows the error code. Pressing the “Reset” button is not required.

ERROR CODE

INDICATION

REMEDY

 

 

 

01

 

Check wire harness connections going to the

Water Outlet Sensor Open

sensor.

 

 

Replace the sensor.

 

 

 

02

 

Check wire harness connections going to the

Water Inlet Sensor Open

sensor.

 

 

Replace the sensor.

 

 

 

03

Flue Gas Sensor Open

Check wire harness connections going to the

sensor.

 

 

Replace the sensor.

 

 

 

11

Water Outlet Sensor Shorted

Replace the sensor.

 

 

 

12

Water Inlet Sensor Shorted

Replace the sensor.

 

 

 

13

Flue Gas Sensor Shorted

Replace the sensor.

 

 

 

19, 42, 45,

 

Replace control board. Make sure the proper

Control Failure

boiler model selection and confirmation code is

46, 47, 48

 

entered. See Table 5 on page 33.

 

 

 

 

 

If a flame is still observed after a call for heat is

20

Flame Detected at Wrong Time

stopped, replace the gas valve, If the burner

seems to be shutting down properly, replace the

 

 

 

 

spark ignitor.

 

 

 

21

Polarity Error

Reverse the hot and neutral power supply wires.

 

 

 

22

 

Check power supply frequency to be 60 hz,

Frequency Error

certain power supplies may not provide the

 

 

proper frequency.

 

 

 

24

Earth Connection Faulty

Check grounding of control and boiler chassis.

 

 

 

continued on page 39

Image 39
Contents Installation and Operating Instructions Jaguar J-390 Boiler Ratings and DimensionsLocation and identification of parts Location and Identification of PartsMinimum Clearances from Combustible Constructions SafetyBoiler Location Boiler FoundationProducts to Avoid NON-DIRECT Vent InstallationDirect Vent Installation Contamination PreventionVent and AIR Intake Materials Flue GAS Venting RequirementsVent and AIR Intake Restrictions PVC/CPVC Pipe General Assembly MethodNON-DIRECT Vent Vertical Venting Venting InstallationSidewall Venting NON-DIRECT Vent Vent Termination Location and Clearances10 MAX Jaguar J-390 NON-DIRECT VENT, Sidewall VentingFT. MIN Jaguar J-390 NON-DIRECT VENT, Venting Through a RoofFT. MIN Thick Wall Jaguar J-390 Direct VENT, Sidewall VentingDIA PVC/CPVC Pipe for Vent Combustion Screw Jaguar Model J-390 FT. MIN Direct Vent Venting and AIR Intake Through a RoofGAS Piping Venting and AIR Intake System Regular InspectionCondensate Removal System Commonwealth of Massachusetts Special RequirementOutdoor AIR Sensor Electrical WiringSpace Heating Thermostats Domestic HOT Water Tank Thermostat101112 Boiler Control 120V 3 4 5 6 7 3 4 5 6 7 Thermostat Water Piping Water Outlet Piping Jaguar Tank PipingFeet w.c Zoning with circulators Zoning with zone valves Piping a heating-cooling system to the boiler and a chiller Before Firing BOILER, make these checks View and Changing TemperaturesViewing and changing system setting Operating Instructions Filling and Venting Water SystemsBoiler Operation Status Jaguar Boiler Display BoardIf outdoor sensor is used Viewing and Changing TemperaturesBoiler model selection, value is 5 for model J-390 Water To Turn OFF GAS to Appliance Safety InformationIII. Initial Start InstructionsJaguar Model J-390 Sequence of Operation IV. Check Combustion and Fuel Input Rate Gas valve adjustmentCheck for gas leaks Safety CheckControl Safety Shutdown test VI. Diagnostic Error Codes19, 42 Going to the sensor, or replace the sensor. If no sen If Replacement Parts are Needed Care and MaintenanceGeneral Maintenance III. CleaningGeneral Troubleshooting Guide for Service Personnel Jaguar Model J-390 SLANT/FIN CORPORATION, Greenvale, N.Y Phone 516