Slant/Fin installation instructions Boiler model selection, value is 5 for model J-390

Page 33

Jaguar Model J-390

33

 

 

 

VIEWING AND CHANGING SYSTEM SETTING - Table 5

“To change system setting or perform system test”

The menu is accessed by pressing and holding “SELECT” and “ENTER” buttons for 10 seconds. To change

system setting: Press “UP or DOWN” button, then press “ENTER”

WARNING: Only a trained, experienced service technician or installer should use this table.

Table 2

Table 1

Table 2

Table 1

Table 3

Table 1

Table 1

Tablle 1

Table 1

Table 3

Table 3

Table 3

Table 3

Table 3

Table 3

Table 3

Table 3

MODE DISPLAY

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Changing space heating post pump time. Settable from 10 to 900 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(steps of 10 seconds). The default value is 30 seconds.

 

 

 

 

 

 

 

 

 

 

Table 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Changing DHW post pump time. Settable from 1 to 255 seconds.

Table 3

 

 

(steps of 1 seconds). The default value is 15 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Changing space heating control mode

 

 

 

 

 

 

 

 

 

*

0: Thermostat only (default) - boiler without outdoor sensor

 

 

 

 

 

 

 

 

 

1: Outside sensor and Thermostat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2: Outside sensor only

 

 

 

 

 

 

 

 

 

 

3: Permanent heat demand (boiler circulator always on)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Changing domestic hot water (DHW) mode

 

 

 

 

 

 

 

 

 

 

0: No DHW

 

 

 

 

 

 

 

 

*

1: Storage tank with sensor

 

 

 

 

 

 

 

 

2: Storage tank with thermostat (default value)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3: Plate heat exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Changing DHW or space heating priority mode

 

 

 

 

 

 

 

 

*

0: DHW priority (no time limit)

 

 

 

 

 

 

 

 

1: Space heating priority (no time limit)

Table 3

 

 

2: DHW priority for limited time (default)

Table 3

 

 

 

 

3: Space heating priority for limited time

 

 

 

 

 

 

 

 

 

 

Tablle 3

 

 

 

Table 3

*

Changing priority limited time. Settable from 20 to 80 minutes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The default value is 30 minutes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Boiler model selection, value is 5 for model J-390

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Boiler model confirmation, value is 5 for model J-390

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Weather compensation supply water reference temperature

 

 

 

 

 

 

 

 

(space heating mode 1 or 2). Settable from 16˚F to 122˚F (steps of 1 F).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The default value is 86˚F.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Changing compensation slope (space heating mode 1 or 2).

 

 

 

 

 

 

 

 

Settable from 0.1 to 5.0 (steps of 0.1).

 

 

 

 

 

 

 

 

 

 

The default value is 1.0.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Not Utilized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Changing weather compensation set point (space heating mode 2 only).

 

 

 

 

 

 

 

 

Settable from 32˚F to 122˚F (steps of 1˚F).

 

 

 

 

 

 

 

 

 

 

The default value is 68˚F.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

Display shows blower RPM (mutiply reading by 10 for actual RPM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Change blower RPM for high input (steps of 30 RPM, limit +/- 480 RPM).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

Change blower RPM for low input (steps of 30 RPM, limit +/- 120 RPM).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

Display shows flame current in micro amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

System test – Display shows flame current

 

 

 

 

 

 

 

 

0: System test off

 

 

 

 

 

 

 

 

 

 

L: Steady low input (20 minutes)

 

 

 

 

 

 

 

 

 

 

I: Steady ignition input (20 minutes)

 

 

 

 

 

 

 

 

 

 

H: Steady high input (20 minutes)

 

 

 

 

 

 

 

 

 

 

 

NOTE: *: Alternating **: Steady

Image 33
Contents Installation and Operating Instructions Jaguar J-390 Boiler Ratings and DimensionsLocation and identification of parts Location and Identification of PartsBoiler Location SafetyBoiler Foundation Minimum Clearances from Combustible ConstructionsDirect Vent Installation NON-DIRECT Vent InstallationContamination Prevention Products to AvoidVent and AIR Intake Materials Flue GAS Venting RequirementsVent and AIR Intake Restrictions PVC/CPVC Pipe General Assembly MethodSidewall Venting NON-DIRECT Vent Venting InstallationVent Termination Location and Clearances NON-DIRECT Vent Vertical Venting10 MAX Jaguar J-390 NON-DIRECT VENT, Sidewall VentingFT. MIN Jaguar J-390 NON-DIRECT VENT, Venting Through a RoofFT. MIN Thick Wall Jaguar J-390 Direct VENT, Sidewall VentingDIA PVC/CPVC Pipe for Vent Combustion Screw Jaguar Model J-390 FT. MIN Direct Vent Venting and AIR Intake Through a RoofCondensate Removal System Venting and AIR Intake System Regular InspectionCommonwealth of Massachusetts Special Requirement GAS PipingSpace Heating Thermostats Electrical WiringDomestic HOT Water Tank Thermostat Outdoor AIR Sensor101112 Boiler Control 120V 3 4 5 6 7 3 4 5 6 7 Thermostat Water Piping Water Outlet Piping Jaguar Tank PipingFeet w.c Zoning with circulators Zoning with zone valves Piping a heating-cooling system to the boiler and a chiller Viewing and changing system setting View and Changing TemperaturesOperating Instructions Filling and Venting Water Systems Before Firing BOILER, make these checksBoiler Operation Status Jaguar Boiler Display BoardIf outdoor sensor is used Viewing and Changing TemperaturesBoiler model selection, value is 5 for model J-390 Water III. Initial Start Safety InformationInstructions To Turn OFF GAS to ApplianceJaguar Model J-390 Sequence of Operation IV. Check Combustion and Fuel Input Rate Gas valve adjustmentControl Safety Shutdown test Safety CheckVI. Diagnostic Error Codes Check for gas leaks19, 42 Going to the sensor, or replace the sensor. If no sen General Maintenance Care and MaintenanceIII. Cleaning If Replacement Parts are NeededGeneral Troubleshooting Guide for Service Personnel Jaguar Model J-390 SLANT/FIN CORPORATION, Greenvale, N.Y Phone 516