R
Mt. Vernon Pellet Insert (AE)
H. Prefabricated Metal Chimney
The chimney can be new or existing, masonry or prefabricated and must meet the following minimum requirements:
•Must be minimum 6 inch (152mm) inside diameter of high temperature chimney listed to UL 103 HT (2100oF) or
•Must use components required by the manufacturer for installation.
•Must maintain clearances required by the manufacturer for installation.
•Refer to manufacturers instructions for installation
•This insert is listed to ASTM E 1509 Standard and is approved for installation into listed
•The original
•If the chimney is not listed as meeting HT requirements, or if the factory built fi replace was tested prior to 1998, a full height listed chimney liner must be installed from the appliance fl ue collar to the chimney top.
•The liner must be securely attached to the insert fl ue collar and the chimney top.
•The air fl ow of the
•No dilution air is allowed to enter the chimney.
1.Secure the fi replace damper in the open position. If this cannot be accomplished, it will be necessary to remove the damper
2.Seal damper area of chimney around chimney connector with a high temperature sealant or seal insert against the face of the fi replace.
3.Both methods must be removable and replaceable for cleaning and
I. Altering the Factory-Built Fireplace
•The fireplace must not be altered, except for the exceptions listed below. Do not remove the bricks and mortar from the existing fi replace.
The following modifi cations are permissible:
•Removal of damper or locked in open position
•Removal of smoke shelf or baffl e
•Removal of ember catches
•Removel of fi re grate
•Removal of view screen/curtain
•Removal of doors
•External trim pieces which do not affect the operation of the fi replace may be removed providing they can be stored on or within the fi replace for reassembly if the insert is removed.
•The permanent metal warning label provided must be attached to the back of the fi replace, with screws or nails, stating that the fi replace may have been altered to accommodate the insert, and must be returned to original condition for use as a conventional fi replace. Figure 11.1
•If the hearth extension is lower than the fi replace opening, the portion of the insert extending onto the hearth must be supported.
•Manufacturer designed adjustable support kit can be ordered from your dealer.
•Final approval of this installation type is contingent upon the authority having jurisdiction.
NOTE: Refer to chimney liner manufacturer for recom- mendations on supporting the liner. Installation into fi replaces without a permit will void the listing
WARNING! Risk of Fire!
Follow venting manufacturer’s clearances and instructions when installing venting system.
NOTICE: In Canada when using a
WARNING
THIS FIREPLACE MAY HAVE BEEN ALTERED TO ACCOMMODATE AN INSERT. IT MUST BE RETURNED TO ITS ORIGINAL CONDITION BEFORE USE AS A SOLID FUEL BURNING FIREPLACE.
Figure 11.1
November 22, 2011 | Page 11 |