Honeywell LYNXR Series, LYNXR-EN setup guide Recommendations for Smoke and Heat Detectors

Page 2

RECOMMENDATIONS FOR PROPER PROTECTION

The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises.

Recommendations for Smoke and Heat Detectors

With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.

Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: For minimum protection a smoke detector should be installed outside of each separate sleeping area, and on each additional floor of a multi-floor family living unit, including basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not normally recommended.

For additional protection the NFPA recommends that you install heat or smoke detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages.

In addition, we recommend the following:

Install a smoke detector inside every bedroom where a smoker sleeps.

Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the door is closed.

Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air conditioners or humidifiers) are used.

Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.

Install smoke detectors in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire or an intrusion.

THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE

SOUNDING OF FIRE NOTIFICATION APPLIANCES.

KITCHEN

 

 

KITCHEN

DINING

BEDROOM

 

BEDROOM

BEDROOM

DINING

TV ROOM

 

 

 

 

 

 

 

 

 

LIVING ROOM

BEDROOM

 

 

 

 

LIVING ROOM

BEDROOM

BEDROOM

 

 

 

 

 

 

 

 

 

 

Smoke Detectors for Minimum Protection

 

 

 

Smoke Detectors for Additional Protection

BEDROOM

 

 

Heat-Activated Detectors

 

 

BEDROOM BEDROOM

LIVING

KTCHN

GARAGE

ROOM

.

CLOSED

 

TO

 

 

DOOR

 

 

 

 

 

BEDROOM

 

BASEMENT

01000-002-V0

Recommendations For Proper Intrusion Protection

For proper intrusion coverage, sensors should be located at every possible point of entry to a home or premises. This would include any skylights that may be present, and the upper windows in a multi-level building.

In addition, we recommend that radio backup be used in a security system. This will ensure that alarm signals can be sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are normally sent over the phone lines, if connected to an alarm monitoring station).

–2–

Image 2
Contents Ademco Lynxr Series Security Systems Recommendations for Smoke and Heat Detectors Recommendations For Proper Intrusion ProtectionTable of Contents Hour backup System FeaturesHardwire zone Two-way voice communication Speaker phone operationMounting the Control Desktop MountingWiring Connections Wiring ConnectionsWiring Overview Full Line Seizure Connections This System 75 to 150 feet AC Power and Backup BatteryAC Power and Rechargeable Backup Battery 150 to 300 feetHours minimum Approximately 1-hour before battery depletion Hours minimum At least 1-hour before battery depletionHouse Identification Installing Wireless ZonesGeneral Information Transmitter SupervisionEnter Installer code 4112 + # + Transmitter Battery LifeUsing the Transmitter Sniffer Mode Go/No Go Test ModeSetting DIP Switches on the 5800RL and 5827 Transmitters Mechanics of Programming Loading Factory DefaultsExiting Program Mode General Programming InformationZone Not Used Type Entry/Exit Burglary #1 Zone Response Type DefinitionsType Type 02 Entry/Exit Burglary #25806/5807/5808 Defaults where applicable are Indicated in Text Data Field DescriptionsDialer Programming Fields 43Report Format for Primary/Secondary Follow Me Reminder Phone NumberPhone System Select Split/Dual ReportingSystem Status and Restore Report Codes Programming 59 76 Restore Report Codes System Status Report CodesRestore Report Codes Download Information 94 Device Programming Menu Mode Enabling the Wireless DialerEnhanced Zone Programming Mode Zone Lists for Menu ModeEnabling the 5842 Wireless Dialer Wireless Dialer SetupEnable back-up reporting Enable the wireless dialerEnable trouble reports Response to phone line tamperEnhanced Zone Programming Mode Report code Zone numberZone type Input typeConfirmation Enroll modeDelete zone parameters Descriptor Serial numberVoice descriptor Start by Event Device Programming Menu ModeProgramming Options Defined Start by Zone Type or System OperationStop Programming Powerline Carrier DevicesUpon Restore of a Zone List Upon a Zone Type or System OperationDevice number Powerline Carrier DeviceProgramming Device actionZone List Menu Mode Enter the 2-digit zone number Enhanced Sequential Mode00 = exit Sequential mode IA LC = copy the previous serial number entry from the bufferDelete serial number Assign Zone Voice Descriptors Assign zone voice descriptorsAssign Zone Voice Descriptor Voice Vocabulary IndexCustom descriptor number Record Custom Voice DescriptorsAssign custom voice descriptors Voice Prompt Programming Voice Prompt Programming Keypad FunctionsPatio Second Central Station Account NumberFront Basement Back Sliding ToenrollPendant Type To Enter Expert Programming Mode TemplateEquipment required to download to a system at the premises Remote Programming/Control DownloadingRemote Programming Information Remote Programming Advisory Notes Panic Keys System OperationSecurity Codes Message Center Volume ControlKeypad Functions Other FunctionsSpeaker Phone Operation LYNXR-EN Only Remote Phone Control FeatureRemote Phone Control Feature Activation Alarm Audio Verification Two-Way Voice FeatureOperator Commands Exit Error Alarm Displays Follow Me System Announcement FeaturePowerline Carrier Devices e.g. X-10 devices If programmedOther Displays Fault and Battery DisplaysTrouble Conditions Armed System Test Testing the SystemTest Mode System Communication Communication OverviewContact ID Event Codes Report +1/4+1 Standard +1/4+1 ExpandedTroubleshooting Guide S T E M i n c l u d i n g W i r e l e s sN T R O L O K E D E T E C T O RPLEASE, before you call Technical Support, be sure you Read the InstructionsRegulatory Agency Statements UL Notice This is a Grade a residential systemElectrical SpecificationsLYNXR-Series Security Controls CommunicationLYNXR/LYNXR24 Programming Default Tables LYNXR-EN Programming Default Tables Zone ASSIGNMENT/ALARM Report Codes for Table Event Start StopDevice Number System OperationIndex 20, 61Exit Delay Serial Number Page Limitations of this Alarm System Limited Warranty Police With System‡K5963V3oŠ

LYNXR Series, LYNXR-EN specifications

The Honeywell LYNXR Series, particularly the LYNXR-EN model, represents a pinnacle of advanced security technology designed for residential and small business applications. This all-in-one wireless security system is lauded for its innovative features, ease of use, and powerful performance, making it a top choice among users seeking enhanced security solutions.

One of the standout features of the LYNXR-EN is its user-friendly touchscreen interface. The large, intuitive display allows for straightforward navigation, enabling users to arm or disarm the system, check status, and receive alerts with just a few taps. This ease of use is complemented by programmable quick access keys, which allow users to personalize their experience according to their security requirements.

Additionally, the LYNXR-EN is designed with flexibility in mind. It supports a wide range of wireless sensors and devices, facilitating comprehensive coverage for homes or small businesses. Users can integrate door and window contacts, motion detectors, glass break sensors, and more, ensuring that every entry point is monitored. The system can accommodate up to 48 wireless zones, allowing for extensive security applications without the clutter of wires.

Technologically, the LYNXR-EN leverages advanced RF technology, enhancing the reliability of communication between the panel and sensors. This feature minimizes the risk of interference and ensures consistent performance even in challenging environments. Along with this robust connectivity, the system offers dual-path communication capabilities, enabling both IP and cellular reporting. This redundancy ensures that alerts are promptly sent to the monitoring center and mobile devices, providing peace of mind to users.

Moreover, the LYNXR-EN can be easily integrated with smart home technology. It is compatible with various smart devices, allowing users to control lighting, thermostats, and other home automation features from a single platform. This integration not only enhances convenience but also optimizes energy efficiency.

The LYNXR-EN also includes a built-in battery backup, ensuring that the system remains operational during power outages. This is a crucial feature for maintaining security when it is needed most. Additionally, users can set up customizable alerts and notifications, allowing them to stay informed of any unusual activity in real-time.

In summary, the Honeywell LYNXR Series, especially the LYNXR-EN model, combines advanced technology with user-friendly design to deliver a versatile and robust security solution. Its wireless capabilities, comprehensive sensor support, smart home integration, and reliable communication make it a prominent choice in the ever-evolving realm of security systems.