Honeywell LYNXR-EN, LYNXR Series setup guide Full Line Seizure Connections

Page 7

Wiring Connections

Wiring Connections

2.Make Phone Line Connections - For local or full line seizure proceed to the appropriate steps below.

Local Seizure

a.Connect the incoming phone line to either the 8-position jack or terminals 2 (TIP) and 3 (RING) on the Lynx.

b.Connect the handset phone lines to either the RJ11 jack or terminals 4 (TIP) and 5 (RING).

Full Line Seizure: The control must be placed in series with the incoming phone line. Plugging the Direct Connect Cord directly into the RJ31X jack, allows the control to seize the phone line when an alarm occurs and normal phone line usage by the premises phones if the plug needs to be removed.

a. Cut the incoming RING and TIP phone lines (typically red and green, respectively) and connect them to RJ31X terminals 4 (red) and 5 (green).

b.Connect the premises end of the cut RING and TIP wires to RJ31X terminals 1 (grey) and 8 (brown) respectively.

c.Wire the flying leads of a Direct Connect Cord to the control’s phone terminals as shown in the diagram or plug into the 8-position jack.

d. Plug the Direct Connect Cord into the RJ31X jack.

 

 

 

 

 

 

INCOMING

 

 

 

 

 

 

PHONE LINE

 

 

 

 

 

 

RING

 

 

 

 

 

 

TIP

 

RED

 

4

5

 

GREEN

 

 

 

3

 

6

TO

 

 

 

 

 

 

 

 

 

RJ31X

 

PREMISES PHONES

 

 

 

 

 

 

RING

 

 

 

2

 

7

TIP

 

GREY

 

1

 

8

BROWN

 

 

 

 

DIRECT

 

 

 

 

CONNECT

 

 

 

 

CORD

 

 

 

OR

 

 

 

GREEN

RED

BROWN

GREY

 

 

 

 

 

 

 

 

 

8-POSITION

TIP

RING

TIP

RING

 

 

JACK

} }

 

 

 

INCOMING

 

TO

 

 

 

PHONE LINE

PREMISES

 

 

 

 

 

PHONES

 

 

 

 

 

 

 

 

 

01000-008-V0

 

Full Line Seizure Connections

HARDWIRED ZONE: If the EOLR is not at the end of the loop, the zone will not be properly supervised, and the system may not respond to an open circuit on the zone.

3.Make Hardwired Zone Connections - Zone 1 is an EOLR supervised zone that supports both open circuit and closed circuit devices and has a response time of 350msec. Maximum zone resistance: 300 ohms, plus EOLR

Note: The hardwire zone cannot be used as a fire zone.

a.Connect sensors/contacts to the hardwired zone terminals 6 (+) and 7 (–). Refer to the Summary of Connections diagram.

b.Connect closed circuit devices in series in the high (+) side of the loop. The EOL resistor must be connected in series with the devices, following the last device.

c.Connect open circuit devices in parallel across the loop. The 2000-ohm EOLR must be connected across the loop at the last device.

4.Make External Sounder Connections - The control panel supports either a 6-14VDC piezo sounder (30mA max.) or 6-14VDC bell (120mA max.; e.g. ADEMCO WAVE2EX).

a.Connect a piezo sounder to terminals 10 (+) and 11 (–); OR a bell to terminals 11 (–) and 12 (+).

UL

LOCAL SOUNDER DISABLE: The Master Keypad’s built-in piezo sounder can be disabled by removing the shorting jumper (shunt) on the terminal board. If disabled, however, no sounding will occur upon AC loss, since the external sounder does not operate when AC power is lost.

Do not remove shorting jumper (the shunt) for UL installations.

5.Disable Local Sounder Option - If required the Master Keypad’s built-in piezo sounder can be disabled.

a.Remove the shorting jumper (shunt) on the terminal board.

6.Make Powerline Carrier Device Connections - The control panel supports up to 8 Powerline Carrier Devices. If using these devices, they must be connected to the ADEMCO 1332X10 transformer, as shown in the SUMMARY OF CONNECTIONS diagram.

a.Connect the com/data/sync/ lines from the ADEMCO 1332X10 transformer to terminals 9, 13, and 14, respectively.

Note: If not using the supplied Ademco connection cable, you may need to reverse the black and yellow wire connections. Refer to the 80 Device Programming Menu Mode section for details on programming Powerline Carrier Devices.

–7–

Image 7
Contents Ademco Lynxr Series Security Systems Recommendations For Proper Intrusion Protection Recommendations for Smoke and Heat DetectorsTable of Contents Two-way voice communication Speaker phone operation System FeaturesHardwire zone Hour backupDesktop Mounting Mounting the ControlWiring Overview Wiring ConnectionsWiring Connections Full Line Seizure Connections This System 150 to 300 feet AC Power and Backup BatteryAC Power and Rechargeable Backup Battery 75 to 150 feetHours minimum At least 1-hour before battery depletion Hours minimum Approximately 1-hour before battery depletionTransmitter Supervision Installing Wireless ZonesGeneral Information House IdentificationGo/No Go Test Mode Transmitter Battery LifeUsing the Transmitter Sniffer Mode Enter Installer code 4112 + # +Setting DIP Switches on the 5800RL and 5827 Transmitters General Programming Information Loading Factory DefaultsExiting Program Mode Mechanics of ProgrammingType 02 Entry/Exit Burglary #2 Zone Response Type DefinitionsType Zone Not Used Type Entry/Exit Burglary #15806/5807/5808 Data Field Descriptions Defaults where applicable are Indicated in TextFields 43 Dialer ProgrammingSplit/Dual Reporting Follow Me Reminder Phone NumberPhone System Select Report Format for Primary/SecondarySystem Status and Restore Report Codes Programming 59 76 System Status Report Codes Restore Report CodesRestore Report Codes Download Information 94 Zone Lists for Menu Mode Enabling the Wireless DialerEnhanced Zone Programming Mode Device Programming Menu ModeWireless Dialer Setup Enabling the 5842 Wireless DialerResponse to phone line tamper Enable the wireless dialerEnable trouble reports Enable back-up reportingEnhanced Zone Programming Mode Input type Zone numberZone type Report codeDelete zone parameters Enroll modeConfirmation Voice descriptor Serial numberDescriptor Start by Zone Type or System Operation Device Programming Menu ModeProgramming Options Defined Start by EventUpon a Zone Type or System Operation Programming Powerline Carrier DevicesUpon Restore of a Zone List StopDevice action Powerline Carrier DeviceProgramming Device numberZone List Menu Mode 00 = exit Sequential mode Enhanced Sequential ModeEnter the 2-digit zone number = copy the previous serial number entry from the buffer IA LCDelete serial number Assign zone voice descriptors Assign Zone Voice DescriptorsVoice Vocabulary Index Assign Zone Voice DescriptorAssign custom voice descriptors Record Custom Voice DescriptorsCustom descriptor number Voice Prompt Programming Keypad Functions Voice Prompt ProgrammingToenroll Second Central Station Account NumberFront Basement Back Sliding PatioPendant Type Template To Enter Expert Programming ModeRemote Programming Information Remote Programming/Control DownloadingEquipment required to download to a system at the premises Remote Programming Advisory Notes Security Codes System OperationPanic Keys Other Functions Volume ControlKeypad Functions Message CenterRemote Phone Control Feature Remote Phone Control FeatureSpeaker Phone Operation LYNXR-EN Only Operator Commands Alarm Audio Verification Two-Way Voice FeatureActivation If programmed Follow Me System Announcement FeaturePowerline Carrier Devices e.g. X-10 devices Exit Error Alarm DisplaysTrouble Conditions Fault and Battery DisplaysOther Displays Test Mode Testing the SystemArmed System Test Communication Overview System CommunicationReport +1/4+1 Standard +1/4+1 Expanded Contact ID Event CodesS T E M i n c l u d i n g W i r e l e s s Troubleshooting GuideO K E D E T E C T O R N T R O LRead the Instructions PLEASE, before you call Technical Support, be sure youUL Notice This is a Grade a residential system Regulatory Agency StatementsCommunication SpecificationsLYNXR-Series Security Controls ElectricalLYNXR/LYNXR24 Programming Default Tables LYNXR-EN Programming Default Tables Zone ASSIGNMENT/ALARM Report Codes for Table System Operation Start StopDevice Number Event20, 61 IndexExit Delay Serial Number Page Limitations of this Alarm System Limited Warranty System Police With‡K5963V3oŠ

LYNXR Series, LYNXR-EN specifications

The Honeywell LYNXR Series, particularly the LYNXR-EN model, represents a pinnacle of advanced security technology designed for residential and small business applications. This all-in-one wireless security system is lauded for its innovative features, ease of use, and powerful performance, making it a top choice among users seeking enhanced security solutions.

One of the standout features of the LYNXR-EN is its user-friendly touchscreen interface. The large, intuitive display allows for straightforward navigation, enabling users to arm or disarm the system, check status, and receive alerts with just a few taps. This ease of use is complemented by programmable quick access keys, which allow users to personalize their experience according to their security requirements.

Additionally, the LYNXR-EN is designed with flexibility in mind. It supports a wide range of wireless sensors and devices, facilitating comprehensive coverage for homes or small businesses. Users can integrate door and window contacts, motion detectors, glass break sensors, and more, ensuring that every entry point is monitored. The system can accommodate up to 48 wireless zones, allowing for extensive security applications without the clutter of wires.

Technologically, the LYNXR-EN leverages advanced RF technology, enhancing the reliability of communication between the panel and sensors. This feature minimizes the risk of interference and ensures consistent performance even in challenging environments. Along with this robust connectivity, the system offers dual-path communication capabilities, enabling both IP and cellular reporting. This redundancy ensures that alerts are promptly sent to the monitoring center and mobile devices, providing peace of mind to users.

Moreover, the LYNXR-EN can be easily integrated with smart home technology. It is compatible with various smart devices, allowing users to control lighting, thermostats, and other home automation features from a single platform. This integration not only enhances convenience but also optimizes energy efficiency.

The LYNXR-EN also includes a built-in battery backup, ensuring that the system remains operational during power outages. This is a crucial feature for maintaining security when it is needed most. Additionally, users can set up customizable alerts and notifications, allowing them to stay informed of any unusual activity in real-time.

In summary, the Honeywell LYNXR Series, especially the LYNXR-EN model, combines advanced technology with user-friendly design to deliver a versatile and robust security solution. Its wireless capabilities, comprehensive sensor support, smart home integration, and reliable communication make it a prominent choice in the ever-evolving realm of security systems.