New Buck Corporation 74 installation instructions

Page 30
Manual background

2.After locating the center of the hole install the ceiling support box, chimney flashing and rain cap. Only use2100° UL 103 HT chimney and parts listed in this manual per the chimney manufactures instruction .

3.Add additional pipe until both of the following are met:

(a)Chimney pipe is 3 feet higher than roof at the point where it penetrates the roof.

(b)Chimney pipe height is at least 2 feet higher than any part of the roof within 10 feet of the chimney. (See Figure 12A. Page 27.)

4.Using only double wall chimney connector listed in this manual (See Page 17), connect the heater to the chimney by following chimney manufacturer's installation instructions exactly. (See Figure 13.)

CEILING

ROOF

COLLAR

3 SHEET METAL SCREWS

3 SHEET METAL SCREWS OR RIVETS

Figure 13

28

Image 30
Contents BUCKSTOVE Page TABLE OF CONTENTS BEFORE INSTALLING YOUR NEW BUCK STOVE INSTALLATION, OPERATION, ANDMAINTENANCE INSTRUCTIONS MODEL IMPORTANT INSTRUCTIONSSECTION INTRODUCTIONMODEL MASONRY INSERT INSTALLATIONMINIMUM CLEARANCE MASONRY INSERT SECTIONMASONRY INSERT INSTALLATION POSSIBLE TOOLS NEEDED FOR INSTALLATIONINSTALLATION PREPARATION INSTALLATION OPTIONSOPTION A AIRTIGHT INSU LATED CLEAN OUT REMOVE DAMPEROR WIRE IT OPEN OPTION BPOSITIONING INSTALLATION PROCEDUREPOSITIONING THE HEATER MOUNTING THE TRIM PANELSFINAL CHECK Page SECTION PRE-FABINSERT INSTALLATION SECTION RESIDENTIAL FREESTANDING INSTALLATION PREPARING THE STOVE FOR INSTALLATIONheater to the remainder of the home Chimney Floor ProtectionDETERMINING THE CHIMNEY LOCATION B. Wall Exit Into Metal Tee-Box Page D. Ceiling Exit-CloseClearance Alcove Installation Clearances COLLARFINAL CHECK CLEARANCES FOR MODEL MINIMUM CLEARANCES TO COMBUSTIBLES RESIDENTIAL / MOBILE HOMECLEARANCES FOR MODEL CLEARANCES FOR MODEL CONNECTOR WITHOUT CLOSE CLEARANCE SHIELDSDOUBLE WALL OR SHIELDED SINGLE WALL MINIMUM CLEARANCES TO COMBUSTIBLESInstallation of Close Clearance Shields Optional WITH CLOSE CLEARANCE SHIELDS CLEARANCES FOR MODEL ALCOVE INSTALLATION DOUBLEOR SHIELDED SINGLE WALL CONNECTOR B H CSECTION FREESTANDING MOBILE HOME INSTALLATION FLOOR PROTECTIONTOOLS FOR INSTALLATION PREPARING THE HEATER FOR INSTALLATIONCHIMNEY PREPARING THE LOCATION FOR ROOM HEATER Ceiling Exit Using Close Clearance listed chimney Page FINAL CHECK 1.Recheck the specified clearancesSECTION WOOD HEATER SAFETY SECTION OPERATION BUILDING A FIRESOLUTION SECTION TROUBLESHOOTINGPROBLEM POSSIBLE CAUSEPROBLEM SOLUTIONPOSSIBLE CAUSE NEW BUCK CORPORATION NBC WARRANTY TIME PERIODSPROCEDURE PRODUCTS COVEREDCONDITIONS AND EXCLUSIONS OTHER RIGHTS