Heat & Glo LifeStyle LUX60 owner manual Electrical Information, Wiring Requirements

Page 45

13 Electrical Information

A. Wiring Requirements

NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code ANSI/NFPA 70-latest edition or the Canadian Electric

Code CSA C22.1.

Wire the appliance junction box to 110-120 VAC. This is required for use of optional accessories.

A 110-120 VAC circuit for this product must be protected with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.

Low voltage and 110 VAC voltage cannot be shared within the same wall box.

WARNING! Risk of Shock or Explosion! DO NOT wire

110V to the valve or to the appliance wall switch. Incorrect wiring will damage controls.

B. Electrical Service and Repair

WARNING! Risk of Shock! Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

WARNING! Risk of Shock! Replace damaged wire with type 105° C rated wire. Wire must have high temperature insulation.

 

 

 

ORANGE

 

 

 

 

WHITE

 

 

 

 

 

 

 

 

F

 

 

BLACK

 

 

 

M

 

 

 

 

 

F

 

 

 

 

 

M

 

 

 

 

 

 

 

 

 

 

 

 

POWER

 

 

 

 

 

 

SUPPLY

 

 

 

GREEN

 

BROWN

 

ORANGE

 

ORANGE

 

 

 

 

 

 

 

 

 

 

GROUND

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

IPI

 

 

 

 

 

 

VALVE

 

 

 

 

 

 

 

 

1

 

 

 

 

 

GREEN

2

 

 

 

 

 

IPI

3

 

BROWN

 

 

 

4

 

LUX

 

 

MODULE

5

 

BROWN

 

 

 

6

 

RED

CONTROL

 

 

 

7

 

MODULE

 

 

 

8

 

 

 

 

 

3V DC

BLACK

 

 

FLAME

 

 

 

 

SOLENOID

 

 

 

 

 

 

 

 

 

 

 

LEARN

BLACKWires

 

 

 

 

 

BUTTON

 

 

 

 

 

4BLACKWires

 

 

 

 

 

 

4

 

 

 

 

 

4 BLACK Wires

 

Figure 13.1 Wiring Diagram

 

 

 

 

 

 

 

 

Heat & Glo • LUX60 • 4062-116 • Rev. G • 4/11

45

Image 45
Contents Models Installation and OperationHomeowner Reference Information CongratulationsTable of Contents Reference Materials Limited Lifetime Warranty  B. Limited Lifetime WarrantyWarranty Conditions Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Gas Fireplace Safety Operating InstructionsYour Fireplace Clear Space Fixed Glass AssemblyDecorative Doors and Fronts Operation of the LUX60Before Lighting Fireplace Matching Security CodesSystem Operation IntelliFire Ignition System IPI Lighting Instructions For Your Safety Read Before LightingFrequently Asked Questions Initial Break-in ProcedureAfter Fireplace is Lit Maintenance and Service Maintenance Tasks-HomeownerGlass Cleaning Remote Control Doors, Surrounds, FrontsVenting Gasket Seal and Glass Assembly Inspection Maintenance Tasks-Qualified Service TechnicianFirebox Control Compartment and Firebox TopLED Light Bar Replacement Light Glass Replacement/CleaningBack Clean Porcelain PanelsRemove Screws Typical Appliance System Getting StartedDesign and Installation Considerations Tools and Supplies NeededInspect Appliance and Components Framing and Clearances Select Appliance LocationAssemble Steel Stud Kit Clearances Construct the Appliance ChaseClearances to Combustibles Vent Termination Minimum Clearances Termination LocationsMinimum Clearances for Termination Approved Pipe Vent Information and DiagramsVent Table Key Use of ElbowsVent Diagrams Top Vent Horizontal TerminationOne Elbow Three Elbows Two 45 Elbows replacing One 90 ElbowTop Vent Vertical Termination No ElbowTwo Elbows Pipe Clearances to Combustibles Vent Clearances and FramingWall Penetration Framing Combustible Wall PenetrationCeiling firestop Must be used between floors and at- tics Install the Ceiling FirestopInstall Attic Insulation Shield Flat Ceiling InstallationVaulted Ceiling Installation Secure and Level the Appliance Appliance PreparationAttach Pipe to the Firebox Assembly Install Vent PipeAssemble Vent Sections Assemble Pipe SectionsSecure the Vent Sections Assemble Slip SectionsDisassemble Vent Sections Install Metal Roof Flashing13 Assembling the Storm Collar Assemble and Install Storm CollarHeat Shield Requirements for Horizontal Termination Install Vertical Termination Cap16 Venting through the wall Install Horizontal Termination CapHHT Shrouds ShroudsField Constructed Shrouds Open Top Shroud may be used with DVP-TV, DVP-TVHWRoofed Style Shroud may be used with DVP-TV, DVP-TVHW Mailbox Style Shroud may be used with DVP-TV, DVP-TVHWGas Information Gas PressureGas Connection Setting Flame Height/Manifold Pressure Install Flame SolenoidWiring Requirements Electrical Service and RepairElectrical Information Junction Box Detail Junction Box InstallationStandard 1/2 in mm Sheetrock Wall FinishingAdditional Decorative Finishing over 1 in mm Thick Additional Decorative Finishing up to 1 in mm ThickRemove Glass Assembly Appliance SetupAir Shutter Access & Adjustment Clean the ApplianceCenter Burner Tube Air Shutter Outside Burner Tube Air Shutter AdjustmentInstall Glass Rock Install Glass RockIntelliFire IPI Ignition System TroubleshootingIntelliFire IPI Ignition System Reference Materials Appliance Dimension DiagramDVP45 Vent Components DiagramsDVP-TRAPFL DVP-TVHW DVP-TRAP Optional Components Do not Discard this Manual Contact Information