INSTALLATION
RIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS
REGENCY DIRECT VENT SYSTEM (FLEX) - Propane & Natural Gas
The diagram below shows examples of horizontal termination arrangements using two 90o elbows.
Note: | 1) | A maximum of two 90o elbows are permitted (two 45o elbows equal one 90o elbow). |
| 2) | A minimum of 6 ft.(1.8m) vertical from base of unit is required if two 90o elbows are used. |
| 3) | Minimum distance between elbows is 2 ft. (0.6m). |
If length "B" is increased, length "A" must be decreased by a corresponding amount.
For All Horizontal Terminations
All Rigid Pipe Systems 4" inner diameter
Regency Flex Vent 4" inner diameter
A vent guard may be required, check local codes.
•Maintain a
combustibles for rigid pipe systems and
• Horizontalventmustbesupportedevery 3 feet
•Firestops are required at each floor
level and whenever passing through a wall.
Note: Regency Direct Vent System (Flex) is only approved for horizontal termina- tions.
14 | Regency |