Regency P42-LP3, P42-NG3 installation manual Exterior Vent Termination

Page 9

Regency P42-3 Zero Clearance Direct Vent Gas Fireplace

Vertical

Termination

24"

D

E

V

B

V

M

.

Inside corner detail

G

V

A

C

 

V

Fixed

 

 

Closed

F

V

Openable

 

 

B

B

V

B

Vertical

Termination

24"

18"

V

 

 

 

 

 

 

 

 

H

 

 

B

V

 

 

 

 

 

Openable

Fixed Closed

 

 

 

 

 

B

N

 

 

 

 

V

K

A

 

 

 

 

 

j

 

 

 

 

 

A

 

 

 

V

L

A

EXTERIOR VENT TERMINATION

V

Vent terminal

A

Air supply outlet

 

Area where terminal is not permited

 

 

 

 

 

 

 

A= Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm)

H= Not to be installed above a meter/regulator assembly within (3'/90cm) horizontally from

B= Clearance to window or door that may be opened *(12"/30cm)

 

the centerline of the regulator.

C= Clearance to permanently closed window *(min. 12"/30cm)

J=

Clearance to service regulator vent outlet *(min 36"/90cm)

D= Vertical clearance to ventilated soffit located above the terminal within a horizontal

K= Clearance to non-mechanical air supply inlet to building or the combustion air inlet to

 

distance of (24"/60cm) from the centerline of the terminal (min. 18"/46cm) check with

 

any other appliance *(12"/30cm)

 

local code.

L=

Clearance to a mechanical air supply inlet *(min. 72"/1.8m)

E=

Clearance to unventilated soffit (min. 15"/38cm)

M= Clearance above paved sidewalk or a paved driveway located on public property

F=

Clearance to outside corner: with AstroCap Termination Cap (min 6"/15cm), with Dura-

 

*(min. 84"/2.1m)

 

Vent Termination Cap (13"/33cm)

N= Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)

G= Clearance to inside corner: with AstroCap Termination Cap (min 6"/15cm), with Dura-

Vent Termination Cap (12"/30cm)

Note:

-A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.

-Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

-If the vent termination is accessible, a certified guard shall be installed.

* As specified in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances.

9

REQUIREMENTS

INSTALLATION

Image 9
Contents P42 Gas Fireplace To the New Owner Information for MOBILE/MANUFACTURED Homes After First SaleTable of Contents Copy of Safety Decal for P42 Safety LabelGeneral Safety Information InstallationInstallation Checklist Save These InstructionsManufactured Mobile Home Additional Requirements Unit Specifications Locating Your GAS StoveOptional Duct System Optional Heat ReleaseMantel LEG Clearances Clearances MantelsFraming Finishing TOP Assembly Nailing StripsVenting Introduction Vent RestrictorExterior Vent Termination Regency Direct Vent System Flex Horizontal Terminations Only Venting4DT-AJB Rigid Pipe Venting Components ListAlternate Rigid Pipe VentingHorizontal TerminationVent guard may be required, check local codes Rigid Pipe Venting Arrangements Horizontal TerminationsFor All Horizontal Terminations Propane & Natural Gas Rigid Pipe Venting Arrangements Vertical TerminationsVent restrictor #6 must be used Required Parts Vertical Termination With CO-LINEAR Flex SystemDescription Alternate Approved CapsInstallation Horizontal Installations Below Grade InstallationSnorkel Terminations Continue to assemble pipe lengths Vertical TerminationInstallation Procedures Offset ChartFor Regency Direct Vent System Flex GAS Line Installation GAS Pipe Pressure TestingHigh Elevation Aeration Brick Panels Adjustment Natural GAS LOG SET InstallationPropane Burner tray without front logs in placeFlush Louvers Standard Flush DoorDouble Screen Door Not under the gas lineOptional BAY Door BAY LouversOptional Bay Trim Full Screen Front Full Screen Door Frame InstallationHinge Location Bottom Grill Hinge Screen Door Wiring Diagram To Thermocouple T ValveDo not cut the ground terminal off under any circumstances Optional Wall Switch Remote ControlLighting Procedure Operating InstructionsTemperatures keep children, clothing Clean. See installationCopy of the Lighting Plate Instructions Maintenance MaintenanceShutdown Procedure First FireLOG Replacement Glass ReplacementGOLD-PLATED Louvers Thermopile ThermocoupleRemoving the FAN Replacing the FAN Shut the power offInstalling Valve P42 Main Assembly Parts ListP42 Burner & LOG Assembly P42 Flush Door & Louvers P42 BAY Front & Louvers Regency P42-3 Zero Clearance Direct Vent Gas Fireplace Regency P42-3 Zero Clearance Direct Vent Gas Fireplace Conditions WarrantyInstaller Please complete the following information