Regency P42-LP3 Rigid Pipe Venting Arrangements Vertical Terminations, Propane & Natural Gas

Page 15

INSTALLATION

RIGID PIPE VENTING ARRANGEMENTS - VERTICAL TERMINATIONS

(Propane & Natural Gas)

The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations with rigid pipe vent systems for Propane and Natural Gas.

Maximum two 45o elbows allowed.

Vent restrictor #6 must be used in shaded area in diagram below.

Vent must be supported at offsets

The P42 is approved for a 37 ft. (11.3m) straight ver- tical, including a 20" (0.5m) horizontal offset using two 90o elbow (two 45o elbows equal one 90o el- bow) with rigid pipe vent systems for Propane and Natural Gas, as per the diagram to the right.

Vent restrictor #6 is required for ter- minations in shad- ed area.

Vent must be sup- ported at offsets

Diagram 1

Note: Must use optional rigid pipe adap- tor when using rigid pipe vent systems (Part # 510-994).

Note: Regency Direct Vent System (Flex) is only approved for horizontal ter- minations.

Diagram 2

Regency P42-3 Zero Clearance Direct Vent Gas Fireplace

15

Image 15
Contents P42 Gas Fireplace To the New Owner Information for MOBILE/MANUFACTURED Homes After First SaleTable of Contents Copy of Safety Decal for P42 Safety LabelSave These Instructions InstallationGeneral Safety Information Installation ChecklistOptional Heat Release Unit Specifications Locating Your GAS StoveManufactured Mobile Home Additional Requirements Optional Duct SystemMantel LEG Clearances Clearances MantelsVent Restrictor TOP Assembly Nailing StripsFraming Finishing Venting IntroductionExterior Vent Termination Regency Direct Vent System Flex Horizontal Terminations Only Venting4DT-AJB Rigid Pipe Venting Components ListTermination Rigid Pipe VentingAlternate HorizontalVent guard may be required, check local codes Rigid Pipe Venting Arrangements Horizontal TerminationsFor All Horizontal Terminations Propane & Natural Gas Rigid Pipe Venting Arrangements Vertical TerminationsVent restrictor #6 must be used Alternate Approved Caps Vertical Termination With CO-LINEAR Flex SystemRequired Parts DescriptionInstallation Horizontal Installations Below Grade InstallationSnorkel Terminations Continue to assemble pipe lengths Vertical TerminationInstallation Procedures Offset ChartFor Regency Direct Vent System Flex GAS Line Installation GAS Pipe Pressure TestingHigh Elevation Aeration Brick Panels Adjustment Burner tray without front logs in place LOG SET InstallationNatural GAS PropaneNot under the gas line Standard Flush DoorFlush Louvers Double Screen DoorOptional BAY Door BAY LouversOptional Bay Trim Full Screen Front Full Screen Door Frame InstallationHinge Location Bottom Grill Hinge Screen Door Wiring Diagram To Thermocouple T ValveDo not cut the ground terminal off under any circumstances Operating Instructions Remote ControlOptional Wall Switch Lighting ProcedureTemperatures keep children, clothing Clean. See installationCopy of the Lighting Plate Instructions First Fire MaintenanceMaintenance Shutdown ProcedureThermopile Thermocouple Glass ReplacementLOG Replacement GOLD-PLATED LouversRemoving the FAN Replacing the FAN Shut the power offInstalling Valve P42 Main Assembly Parts ListP42 Burner & LOG Assembly P42 Flush Door & Louvers P42 BAY Front & Louvers Regency P42-3 Zero Clearance Direct Vent Gas Fireplace Regency P42-3 Zero Clearance Direct Vent Gas Fireplace Conditions WarrantyInstaller Please complete the following information