INSTALLATION
The P42 is approved for a 23 ft. (7.0m) vertical, with a maximum 12 ft (3.7m) horizontal offset using two 90o elbows (two 45o elbows equal one 90o elbow) with rigid pipe vent systems for Propane and Natural Gas, as per the diagram below.
•No Vent restrictor is required.
•Vent must be supported at offsets
Diagram 3
Note: Regency Direct Vent System (Flex) is only approved for horizontal terminations.
The P42 is approved for a 37 ft. (11.3m) straight vertical, with rigid pipe vent systems for Propane and Natural Gas, as per the diagram below.
•Vent restrictor #6 must be used
Diagram 4
16 | Regency |