Regency L676-LP1, L676-NG1 Installation, Exterior Vent Termination Requirements, Canada1, USA2

Page 14
EXTERIOR VENT TERMINATION REQUIREMENTS

INSTALLATION

EXTERIOR VENT TERMINATION REQUIREMENTS

INSTALLATION

 

 

Minimum Clearance Requirements

Canada1
USA2

 

 

 

 

 

 

A

Clearance above grade, veranda, porch, deck, or balcony

12"(30cm)

12"(30cm)

 

 

 

 

 

 

B

Clearance to window or door that may be opened

12"(30cm)

9" (23cm)

 

 

 

 

 

 

C

Clearance to permanently closed window

*

*

 

 

 

 

 

 

D

Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61cm)

24"(60cm)

24"(60cm))

 

 

 

 

 

 

E

Clearance to unventilated soffit

24"(60cm)

24"(60cm)

 

 

 

 

 

 

F

Clearance to outside corner: with AstroCap Termination Cap.

13"(33cm)

13"(33cm)

 

 

 

 

 

 

 

Clearance to outside corner: with all other approved Termination Caps.

13"(33cm)

13"(33cm)

 

 

 

 

 

 

G

Clearance to inside corner: with AstroCap Termination Cap

13"(33cm)

13"(33cm)

 

 

 

 

 

 

 

Clearance to inside corner: with all other approved Termination Caps.

13"(33cm)

13"(33cm)

 

 

 

 

 

 

H

Clearance to each side of center line extended above meter/regulator assembly

36"(90cm)a

*

 

 

 

 

 

 

J

Clearance to service regulator vent outlet

36"(90cm)

*

 

 

 

 

 

 

K

Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance

12"(30cm)

9" (23cm)

 

 

 

 

 

 

L

Clearance to a mechanical air supply inlet

72"(1.8m)

36"(90cm)b

 

 

 

 

 

 

M

Clearance above paved sidewalk or a paved driveway located on public property

84"(2.1m)

*

 

N

Clearance under veranda, porch, deck, or balcony

12"(30cm)

*

1

In accordance with current CSA B149.1, Natural Gas and Propane Installation Code

 

 

2

In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code

 

 

A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings

‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor * Clearance in accordance with local installation codes and the requirements of the gas supplier

a 3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly b 3 feet (91cm) above - if within 10 feet (3m) horizontally

14

Regency® L676-1 Direct Vent Gas Fireplace

Image 14
Contents LIBERTY L676-1Gas Fireplace Congratulations MANUFACTURED MOBILE HOME REQUIREMENTSINSTALLATION TABLE OF CONTENTSSAFETY LABEL WARRANTYSAFETY LABEL INSTALLATIONMA Code - CO Detector REQUIREMENTSINSTALLATION 5.08: Modifications to NFPA-54,ChapterRegency L676-1Direct Vent Gas Fireplace UNIT DIMENSIONSINSTALLATION INSTALLATION CHECKLIST INSTALLATIONGENERAL SAFETY INFORMATION INSTALLATIONDiagram INSTALLATIONINSTALLATION HEAT RELEASE KITClearance to Combustibles from INSTALLATIONCLEARANCES Minimum Clearance from Top of Front FacingMANTEL CLEARANCES INSTALLATIONINSTALLATION MANTEL LEG CLEARANCESDiagram Diagram INSTALLATIONINSTALLATION DiagramINSTALLATION INSTALLATIONUNIT ASSEMBLY PRIOR TO INSTALLATION FINISHING TEMPLATEVENT RESTRICTOR POSITION INSTALLATIONINSTALLATION Vent Restrictor PlateEXTERIOR VENT TERMINATION REQUIREMENTS INSTALLATIONINSTALLATION Minimum Clearance RequirementsVENTING ARRANGEMENTS INSTALLATIONINSTALLATION FPI Kit #When using Rigid Vent other than INSTALLATIONINSTALLATION RIGID PIPE VENTING SYSTEMSINSTALLATION INSTALLATION5” X 8” RIGID PIPE CROSS REFERENCE CHART Regency L676-1Direct Vent Gas Fireplace INSTALLATIONINSTALLATION VENT RESTRICTOR SETTING INSTALLATIONINSTALLATION VENTING ARRANGEMENTSHorizontal Venting with Two 2 90o Elbows INSTALLATIONINSTALLATION Horizontal Venting with Three 3 90o ElbowsVENT RESTRICTOR SETTING INSTALLATIONINSTALLATION Vertical Venting with Three 3 90o ElbowsVENTING ARRANGEMENTS INSTALLATIONINSTALLATION ALLOWABLE VERTICAL TERMINATIONSINSTALLATION INSTALLATIONUNIT INSTALLATION WITH HORIZONTAL TERMINATION DiagramINSTALLATION INSTALLATIONUNIT INSTALLATION WITH VERTICAL TERMINATION DiagramINSTALLATION INSTALLATIONUNIT INSTALLATION ASTROCAP XL DIMENSIONS 946-623/PGAS LINE INSTALLATION INSTALLATIONPILOT ADJUSTMENT TESTINGWIRING DIAGRAM INSTALLATIONAERATION ADJUSTMENT INSTALLATIONCONVERSION KIT #522-969FROM NG TO LP INSTALLATIONINSTALLATION LP Conversion Kit ContainsNOTE Once the unit has been installed INSTALLATIONINSTALLATION Burner TubeINSTALLATION INSTALLATIONBRICK PANEL INSTALLATION Diagram Right Side Rod with Screen RemovedBurner Orifi ce Cover Plate Diagram INSTALLATIONINSTALLATION DiagramINSTALLATION INSTALLATIONLOG SET INSTALLATION Log kit # 522-930contains the following pieces5 Fit log A into the pins on the log tray INSTALLATIONINSTALLATION 7 Fit log E into the pin at the center of log AF BA C INSTALLATIONINSTALLATION 1st Grate PostCompleted Log Set Installation INSTALLATIONINSTALLATION E F A B CINSTALLATION INSTALLATIONMESH PULL SCREEN INSTALLATION Left Side Rod Right Side RodFinal Installation L900-1 OPTIONAL ANDIRON INSTALLATIONINSTALLATION Log GLIGHTING PROCEDURE OPERATING INSTRUCTIONSMATCHING REMOTE CONTROL & RECEIVER CODE SHUTDOWN PROCEDURECOPY OF LIGHTING PLATE INSTRUCTIONS OPERATING INSTRUCTIONSNORMAL OPERATING SOUNDS OF GAS APPLIANCES DO NOT REMOVE THIS INSTRUCTION PLATELOG REPLACEMENT MAINTENANCEMAINTENANCE INSTRUCTIONS GENERAL VENT MAINTENANCEDC SPARK BOX REPLACEMENT MAINTENANCEDC SPARK BOX BATTERY REPLACEMENT MAINTENANCEMAINTENANCE MAINTENANCEVALVE TRAY REPLACEMENT Latch Location LatchDC Spark Box MAINTENANCEMAINTENANCE DC Spark BoxPARTS LIST PARTS LISTMAIN ASSEMBLY Part #PARTS LIST PARTS LISTPARTS LIST PARTS LISTBURNER & LOG ASSEMBLY Part #Conditions WARRANTYThe Warranty: Limited Lifetime ExclusionsSee the inside back cover for details