3 Sidewall direct venting
Vent/air termination – sidewall
Figure 3-1A PVC/CPVC/Centrotherm Sidewall Termination of Air and Vent
WARNING
WARNING
Follow instructions below when determining vent location to avoid possibility of severe personal injury, death, or substantial property damage.
A gas vent extending through an exterior wall shall not terminate adjacent to a wall or below building extensions such as eaves, parapets, balconies, or decks. Failure to comply could result in severe personal injury, death, or substantial property damage.
Note: Available in 6" | TO BOILER |
INTAKE AIR | |
diameter only. | CONNECTION |
FROM BOILER |
|
VENT PIPE |
|
CONNECTION |
|
POSSIBLE ORIENTATIONS | 12" |
MIN | |
| TO |
| OVER- |
| HANG |
| VENT / AIR |
| TERMINATION |
| 12" |
| MIN |
Determine location
Locate the vent/air terminations using the following guidelines:
1.The total length of piping for vent or air must not exceed the limits given in the General Venting Section on page 16 of this manual.
|
| GRADE OR |
|
| SNOW LINE |
Table 3A CPVC/PVC Sidewall Vent Kits | ||
Model | Kit Number | Vent Size |
1.0 - 1.5 | KIT30047 | 6 inch vent |
2.You must consider the surroundings when terminating
the vent and air:
a.Position the vent termination where vapors will 3. The air piping must terminate in a
| not damage nearby shrubs, plants or air |
| as shown in FIG. | |||||
| conditioning equipment or be objectionable. |
| recirculation of flue products into the combustion air | |||||
b. | The flue products will form a noticeable plume as |
| stream. |
| ||||
| they condense in cold air. | Avoid areas where the | 4. The vent piping must | terminate in an elbow pointed | ||||
| plume could obstruct window views. |
|
| outward or away from the air inlet, as shown in FIG. | ||||
c. | Prevailing winds could cause freezing of |
| ||||||
|
| Do not exceed the maximum lengths of the | ||||||
| condensate and water/ice buildup where flue |
| WARNING | |||||
| products impinge on building surfaces or plants. |
|
| outside vent piping shown in FIG.’s | ||||
|
|
| ||||||
d. | Avoid possibility of accidental contact of flue |
|
| and | Excessive length exposed to the | |||
| products with people or pets. |
|
|
| outside could cause freezing of condensate | |||
e. | Do not locate the terminations where wind eddies |
|
| in the vent pipe, resulting in potential boiler | ||||
| could affect performance or cause recirculation, |
|
| shutdown. |
| |||
| such as | inside building | corners, near | adjacent |
|
|
|
|
| Figure | |||||||
| buildings | or surfaces, window wells, | stairwells, | |||||
| Vent w/Field Supplied Fittings | |||||||
| alcoves, courtyards, or other recessed areas. | |||||||
|
|
|
|
|
WARNING
Sidewall vent and air inlet terminations must terminate in the same pressure zone.
f.Do not terminate above any door or window. Condensate can freeze, causing ice formations.
g.Locate or guard vent to prevent condensate damage to exterior finishes.
22