Installation & Operation Manual
5 Hydronic piping
Hot Water Generator pump sizing
The SYNC has two (2) heat exchangers that require two (2) individual pumps for proper installation in the boiler loop and an additional two (2) pumps for the Hot Water Generator loop.
Hot Water Pump Head Loss = Ft. of Head for Heat Exchanger 1 (at required flow) + Ft. of Head for the Hot Water Generator (at 2 X the flow of Heat Exchanger 1)
Example:
Boiler: SB1500
A ΔT of 30° requires a flow through each heat exchanger of 51 GPM. The heat exchanger head loss is 18 ft. of head (see Table 5A).
Coupled with a Lochinvar Hot Water Generator with a
Hot Water Pump Head Loss = 18 Ft/Hd (51 GPM) + 1.2 Ft/Hd (102 GPM) = 19.2 Ft/Hd
A pump will need to be selected to flow 51 GPM with a head loss of 19.2 Ft/Hd.
Figure 5-2 Boiler Schematic
TO SYSTEM | FROM SYSTEM | |
HEAT EXCHANGER 2 | HEAT EXCHANGER 1 | |
BOILER PUMP | ||
BOILER PUMP | ||
| ||
HOT WATER | AIR COVER | |
| ||
GENERATOR |
| |
HEAT EXCHANGER 1 |
| |
HOT WATER PUMP |
| |
| 51 GPM | |
102 GPM | 102 GPM | |
HEAT EXCHANGER 2 | 51 GPM | |
| ||
HOT WATER PUMP |
|
Figure 5-3 Pump Configuration
FROM SYSTEM
FROM SYSTEM
TO BOILER
INLETS
TO BOILER
INLETS