Annual Maintenance Checklist

WARNINGS

THE BOILER CONTAINS REFRACTORY CERAMIC FIBER, a possible human carcinogen Use a NIOSH approved respirator when servicing high-temperature insulation and gasket materials. Wash exposed skin gently with soap and water after contact Wash exposed clothing separate from normal laundry.

LABEL ALL WIRES prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation

FAILURE TO MAINTAIN THE BOILER in proper working condition may lead to fire, explosion,

personal injury or death, and extensive property damage.

TURN OFF ALL GAS AND ELECTRIC power supplies to the boiler before servicing. Contact with or release of dangerous flammable gas, electrical voltage, moving parts, and very hot water under pressure may cause serious personal injury, property damage, or death.

LOCK ELECTRICAL BOXES AND GAS VALVES CLOSED to prevent someone from inadvertently restoring power or gas before the heating system is safe to operate.

Equipment you will need:

qSoft bristle brush

qBristle flue brush

qVacuum with brush attachment Perform these tasks each year:

1.Clean low water cutoff probe (if applicable).

2.Inspect vent for obstruction and signs of condensation, distortion, overheating or gas leakage.

3.Clean vent terminal and air intake screens.

4.Inspect boiler flue passages:

(1)Remove vent pipe, damper.

(2)Remove top panel and hood.

(7)Hold burner at throat. Lift front of burner to clear orifice (Figure AM-1). The burner that holds the pilot can only be removed by first lifting the burner adjacent to its right.

6.Perform Startup Checks and Adjustments described earlier in this manual.

7.Check operation of airflow sensing switches.

8.Check for water leaks on the boiler or water pooling around boiler.

9.Manually operate the relief valve. If the water is grey or black, there is excessive oxygen in the system. Oxygen is corrosive to boilers. Eliminate any source of oxygen.

(3)

Remove blocked vent switch and

10. Verify proper operation after servicing.

 

canopy.

 

(4)

Examine all flue passageways. Using

 

 

bristle flue brush and vacuum,

 

 

remove any soot or obstructions.

 

5. Remove and clean main burners:

 

(1)

Remove jacket front panel.

 

(2)

Disconnect pilot tubing at gas valve.

 

(3)

Disconnect pilot lead wires at gas valve.

 

(4)

Remove wires from flame roll-out switch.

 

(5)

Remove burner access panel.

 

(6)

Mark location of the pilot main burner on

 

 

the manifold if the marking on manifold

 

 

is missing or obliterated.

 

 

 

AM-1

 

 

17

Image 17
Contents ES2 Page Whats in the crate? ES2 Series SpecificationsSpecifications Appendices InstallationBoiler Quick-Start Position the Boiler Unpack the CrateConnect Venting Provide Combustion AirConnect Venting ES2 Vent Connector Horizontal Length Restrictions ftConnect Boiler Water Piping Connect Gas PipingDescription Burnham Part Number Connect Boiler Water Piping Connect Electrical WiringViewing the Operating Mode Options Using IQ Boiler Control DisplayOperating Mode Options Status Code Displayed in STA ModeMore Information about Adjustable Parameters Changing the Adjustable ParametersUsing the IQ Option Panel Adjustment Mode OptionsCheck for Gas and Water Leaks Using the Optional LCD Display KitBoiler restarts Perform Startup Checks and AdjustmentsAnnual Maintenance Checklist IQ Boiler Control Status Codes when Err is not displayed TroubleshootingIQ Boiler Control Error Codes when Err is flashing TroubleshootingDisplay Status Boiler / Control Actions IQ Option Panel Display Shows ERRRepair Parts List Repair Parts List Burner Orifices LP Gas 1.20mm IQ Boiler Control Jacket Vestibule Panel Supply Water Manifold Figure IW-1 Wiring Diagram Internal WiringFigure IW-2 Wiring Schematic Internal WiringFigure IW-3 Single Zone System with Domestic Hot Water Tank Figure IW-5 Multiple Zone System with Zone Valves Figure IW-7 Multiple Zone System with Zone Valve Panel Combined appliance Input BTU/hr Appendix a Combustion AirAppendix B Venting Figure B-1 Typical Atmospheric Vent Installation This page Intentionally Left Blank Length W.c. Pressure Drop Feet Appendix C Gas PipingAppendix D System Piping Appendix C Gas PipingHot Water Boilers, Non-Condensing Appendix D System PipingFigure D-0 Piping Schematic Symbols Figure D-W1 Water Boiler, Series Loop Figure D-W3 Water Boiler, Tankless Coil, Two or More Zones Figure D-W5 Water Boiler, Indirect Water Heater Confirm that the boiler and system have no water leaks Appendix E Filling the System and Checking for LeaksNatural Gas Boilers Appendix F Adjusting Gas Input RateLP/Propane Gas Boilers Appendix F Adjusting Gas Input RateLeak Test Gas Piping Table F-1 Gas Flow Rate in Cu. Ft. / HrAppendix G Checking Draft and Combustion IQ Control System Overview Appendix H iq control systemIQ Boiler Control IQ Option PanelAppendix H IQ Control System EnviraCOM Thermostats IQ Display KitAdditional Information List Appendix H IQ Control System System Parts ListFactory Mounted Components Optional ComponentsService Record Limited Warranty