Burnham manual Specifications, ES2 Series

Page 4

SPECIFICATIONS

Ratings

ES2 Series

Boiler Model

Input (MBH)

DOE Heating Capacity (MBH)

Net I=B=R Rating (MBH)

AFUE (%)

ES23

70

59

51

85

ES24

105

88

77

85

ES25

140

118

102

85

ES26

175

147

128

85

ES27

210

176

153

85

ES28

245

206

179

85

ES29

280

235

205

85

Electrical Requirements: 120VAC, 60 Hz, 1-ph, 15A

Dimensions and Connections

Boiler

Depth

Width

Height

Supply NPT

Return NPT

Vent

Gas NPT

Relief Valve

Drain

Model

 

 

 

(inch)

(inch)

(inch)

(inch)

NPT (inch)

NPT (inch)

ES23

33

12¾

41

4

½

¾

¾

ES24

33

15½

41

5

½

¾

¾

ES25

33

18½

41

6

½

¾

¾

ES26

33

21½

41

6

½

¾

¾

ES27

33

24¾

41

7

¾

¾

¾

ES28

33

27¾

41

7

¾

¾

¾

ES29

33

30¾

41

8

¾

¾

¾

Water Temperatures and Flows

Boiler Model

Allowable Supply

Minimum Return

Minimum Flow

Waterside Pressure Drop

Water Temperature

Water Temperature

(GPM)

at 20°F ΔT

 

(°F)

(°F)

(Ft. of Head)

 

 

ES23

130-220

110

None

<1

ES24

130-220

110

None

<1

ES25

130-220

110

None

<1

ES26

130-220

110

None

<1

ES27

130-220

110

None

<1

ES28

130-220

110

None

<1

ES29

130-220

110

None

<1

Weights and Volume

Boiler

Shipping Weight

Empty Weight

Water Content

Model

(lbs)

(lbs)

(gal)

ES23

250

170

2

ES24

300

220

3

ES25

350

270

4

ES26

410

320

5

ES27

460

370

5

ES28

510

420

6

ES29

560

470

7

Image 4
Contents ES2 Page Whats in the crate? Specifications ES2 SeriesSpecifications Boiler Quick-Start InstallationAppendices Unpack the Crate Position the BoilerProvide Combustion Air Connect VentingES2 Vent Connector Horizontal Length Restrictions ft Connect VentingConnect Gas Piping Connect Boiler Water PipingConnect Boiler Water Piping Description Burnham Part NumberConnect Electrical Wiring Using IQ Boiler Control Display Viewing the Operating Mode OptionsOperating Mode Options Status Code Displayed in STA ModeChanging the Adjustable Parameters More Information about Adjustable ParametersUsing the IQ Option Panel Adjustment Mode OptionsUsing the Optional LCD Display Kit Check for Gas and Water LeaksPerform Startup Checks and Adjustments Boiler restartsAnnual Maintenance Checklist Troubleshooting IQ Boiler Control Status Codes when Err is not displayedTroubleshooting IQ Boiler Control Error Codes when Err is flashingIQ Option Panel Display Shows ERR Display Status Boiler / Control ActionsRepair Parts List Repair Parts List Burner Orifices LP Gas 1.20mm IQ Boiler Control Jacket Vestibule Panel Supply Water Manifold Internal Wiring Figure IW-1 Wiring DiagramInternal Wiring Figure IW-2 Wiring SchematicFigure IW-3 Single Zone System with Domestic Hot Water Tank Figure IW-5 Multiple Zone System with Zone Valves Figure IW-7 Multiple Zone System with Zone Valve Panel Appendix a Combustion Air Combined appliance Input BTU/hrAppendix B Venting Figure B-1 Typical Atmospheric Vent Installation This page Intentionally Left Blank Appendix C Gas Piping Length W.c. Pressure Drop FeetAppendix C Gas Piping Appendix D System PipingAppendix D System Piping Hot Water Boilers, Non-CondensingFigure D-0 Piping Schematic Symbols Figure D-W1 Water Boiler, Series Loop Figure D-W3 Water Boiler, Tankless Coil, Two or More Zones Figure D-W5 Water Boiler, Indirect Water Heater Appendix E Filling the System and Checking for Leaks Confirm that the boiler and system have no water leaksAppendix F Adjusting Gas Input Rate Natural Gas BoilersAppendix F Adjusting Gas Input Rate LP/Propane Gas BoilersLeak Test Gas Piping Table F-1 Gas Flow Rate in Cu. Ft. / HrAppendix G Checking Draft and Combustion Appendix H iq control system IQ Control System OverviewIQ Boiler Control IQ Option PanelAppendix H IQ Control System IQ Display Kit EnviraCOM ThermostatsAppendix H IQ Control System System Parts List Additional Information ListFactory Mounted Components Optional ComponentsService Record Limited Warranty