Burnham ES2 manual Appendix D System Piping, Hot Water Boilers, Non-Condensing

Page 38

APPENDIX D – System Piping (continued)

(2)Comply with the boiler’s specific water quality requirements. See the Specifications Section of this manual.

(3)Comply with the boiler’s specific requirements for minimum water flow through the boiler, installing a system bypass or primary-secondary loop if necessary to maintain flow through the boiler when serving small zones.

3.Overpressure

(1)Install a properly sized expansion tank.

(2)Do not exceed the boiler’s specific requirements for maximum allowable working pressure.

(3)Do not plug or block the relief valve.

4.Freezing

(1)Run all portions of the system piping inside a heated space unless the system is properly protected with an inhibited antifreeze solution.

5.Overheating

(1)Comply with the boiler’s specific requirement for minimum water flow through the boiler. See the

Specifications Section of this manual.

(2)Install a low-water cutoff device whenever the boiler is installed above the level of the lowest heat emitter

or radiator. Also add a low-water cutoff when required by local code requirements.

6.Thermal shock

(1)Do not over-pump. Adhere to the design flow requirements for each zone.

(2)Install a boiler bypass, system bypass, or primary-secondary loop when needed to avoid returning large volumes of cold water directly to a hot boiler.

7.Condensation

(1)Do not over-pump. Adhere to the design flow requirements for each zone.

(2)Adhere to the boiler’s specific minimum return water and supply water temperature requirements. Install a boiler bypass, system bypass, or primary-secondary loop when needed to maintain water temperatures and flows within the specified limits.

(3)Do not allow chilled water to enter the boiler during the heating cycle, or heated water to enter chilled water coils during the cooling cycle.

8.Dry Fire

Install a low-water cutoff when the boiler is installed above the level of the lowest radiator and when required by local code.

The following system diagrams are intended to provide a minimum level of guidance for a

i successful and trouble-free installation of the boiler in common applications. They do not substitute for proper design, evaluation, and installation by a trained and qualified installer using the proper tools, techniques, and design expertise. Not all options are available with every boiler.

Hot Water Boilers, Non-Condensing

 

 

 

Two or more

Two or more

Two or

 

 

 

zones of

zones of

 

 

Indirect Tank?

more

 

 

the same

different

 

 

 

boilers?

 

 

 

temperature?

temperatures?

 

 

 

 

 

D-W1

 

 

 

 

 

D-W2

 

 

 

See

D-W3

Tankless Coil

 

 

 

Diagram

D-W4

 

 

 

D-W5

 

 

D-W6

 

38

Image 38
Contents ES2 Page Whats in the crate? Specifications ES2 SeriesSpecifications Appendices InstallationBoiler Quick-Start Unpack the Crate Position the BoilerProvide Combustion Air Connect VentingES2 Vent Connector Horizontal Length Restrictions ft Connect VentingConnect Gas Piping Connect Boiler Water PipingConnect Boiler Water Piping Description Burnham Part NumberConnect Electrical Wiring Operating Mode Options Using IQ Boiler Control DisplayViewing the Operating Mode Options Status Code Displayed in STA ModeUsing the IQ Option Panel Changing the Adjustable ParametersMore Information about Adjustable Parameters Adjustment Mode OptionsUsing the Optional LCD Display Kit Check for Gas and Water LeaksPerform Startup Checks and Adjustments Boiler restartsAnnual Maintenance Checklist Troubleshooting IQ Boiler Control Status Codes when Err is not displayedTroubleshooting IQ Boiler Control Error Codes when Err is flashingIQ Option Panel Display Shows ERR Display Status Boiler / Control ActionsRepair Parts List Repair Parts List Burner Orifices LP Gas 1.20mm IQ Boiler Control Jacket Vestibule Panel Supply Water Manifold Internal Wiring Figure IW-1 Wiring DiagramInternal Wiring Figure IW-2 Wiring SchematicFigure IW-3 Single Zone System with Domestic Hot Water Tank Figure IW-5 Multiple Zone System with Zone Valves Figure IW-7 Multiple Zone System with Zone Valve Panel Appendix a Combustion Air Combined appliance Input BTU/hrAppendix B Venting Figure B-1 Typical Atmospheric Vent Installation This page Intentionally Left Blank Appendix C Gas Piping Length W.c. Pressure Drop FeetAppendix C Gas Piping Appendix D System PipingAppendix D System Piping Hot Water Boilers, Non-CondensingFigure D-0 Piping Schematic Symbols Figure D-W1 Water Boiler, Series Loop Figure D-W3 Water Boiler, Tankless Coil, Two or More Zones Figure D-W5 Water Boiler, Indirect Water Heater Appendix E Filling the System and Checking for Leaks Confirm that the boiler and system have no water leaksAppendix F Adjusting Gas Input Rate Natural Gas BoilersLeak Test Gas Piping Appendix F Adjusting Gas Input RateLP/Propane Gas Boilers Table F-1 Gas Flow Rate in Cu. Ft. / HrAppendix G Checking Draft and Combustion IQ Boiler Control Appendix H iq control systemIQ Control System Overview IQ Option PanelAppendix H IQ Control System IQ Display Kit EnviraCOM ThermostatsFactory Mounted Components Appendix H IQ Control System System Parts ListAdditional Information List Optional ComponentsService Record Limited Warranty