Burnham ES2 manual Appendix F Adjusting Gas Input Rate, Natural Gas Boilers

Page 44

APPENDIX F – Adjusting Gas Input Rate

Natural Gas Boilers:

1.Turn off gas supply to all appliances other than gas-fired boiler.

2.Note the rated manifold gas pressure listed on the boiler’s rating label.

3.Connect Manometer to manifold pressure tapping on Gas Valve (Figure F-1).

F-1

4.Light main burners by adjusting thermostat to highest setting.

5.If required, adjust gas manifold pressure to the rated setting by turning the gas valves adjustment screw clockwise to decrease manifold pressure or counterclockwise to increase manifold pressure (Figure F-2). Several turns may be required.

Do not force the adjustment screw.

6.On models using more than one gas valve, turn “off” the gas valve not having pilot control and first adjust the gas valve with pilot control. Then, turn “on” both gas valves and adjust the gas valve without pilot control.

7.Clock gas meter for at least two (2) revolutions of the dial typically labeled ½ or 1 cubic foot per revolution on a residential gas meter.

44

F-2

8.Determine gas flow rate in Cubic Feet per Hour based on elapsed time for two revolutions. (Example: 70 Seconds for (2) Revolutions = 102.8 Cu. Ft.

9.When the clocked time falls between two table values (Table F-1), add the table values shown above and below your clocked reading and divide by 2 (Example: 68 Seconds for (2) Revolutions = (110.7+102.8) /2 = 106.7 Cu. Ft./Hr.).

10.Obtain gas-heating value (Btu per cubic foot) from gas supplier or use nominal value of 1000 Btu per cubic foot.

11.Multiply gas flow rate by gas heating value. (Example: 70 Seconds for (2) Revolutions = 120.8 Cu. Ft./Hr. X 1027 Btu/Cu. Ft. = 124,061 Btu/ Hr.

12.Compare measured input rate to input rate stated on rating label.

Do not exceed the boiler’s rated gas input.

13.If input is too high, reduce input rate by decreasing manifold pressure. Do not reduce more than 0.3” w.c. Instead, contact Burnham for an orifice replacement kit.

14.If input is below 98% of Rating Label input, increase manifold gas pressure no more than 0.3 inches w.c. If measured rate is still less than 98% of rated input, replace or re- drill existing main burner gas orifices:

Image 44
Contents ES2 Page Whats in the crate? Specifications ES2 SeriesSpecifications Appendices InstallationBoiler Quick-Start Unpack the Crate Position the BoilerProvide Combustion Air Connect VentingES2 Vent Connector Horizontal Length Restrictions ft Connect VentingConnect Gas Piping Connect Boiler Water PipingConnect Boiler Water Piping Description Burnham Part NumberConnect Electrical Wiring Using IQ Boiler Control Display Viewing the Operating Mode OptionsOperating Mode Options Status Code Displayed in STA ModeChanging the Adjustable Parameters More Information about Adjustable ParametersUsing the IQ Option Panel Adjustment Mode OptionsUsing the Optional LCD Display Kit Check for Gas and Water LeaksPerform Startup Checks and Adjustments Boiler restartsAnnual Maintenance Checklist Troubleshooting IQ Boiler Control Status Codes when Err is not displayedTroubleshooting IQ Boiler Control Error Codes when Err is flashingIQ Option Panel Display Shows ERR Display Status Boiler / Control ActionsRepair Parts List Repair Parts List Burner Orifices LP Gas 1.20mm IQ Boiler Control Jacket Vestibule Panel Supply Water Manifold Internal Wiring Figure IW-1 Wiring DiagramInternal Wiring Figure IW-2 Wiring SchematicFigure IW-3 Single Zone System with Domestic Hot Water Tank Figure IW-5 Multiple Zone System with Zone Valves Figure IW-7 Multiple Zone System with Zone Valve Panel Appendix a Combustion Air Combined appliance Input BTU/hrAppendix B Venting Figure B-1 Typical Atmospheric Vent Installation This page Intentionally Left Blank Appendix C Gas Piping Length W.c. Pressure Drop FeetAppendix C Gas Piping Appendix D System PipingAppendix D System Piping Hot Water Boilers, Non-CondensingFigure D-0 Piping Schematic Symbols Figure D-W1 Water Boiler, Series Loop Figure D-W3 Water Boiler, Tankless Coil, Two or More Zones Figure D-W5 Water Boiler, Indirect Water Heater Appendix E Filling the System and Checking for Leaks Confirm that the boiler and system have no water leaksAppendix F Adjusting Gas Input Rate Natural Gas BoilersAppendix F Adjusting Gas Input Rate LP/Propane Gas BoilersLeak Test Gas Piping Table F-1 Gas Flow Rate in Cu. Ft. / HrAppendix G Checking Draft and Combustion Appendix H iq control system IQ Control System OverviewIQ Boiler Control IQ Option PanelAppendix H IQ Control System IQ Display Kit EnviraCOM ThermostatsAppendix H IQ Control System System Parts List Additional Information ListFactory Mounted Components Optional ComponentsService Record Limited Warranty