Burnham ES2 Program the Controls, Changing the Adjustable Parameters, Using the IQ Option Panel

Page 14

8. Program the Controls (continued)

1 sec

1 sec

Unit Display

 

 

 

1 sec

Sample

 

OR

 

 

Display

 

 

Please note that in operating mode to hold the display on the value the user can press and hold either the Up ñ or Down ò keys and the value will be continuously shown. This may be helpful in watching a value “live”.

Changing the Adjustable Parameters

To adjust the High Limit setpoint, High Limit Differential or Pump Overrun time settings or setting the display for either °F or °C temperature readings:

1.Access the adjustment mode by pressing and holding the Up , Down , and “I” keys simultaneously for three (3) seconds. This procedure is intended to discourage unauthorized changes or accidental changes to limit settings.

2.Press the "I" key to display available Adjustment Mode options. Select an option.

Adjustment Mode Options

HL_ Adjust High Limit Setting

dF_ Adjust High Limit Differential Or_ Pump Overrun Time (minutes) rst Reset Lockout

f-C Select degrees F or C Mode bac Back to Operating Mode

3.Press the Up and Down keys to adjust the displayed setpoint to the desired value.

4.To return to the normal operating mode from the Adjustment Mode, when the "bAc” option is displayed, press either the Up ñ or Down ò key. If no keys are pressed, after five (5) minutes the IQ Boiler Control will automatically return to the Operating Mode.

More Information about Adjustable Parameters

1.High Limit (HL_)

The IQ Control is factory programmed

with a High Limit Setpoint of 180°F. The boiler turns "off" when the supply water temperature is above this value. The High Limit setpoint is adjustable between 130° and 220°F. The Operating Setpoint (SP) will equal the High Limit Setpoint unless an IQ Outdoor Reset IQ Option Card is installed. The Outdoor Reset IQ Option Card reduces the Operating Setpoint to regulate heat delivery, increase home comfort and

save energy. Refer to the Appendix H for additional information.

2.Differential (df_)

The IQ Boiler Control is factory programmed with a Differential of 15°F. The Differential is the number of degrees the supply temperature must decrease below the Operating Setpoint before the boiler can restart. The differential is adjustable between 10° through 30°F.

3.Pump Overrun Time (OR_)

The IQ Boiler Control is factory programmed with a Pump Overrun Time of 0 minutes. Pump Overrun Time (also called “off delay” or “post purge”) continues pump operation after a call for heat has ended, sending excess heat from the boiler into the priority zone. Ensure system piping and zone panel settings allow water flow to the priority zone after the call for heat ends. The Pump Overrun Time is adjustable between 0 through 10 minutes.

Using the IQ Option Panel

IQ Option Cards are available from Burnham distributors and are the simplest way to add functionality, safety and efficiency to your heating system. The IQ Option Panel provides an easy and convenient means to "plug-in" an Auxiliary High Limit, Low Water Cut-off and/or Outdoor Reset function.

For installation, programming, and troubleshooting instructions, refer to the instructions supplied with those cards.

14

Image 14
Contents ES2 Page Whats in the crate? Specifications ES2 SeriesSpecifications Appendices InstallationBoiler Quick-Start Unpack the Crate Position the BoilerProvide Combustion Air Connect VentingES2 Vent Connector Horizontal Length Restrictions ft Connect VentingConnect Gas Piping Connect Boiler Water PipingConnect Boiler Water Piping Description Burnham Part NumberConnect Electrical Wiring Operating Mode Options Using IQ Boiler Control DisplayViewing the Operating Mode Options Status Code Displayed in STA ModeUsing the IQ Option Panel Changing the Adjustable ParametersMore Information about Adjustable Parameters Adjustment Mode OptionsUsing the Optional LCD Display Kit Check for Gas and Water LeaksPerform Startup Checks and Adjustments Boiler restartsAnnual Maintenance Checklist Troubleshooting IQ Boiler Control Status Codes when Err is not displayedTroubleshooting IQ Boiler Control Error Codes when Err is flashingIQ Option Panel Display Shows ERR Display Status Boiler / Control ActionsRepair Parts List Repair Parts List Burner Orifices LP Gas 1.20mm IQ Boiler Control Jacket Vestibule Panel Supply Water Manifold Internal Wiring Figure IW-1 Wiring DiagramInternal Wiring Figure IW-2 Wiring SchematicFigure IW-3 Single Zone System with Domestic Hot Water Tank Figure IW-5 Multiple Zone System with Zone Valves Figure IW-7 Multiple Zone System with Zone Valve Panel Appendix a Combustion Air Combined appliance Input BTU/hrAppendix B Venting Figure B-1 Typical Atmospheric Vent Installation This page Intentionally Left Blank Appendix C Gas Piping Length W.c. Pressure Drop FeetAppendix C Gas Piping Appendix D System PipingAppendix D System Piping Hot Water Boilers, Non-CondensingFigure D-0 Piping Schematic Symbols Figure D-W1 Water Boiler, Series Loop Figure D-W3 Water Boiler, Tankless Coil, Two or More Zones Figure D-W5 Water Boiler, Indirect Water Heater Appendix E Filling the System and Checking for Leaks Confirm that the boiler and system have no water leaksAppendix F Adjusting Gas Input Rate Natural Gas BoilersLeak Test Gas Piping Appendix F Adjusting Gas Input RateLP/Propane Gas Boilers Table F-1 Gas Flow Rate in Cu. Ft. / HrAppendix G Checking Draft and Combustion IQ Boiler Control Appendix H iq control systemIQ Control System Overview IQ Option PanelAppendix H IQ Control System IQ Display Kit EnviraCOM ThermostatsFactory Mounted Components Appendix H IQ Control System System Parts ListAdditional Information List Optional ComponentsService Record Limited Warranty