WARNING
A hot water boiler installed above radiation level must be provided with a low water cutoff device as part of the installation.
1.HOT WATER HEATING - This boiler must be installed in strict accordance to the instructions found in this installation manual. Deviations from these installation instructions may void manufacturer’s warranty. See warning below to determine the use of the RTC. A Return Temperature Control (RTC) may be provided to protect the boiler from thermal shock and sustained condensing operation. In addition, a properly selected boiler circulator and diverting valve, along with the return sensor, must be installed when using the RTC. A number of typical Crown applications have been added to the appendix (Appendix A). Select the appropriate application before proceeding.
a.Parallel Piping Systems – An existing parallel piping system may be used, provided the return water is not below 135°F for prolonged periods of time, and the return water temperature is not more than 40°F less than the idle boiler temperature (see warning below). A flow analysis should be performed to determine the flow through the boiler when the minimum (and smallest) and maximum number of zones are activated. A sufficient flow through the boiler should be maintained to assure a maximum of 40°F difference between the boiler supply and return.
If the conditions above cannot be met, then parallel piping systems must be converted to a primary/secondary arrangement,
A
b.Primary/Secondary Piping – Boiler(s) must be installed into a heating system that is (are) designed as a primary/secondary piping arrangement when the flow through the boiler cannot be maintained to provide a 20°F - 40°F difference between the boiler supply and return. When using an RTC, the boiler loop contains a boiler, boiler circulator and diverting valve, along with the return temperature control (RTC) and return sensor. The diverting valve consists of a
c.Multiple Boilers – Multiple boilers are installed the same as single boiler installations. Each boiler loop will contain it’s own boiler circulator, diverting valve, RTC and return sensor (see Appendix A). Commonly available sequencers can be used in conjunction with the Return Temperature Control by energizing the control’s heat demand circuit. The outdoor reset feature of the sequencer must be used in multiple boiler installations. The outdoor reset feature
WARNING
Return water cannot be lower than 135°F for prolonged periods of time. Operation under these conditions will result in sustained condensing within the combustion chamber and potentially reduce boiler longevity.
In addition, the return water cannot be introduced into the boiler if it is more than 40°F less than the idle boiler temperature. Continued operation under these conditions may result in premature boiler failure through thermal shock.
Example: A boiler that has been idle for some time since the last heat demand cycle may have it's boiler water temperature reduced to 150°F. The return temperature from the next zone activation cannot be less than 110°F.
If the above conditions exist, an RTC system must be installed to protect the boiler from sustained condensing operation and thermal shock.
33