SECTION VI - BURNER SPECIFICATIONS
NOTICE
Series 24 boiler ratings and capacities are based upon the following burners, pump pressures, noz z le siz es and manifold pressures. Refer to instructions furnished with burner for additional information regarding proper installation, fuel piping, wiring details, burner adjustments, service instructions and burner
Table VI: Beckett Burner Specifications
OIL BURNERS
| BURNER |
|
|
|
| BURNER SETTINGS |
| PUMP PRESS. |
| NOZZLE DATA | |||||
BOILER | BURNER | BURNER | AIR TUBE |
|
|
| (PSI) | NOZZLE | |||||||
|
|
|
|
|
|
| |||||||||
INPUT |
|
|
|
|
|
|
|
|
| ||||||
MODEL | MFR. | MODEL | COMB. |
|
|
|
|
|
|
|
| MAKE |
| ||
(GPH) | HEAD | AIR | AIR | AIR DAMPER | LOW |
| HIGH | GPH X | |||||||
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
| |||||||||
|
|
|
|
| SHUTTER | BAND | LOW | HIGH | FIRE |
| FIRE |
| |||
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
3.1 | BECKETT | CF60KK | 2 | 10 | 3 | N/A | N/A |
| 150 | HAGO | 2.50 X 45° - P | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
4.2 | BECKETT | CF80KH | 1 | 8 | 0 | N/A | N/A |
| 150 | HAGO | 3.50 X 45° - P | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
5.6 | BECKETT | CF80KH | 2 | 10 | 6 | N/A | N/A |
| 150 | HAGO | 4.50 X 45° - P | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
7.0 | BECKETT | CF66KD | 3 | N/A | N/A | 2.75 | 4.0 | 150 |
| 300 | HAGO | 4.00 X 60° - P | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
8.3 | BECKETT | CF66KD | 4 | N/A | N/A | 3.0 | 6.5 | 150 |
| 275 | HAGO | 5.00 X 45° - P | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
9.6 | BECKETT | CF66KEE | 1 | N/A | N/A | 3.5 | 8.5 | 150 |
| 300 | HAGO | 5.50 X 45° - P | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
11.6 | BECKETT | CF66KG | 0 | N/A | N/A | 2.0 | 4.0 | 150 |
| 275 | HAGO | 7.00 X 45° - P | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
13.2 | BECKETT | CF66KG | 1 | N/A | N/A | 2.0 | 6.0 | 150 |
| 275 | HAGO | 8.00 X 45° - P | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
14.8 | BECKETT | CF66KP | 0 | N/A | N/A | 0.5 | 3.0 | 275 |
| 275 | HAGO | (L) 4.50 X 45° - P | |||
|
| ||||||||||||||
(H) 4.50 X 45° - P | |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
16.4 | BECKETT | CF66KP | 0 | N/A | N/A | 0.5 | 4.0 | 275 |
| 275 | HAGO | (L) 5.00 X 45° - P | |||
|
| ||||||||||||||
(H) 5.00 X 45° - P | |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GAS BURNERS (Natural Gas)
Boiler | Gas |
| Damper Settings |
| Manifold Pressure ("WC) | Rate |
| Minimum Inlet Pressure "WC1 |
| ||||||
Burner |
| High |
|
| Low Fire |
|
|
| By Gas Train Pipe Size |
| |||||
Model | Low Fire | Shutter | Band | High Fire | Control |
|
|
| |||||||
Model | Fire | (Start) |
|
|
|
|
|
|
| ||||||
1" |
| 1 1/4" | 1 1/2" | 2" |
| 2 1/2" | |||||||||
|
|
|
|
|
|
|
| ||||||||
CG10.1S |
|
| 10 | 1 | (1.3) | 2.5 | On/Off | 3.24 |
| 3.13 |
| ||||
CG10.4S |
|
| 5 | 2 | (1.3) | 2.6 | On/Off | 3.64 |
| 3.4 |
| ||||
CG10.5S |
|
| 7 | 1 | (1) | 3.3 | On/Off | 4.61 |
| 4.26 |
| ||||
CG10.6S |
|
| 10 | 6 | (1.1) | 3.64 | On/Off | 5.43 |
| 4.76 | 4.38 |
| |||
CG15.3S | 18 | 43 |
|
| 0.9 | 3.1 | Lo/Hi/Lo | 5.31 |
| 4.44 | 3.99 |
| |||
CG15.4S | 21 | 63 |
|
| 0.95 | 3.3 | Lo/Hi/Lo | 6.14 |
| 4.9 | 4.41 |
| |||
CG25.2S | 23 | 47 |
|
| 0.8 | 3.43 | Lo/Hi/Lo |
| 4.69 | 4.28 | 3.86 |
| |||
CG25.3S | 26 | 52 |
|
| 0.8 | 3.44 | Lo/Hi/Lo |
| 4.94 | 4.4 |
| 3.98 | |||
CG25.4S | 28 | 58 |
|
| 0.8 | 3.0 | Lo/Hi/Lo |
| 4.88 | 4.21 |
| 3.68 | |||
CG50.2S | 10 | 25 |
|
| 0.8 | 2.1 | Lo/Hi/Lo |
| 3.87 | 3.56 |
| 2.94 |
1. Standard burners are indicated with bold numbering in shaded boxes. The other burners shown are optional.
57