Crown Boiler 24-03, 24-11, 24-10, 24-08, 24-12, 24-06 Section VI Burner Specifications, OIL Burners

Page 57

SECTION VI - BURNER SPECIFICATIONS

NOTICE

Series 24 boiler ratings and capacities are based upon the following burners, pump pressures, noz z le siz es and manifold pressures. Refer to instructions furnished with burner for additional information regarding proper installation, fuel piping, wiring details, burner adjustments, service instructions and burner start-up.

Table VI: Beckett Burner Specifications

OIL BURNERS

 

BURNER

 

 

 

 

BURNER SETTINGS

 

PUMP PRESS.

 

NOZZLE DATA

BOILER

BURNER

BURNER

AIR TUBE

 

 

 

(PSI)

NOZZLE

 

 

 

 

 

 

 

INPUT

 

 

 

 

 

 

 

 

 

MODEL

MFR.

MODEL

COMB.

 

 

 

 

 

 

 

 

MAKE

 

(GPH)

HEAD

AIR

AIR

AIR DAMPER

LOW

 

HIGH

GPH X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHUTTER

BAND

LOW

HIGH

FIRE

 

FIRE

 

ANGLE-TYPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-03

3.1

BECKETT

CF-500

CF60KK

2

10

3

N/A

N/A

---

 

150

HAGO

2.50 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-04

4.2

BECKETT

CF-800

CF80KH

1

8

0

N/A

N/A

---

 

150

HAGO

3.50 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-05

5.6

BECKETT

CF-800

CF80KH

2

10

6

N/A

N/A

---

 

150

HAGO

4.50 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-06

7.0

BECKETT

CF-1400

CF66KD

3

N/A

N/A

2.75

4.0

150

 

300

HAGO

4.00 X 60° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-07

8.3

BECKETT

CF-1400

CF66KD

4

N/A

N/A

3.0

6.5

150

 

275

HAGO

5.00 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-08

9.6

BECKETT

CF-1400

CF66KEE

1

N/A

N/A

3.5

8.5

150

 

300

HAGO

5.50 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-09

11.6

BECKETT

CF-2300A

CF66KG

0

N/A

N/A

2.0

4.0

150

 

275

HAGO

7.00 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-10

13.2

BECKETT

CF-2300A

CF66KG

1

N/A

N/A

2.0

6.0

150

 

275

HAGO

8.00 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-11

14.8

BECKETT

CF-2500

CF66KP

0

N/A

N/A

0.5

3.0

275

 

275

HAGO

(L) 4.50 X 45° - P

 

 

(H) 4.50 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-12

16.4

BECKETT

CF-2500

CF66KP

0

N/A

N/A

0.5

4.0

275

 

275

HAGO

(L) 5.00 X 45° - P

 

 

(H) 5.00 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GAS BURNERS (Natural Gas)

Boiler

Gas

 

Damper Settings

 

Manifold Pressure ("WC)

Rate

 

Minimum Inlet Pressure "WC1

 

Burner

 

High

 

 

Low Fire

 

 

 

By Gas Train Pipe Size

 

Model

Low Fire

Shutter

Band

High Fire

Control

 

 

 

Model

Fire

(Start)

 

 

 

 

 

 

 

1"

 

1 1/4"

1 1/2"

2"

 

2 1/2"

 

 

 

 

 

 

 

 

24-03

CG10.1S

 

 

10

1

(1.3)

2.5

On/Off

3.24

 

3.13

--

--

 

--

24-04

CG10.4S

 

 

5

2

(1.3)

2.6

On/Off

3.64

 

3.4

--

--

 

--

24-05

CG10.5S

 

 

7

1

(1)

3.3

On/Off

4.61

 

4.26

--

--

 

--

24-06

CG10.6S

 

 

10

6

(1.1)

3.64

On/Off

5.43

 

4.76

4.38

--

 

--

24-07

CG15.3S

18

43

 

 

0.9

3.1

Lo/Hi/Lo

5.31

 

4.44

3.99

--

 

--

24-08

CG15.4S

21

63

 

 

0.95

3.3

Lo/Hi/Lo

6.14

 

4.9

4.41

--

 

--

24-09

CG25.2S

23

47

 

 

0.8

3.43

Lo/Hi/Lo

--

 

4.69

4.28

3.86

 

--

24-10

CG25.3S

26

52

 

 

0.8

3.44

Lo/Hi/Lo

--

 

--

4.94

4.4

 

3.98

24-11

CG25.4S

28

58

 

 

0.8

3.0

Lo/Hi/Lo

--

 

--

4.88

4.21

 

3.68

24-12

CG50.2S

10

25

 

 

0.8

2.1

Lo/Hi/Lo

--

 

--

3.87

3.56

 

2.94

1. Standard burners are indicated with bold numbering in shaded boxes. The other burners shown are optional.

57

Image 57
Contents Series Page Important Information Read Carefully Page Page Table of Contents Table of Contents Section I General Information Boiler RATINGS/DATA Locate the Unit Section I General InformationChimney or Vent Boiler FoundationVents Faults & Suggestions Assembly of Sections Manual DRAW- UP Section II Cast Iron Block AssemblyNipple Gauge Series 24 Section Arrangement Draw-Up Rods Alternating Pattern Manual Draw-up Center Section Channel Block Position Partial Block Draw-Up Hydraulic Draw-Up of Sections Canopy with Rear Flue Outlet Damper Assembly Section III Installation InstructionsBare Boiler Assembly Avoid Breathing Fiber Particulates and Dust Left Side Canopy Intermediate Bracket Inspect ALL Boiler Seals Mount Rear Observation Port Cover Refer to FigureSeries 24 Jacket Assembly Boiler Models 24-03 thru Mount Burner Adapter Plate to Burner Mounting Plate Burner Mounting Plate Refer to Figures 16Purpose of Tappings Steam Boilers Steam Trim Steam Boilers Install Steam Trim This Is Intentionally Left Blank Purpose of Tappings Water Boilers Water Trim Water Boilers Install Water Trim Burner InstallationBoiler Piping Heating Applications Page Parallel Piping Conversion Recommendation 1 Use when Recommendation 2 Use when Recommendation 3 Use when Page Page Page BMounting Elevations M&M 150, 64 Float Low Water Cut-offs Schematic Tankless Heater Piping 24-08 24-09 CCW Open to System Return Temperature Control and ComponentsWater Boiler Pressure Relief Valve Hook-Up Typical Boiler Wiring with RTC Front Typical Boiler with RTC Return Sensor Rear Section IV Operating Instructions Always Inspect Installation BeforeStarting Burner Fill Heating System with WaterFlame Failure Boil MIN Delay Check Operation of High Limit Control Test ControlsBoiler and System Cleaning Steam Boiler Boiler and System Cleaning Water Boilers Oxygen Corrosion Frequent Water AdditionClean the Boiler Flueways Section V Service InstructionsMaintenance of LOW Water Cutoff Devices Operation General Maintenance ConsiderationsOIL Burners Section VI Burner SpecificationsSection VII Repair Parts & Carton Contents Series 24 Master Parts List Section VII Repair Parts Jacket Carton Bare Boiler Assembly Section Joiner Carton Assy Rear Target Wall Carton Standard Steam Trim Carton Assy RTC Carton with Outdoor Reset Tankless Coil Components Boiler Water Section Viii Appendix Page Mechanical Page Mechanical Electrical Page Page Page Page Page Page Page Page Series 24 Boiler Circulator Selection Taco 20F Differential Boiler Recirculation Grundfos Circulating Pump Way Boiler Recirculation Bell and Gossett Circulating Pump Way Boiler Recirculation Armstrong Circulating Pump Way Application Appendix C Valve and Actuator Mounting InstructionsService Record PN 980417 S24 12/05