A2.
(MECHANICAL)
72
NOTES:
1)Install the boiler as indicated above for systems where return temperatures may be less than 135F and heating/DHW with tankless coils.
2)The Outdoor Sensor (S3) and the Mix Supply Sensor (S2) are required when the Outdoor Reset feature is selected. The mix sensor must be installed 10 pipe diameters downstream of the system pump, in the primary loop. The mix sensor must be secured to the surface of the pipe using a wire tie or similar device.
3)The
4)Closely spaced tees must connect the branch to the larger header. The Tee centerlines must be no greater than 4 times the larger header pipe diameter.
5)The diverting valve, V1, must be no greater than 11 linear feet of pipe from the Return Sensor, S1.
6)There shall be a MINIMUM of 4 linear feet of pipe between the
7)The balancing valve in the boiler return line, V2, may be necessary in low head
8)Domestic Hot Water must be tempered for safe usage. The tankless aquastat and/or a storage tank aquastat (A1) are normally closed switches. Circuit breaks on temperature rise.
9)Expansion tanks, air scoops and other components left out for clarity.
10)Observe all applicable plumbing and electrical codes.
This diagram is for reference only. The installer or designer is responsible for the proper selection and design of the system.