Crown Boiler 24-11, 24-10, 24-08, 24-12, 24-06 Test Controls, Check Operation of High Limit Control

Page 50

both the boiler circulator and the diverting valve during periods of dormant activity provided power is supplied to the control.

F.DIVERTING VALVE ACTUATOR - A 3-way diverting valve is used to control the temperature of the water returning to the boiler. Proper operation is required to protect the boiler from thermal shock and sustained condensate production. Confirm the operation of the valve as shown above. See Figures 39a and 39b.

G.BOILER OPERATING AQUASTAT – The operating aquastat, L4006A, can be found on the front of the boiler, to the right of the temperature/pressure gauge. The operating aquastat should be set to the designed supply temperature, typically 180ºF. The operating aquastat set point, the RTC MIX TARGET or the RTC MIX DESGN, should be set to the same value for 20°F ∆T applications. In 40°F ∆T applications, the operating aquastat (L4006A) must be set 20°F higher than the MIX TARGET and MIX DESIGN . Under no circumstances should the operating aquastat be set below 135ºF plus (+) the designed boiler temperature drop, ∆T (ºF).

Example: if the flow rate through the boiler corresponds to a 20ºF ∆T design, the operating aquastat cannot be set lower than 135 + 20 = 155ºF.

In reality, most systems are designed for a 180ºF supply water and 160ºF return water. The accuracy of the operating aquastat is less than the RTC accuracy, often requiring the operating aquastat temperature to be bumped upward a few degrees.

H.BOILER HIGH LIMIT AQUASTAT – If used, the high limit aquastat, L4006E, can be found on the front of the boiler, to the left of the temperature/pressure gauge. The high limit aquastat can be identified with a red manual reset button. Ideally, the high limit aquastat should be set 10 -15°F above the RTC MIX MAX setting, when the outdoor reset feature is selected. Typically, this is set between 200ºF and 220ºF. The temperature must be set below the lowest permissible temperature for any system related component affected by boiler supply water. Under no circumstances can the high limit aquastat be set higher than 250ºF.

I.BOILER MODULATING CONTROL – Various controls are used to modulate burner firing rates. No attempt will be made to cover every possibility, however a general outline will be given.

Most modulation controls require the entry of a boiler temperature identifying boiler operation at the maximum firing rate. A boiler operating temperature below that will also generate a full firing rate. When a boiler heat demand is generated the unit will initiate at either a low or high fire rate and quickly ramp up to the

high fire rate. The unit will continue to fire at the high fire rate until the boiler high fire modulating limit is reached.

Many modulation controls require the entry of a burner off or low fire setting. The burner will modulate between the high fire and low fire rate based on the absolute boiler temperature as well as the rate of change in boiler temperature.

If using a T991 Proportional Control or a similar modulating device in a traditional hydronic system, the minimum setting shall be the sum of the designed heating system return temperature + boiler ∆T + 10°F.

Example: System Supply 180°F

System Return

160°F

System ∆T

20°F

Boiler ∆T

40°F

Min. Setting = 160°F + 40°F + 10°F = 210°F

*NOTE: A higher flow through the boiler, achieving a 20°F ∆T would lower the minimum to 190°F.

If using the same control in a system where the designed return is less than 135°F, then the minimum becomes:

135°F + Boiler ∆T + 10°F

J.TEST CONTROLS

WARNING

Before installation of the boiler is considered complete, the operation of the boiler controls should be checked, particularly the low water cutoff and the high limit control.

All controls must be checked prior to putting the boiler in service.

1.CHECK OPERATING CONTROL OPERATION. Raise and lower operating control setting as required to start and stop burner.

2.CHECK OPERATION OF HIGH LIMIT CONTROL —

Jumper Operating Control Terminals. Allow burner to operate until shutdown by limit. Installation is not considered complete until this check has been made. REMOVE JUMPER.

3.CHECK LOW WATER CUTOFF control with water level at normal water line (see Figure 1). Raise operating control setting to allow burner to operate. Open boiler drain to allow water level to drop to bottom of sight glass until burner operation is shut down by low water cutoff.

Close boiler drain and refill to normal water line. Burner should automatically restart during fill.

RESET OPERATING CONTROL.

50

Image 50
Contents Series Page Important Information Read Carefully Page Page Table of Contents Table of Contents Section I General Information Boiler RATINGS/DATA Section I General Information Locate the UnitBoiler Foundation Chimney or VentVents Faults & Suggestions Section II Cast Iron Block Assembly Assembly of Sections Manual DRAW- UPNipple Gauge Series 24 Section Arrangement Draw-Up Rods Alternating Pattern Manual Draw-up Center Section Channel Block Position Partial Block Draw-Up Hydraulic Draw-Up of Sections Section III Installation Instructions Canopy with Rear Flue Outlet Damper AssemblyBare Boiler Assembly Avoid Breathing Fiber Particulates and Dust Left Side Canopy Intermediate Bracket Mount Rear Observation Port Cover Refer to Figure Inspect ALL Boiler SealsSeries 24 Jacket Assembly Boiler Models 24-03 thru Burner Mounting Plate Refer to Figures 16 Mount Burner Adapter Plate to Burner Mounting PlatePurpose of Tappings Steam Boilers Steam Trim Steam Boilers Install Steam Trim This Is Intentionally Left Blank Purpose of Tappings Water Boilers Water Trim Boiler Piping Heating Applications Water Boilers Install Water TrimBurner Installation Page Parallel Piping Conversion Recommendation 1 Use when Recommendation 2 Use when Recommendation 3 Use when Page Page Page BMounting Elevations M&M 150, 64 Float Low Water Cut-offs Schematic Tankless Heater Piping 24-08 24-09 Return Temperature Control and Components CCW Open to SystemWater Boiler Pressure Relief Valve Hook-Up Typical Boiler Wiring with RTC Front Typical Boiler with RTC Return Sensor Rear Starting Burner Always Inspect Installation BeforeSection IV Operating Instructions Fill Heating System with WaterFlame Failure Boil MIN Delay Test Controls Check Operation of High Limit ControlBoiler and System Cleaning Steam Boiler Boiler and System Cleaning Water Boilers Frequent Water Addition Oxygen CorrosionSection V Service Instructions Clean the Boiler FluewaysMaintenance of LOW Water Cutoff Devices General Maintenance Considerations OperationSection VI Burner Specifications OIL BurnersSection VII Repair Parts & Carton Contents Series 24 Master Parts List Section VII Repair Parts Jacket Carton Bare Boiler Assembly Section Joiner Carton Assy Rear Target Wall Carton Standard Steam Trim Carton Assy RTC Carton with Outdoor Reset Tankless Coil Components Boiler Water Section Viii Appendix Page Mechanical Page Mechanical Electrical Page Page Page Page Page Page Page Page Series 24 Boiler Circulator Selection Taco 20F Differential Boiler Recirculation Grundfos Circulating Pump Way Boiler Recirculation Bell and Gossett Circulating Pump Way Boiler Recirculation Armstrong Circulating Pump Way Appendix C Valve and Actuator Mounting Instructions ApplicationService Record PN 980417 S24 12/05