of installation.
5.ON WATER BOILERS WITH TANKLESS HEATERS, set low limit operating control dial at 190°F and high limit dial 210°F. Operating control must be a minimum of 20° below high limit setting. Set differential at 25°.
D.ADJUST BURNER according to the Burner Manual.
1.FLAME FAILURE
The Series 24 boiler controls operate the burner automatically. If for unknown reasons the burner ceases to fire and the reset button on the primary control is tripped, the burner has experienced ignition failure. Before pressing the reset button, call your serviceman immediately.
WARNING
Do not attempt to start the burner when excess oil or gas has accumulated in the combustion chamber, when the unit is full of vapor, or when the combustion chamber is very hot.
E.RETURN TEMPERATURE CONTROL: Initial
1.Initial
2.Testing – The RTC should be tested on initial start- up, as well as during any troubleshooting exercise.
Depressing the test button will activate a test sequence and energize the red test light on the front of the control. Each of the controllers outputs and relays will be energized and tested. One may pause the test sequence at any time by depressing the test button. See the RTC Installation & Maintenance Manual for a detailed description of the sequence and the potential error messages.
a.Return Sensor - The return sensor must be properly connected or an error message will be displayed. Both a short and an open circuit in the sensor circuit will cause an error message to be displayed and the valve will be moved to a partially open position until the error is resolved.
b.Valve Actuator – During the valve actuator test sequence, confirm that the valve travels through 90 degrees of rotation from a full closed position to a full open position. The pointer on the shaft must rotate from “10” to “0” respectively.
3.Adjust Setpoints – The RTC must have a number of setpoints adjusted for proper operation. Below is a summary, however see the RTC Installation and Maintenance Manual for more details. To activate the ADJUST menu, simultaneously depress and
hold the Item, and buttons. ADJUST will appear in the upper right hand corner of the LED display.
a.ROOM - Set desired room temperature. This will provide parallel shift to heating curve.
OUTDR DESIGN OFF
b.MIX TARGET – This represents a fixed target supply temperature when the outdoor reset feature in NOT selected. (OUTDR DESIGN = OFF) Set the MIX TARGET temperature to the designed boiler supply temperature. Example: If the boiler loop is designed to supply hot water to the system at 180ºF, set the MIX TARGET to 180ºF. This is also the same as the operating aquastat set point. The mix target is adjustable from 60°F to 200ºF. The default setting is 180°F. NOTE: This function is only for applications where the mix sensor is installed.
c.MIX DSGN – Mix design temperature represents the design heating system supply temperature when the outdoor reset feature is selected. (OUTDR DESIGN = ON) This represents the design of the system loop. If unsure of the original design temperature, set the MIX DSGN to the same temperature as the boiler operating aquastat, typically 180ºF. The MIX DSGN is adjustable from 70°F to 210ºF. The default setting is 180°F.
d.OUTDR DSGN – The outdoor design temperature represents the value used in the heat loss calculations, when the outdoor reset feature is selected. (OUTDR DESIGN = ON) If this value is unknown, use the value found in
48