Page 16 | BRADFORD WHITE CORP. |
|
|
|
|
| C |
SYSTEM |
|
RETURN | B |
| A |
PUMP LOCATION FOR
T1
COLD WATER
C
| SYSTEM |
SYSTEM PUMP | SUPPLY |
B
A
ADJUSTMENT PROCEDURE TO MAINTAIN 120°F INLET TEMP:
1.Turn on boiler and open valves A & B.
2.After
3.If T1 is greater than 120°F, slowly close valve A until T1 drops to 120°F.
4.Check after system operating temperature has stabilized. Make final adjustments.
T1
CAUTION: THIS DRAWING SHOWS SUGGESTED |
|
| ||
PIPING CONFIGURATION AND VALVING, CHECK | PUMP LOCATION FOR | |||
WITH LOCAL CODES AND ORDINANCES FOR | ||||
ADDITIONAL REQUIREMENTS. |
|
| PRIMARY/SECONDARY MANDITORY FOR ALL | |
|
|
|
| |
|
|
|
| VARIABLE FLOW SYSTEMS |
|
|
|
| INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM |
LEGEND |
|
| PIPING & SIZING OF EXPANSION TANK | |
|
|
|
| |
|
| EXPANSION TANK | PER TANK MANUFACTURER'S INSTRUCTIONS | |
THERMOMETER |
| DIMENSION "C" (COMMON PIPING) TO BE FOUR | ||
| WITH AIR SCOOP AND | |||
|
| |||
|
| PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES) | ||
|
| AUTO AIR VENT | ||
TEMPERATURE | PURGE |
|
|
|
VALVE |
|
| BOILER CIRCUIT PIPING MUST BE EQUAL | |
SENSOR |
|
| ||
|
| TO BOILER WATER CONNECTION SIZE | ||
GLOBE VALVE |
| BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER | ||
|
|
| ||
|
|
|
| |
CHECK VALVE |
| VALVE |
| DOTTED DEVICES INDICATE ALTERNATE LOCATIONS |
|
|
| ||
|
|
| PUT BOILER CONTROL SENSOR IN THE SYSTEM | |
|
|
|
| |
PRESSURE REDUCING VALVE |
|
| SUPPLY WHEN USING THIS PIPING STYLE. | |
|
|
| ||
W/ FAST FILL BYPASS | PUMP |
| MINIMUM BOILER INLET WATER TEMPERATURE | |
|
|
|
| MUST BE AT LEAST 120°F. |