Bradford-White Corp BWCH, BWCV warranty Troubleshooting the Temperature Control

Page 52

Page 52

BRADFORD WHITE CORP.

 

 

 

 

8.6Troubleshooting the Temperature

Control

See Table 12.

8.7Troubleshooting Copper Brute II

Controls

The Copper Brute II series consists of two 2-stage models (500 and 750), one 3-stage model (1000), and four 4-stage models (1250 to 2000). The 2-stage models have one ignition module, and the 3- and 4-stage models have two ignition modules capable of independent operation.

A diagnostic panel, that includes test points, as well as diagnostic lights, is provided in the control module. It is located on the right side of the module, behind the display. To access, remove the retaining screws from the display cover panel and remove it. Grasp the control module at its base and pull it outward. Ladder diagrams are shown in Figures 16 through 18. Voltage test points on the diagnostic panel are indicated by solid circles connected by short diagonal lines.

Figure 16 shows the diagram for the 2-stage sizes 500 and 750. These have one blower and one ignition module. The blower is energized directly through the “inducer” terminals F1 and F2 of the (Fenwal) ignition module. The 24V power to the 2nd stage gas valve is routed through the 1st stage VALVE terminal, so that stage 2 cannot fire unless the stage 1 gas valve is open. The 750 differs from the 500 only in that the 750 has two gas trains in stage 1, while the 500 has only one.

The ladder diagram for the size 1000 is shown in Figure 17. Ignition module #1 handles stages 1 and

2, and ignition module #2 handles stage 3. The single blower is energized directly through the “inducer” terminals of either ignition module. The 24V power to the T’STAT terminal of both ignition modules is routed through the safety interlocks.

The ladder diagram for sizes 1250 to 2000 is shown in Figure 18. These 4-stage models have two ignition modules, each with its own blower, and each controlling 2 stages. The blowers are energized by the ignition modules indirectly via switching relays. When either ignition module receives a call for heat, it switches its blower to high speed and the blower of the idle ignition module to low speed.

The wiring schematics for the Copper Brute II 500 – 1000 are shown in Figure 19, the schematics for the 1250–1500 are shown in Figure 20, and Figure 21 shows the schematic for 1750–2000. All 24V wiring is routed through the diagnostic PC board. Wiring harnesses connect between the diagnostic PC board and the control components, indicator board, or field wiring terminal strip. The diagnostic board contains LEDs that indicate open status of the safety interlocks, and quick-connect terminals that provide tests points for checking voltage/continuity at various points in the control circuit. Line-voltage connections are routed via the line-voltage terminal buss.

Certain control elements that may need to be re-wired in the field are connected via the field wiring terminal strip rather than to the diagnostic PC board. These include the low-water cutoff (LWCO), water flow switch, and inlet/outlet water temperature sensors.

Image 52
Contents Copper Brute Table of Contents Maintenance Trouble ShootingReplacement Parts Operating InstructionsIntroduction General InformationModel Identification Dimensions WarrantyLocating the Appliance Dimensional Data Inches 91cm horizontally Venting and Combustion Air Combustion AirCombustion Air From Room Intake Combustion AirVenting Vent CategoriesCategory I Vent Common Venting SystemsCombustion Air and Vent Through Side Wall Locating Vent & Combustion Air Terminals Category III VentSide Wall Vent Terminal Side Wall Combustion Air TerminalCommon Vent Test Boilers Vent Terminals for Outdoor UnitsVertical Vent Terminal Vertical Combustion Air TerminalGas Supply and Piping 61-91mWater Connections Copper Brute II Boiler 4A.1 Heating System Piping Hot Supply Connections Boiler4A.2 Cold Water Make-Up Boiler 4A.3 Water Flow Requirements BoilerHydronic Piping Multiple Boilers, Primary Secondary System Hydronic Piping Multiple Boilers, Low Temperature System Hydronic Piping One Boiler, Multi-Temperature System Hydronic Piping Primary-Secondary, Reverse-Return Boiler CIRC. Pump Sized for Flow Through Boiler Water Connections Copper Brute II Water Heater 4B.1 Water System Piping Water Heater4B.2 Hot Water Supply Piping Water Heater 4B.3 Water Flow Requirements Water Heater4B.5 Freeze Protection Water Heater SupplyWater Heater Piping Multiple Heaters, One Tank Water Heater Piping Multiple Heaters, Multiple Tanks Temperature Control Main PowerElectrical Connections Field Wiring Panel External Staging Control Wiring AvertissementCopper Brute II 500 750 Ladder Diagram Copper Brute II 1000 Ladder Diagram Copper Brute II 1250 2000 Ladder Diagram Copper Brute II 500 1000 Wiring Schematic Copper Brute II 1250 1500 Wiring Schematic Copper Brute II 1750 2000 Wiring Schematic Terminal designations are as indicated Field Wiring for Modes 1 Avertissement Sequence of Operation Operating InstructionsFilling the Boiler System Programming the Temperature Control Choosing the ModeSystem Piping Primary Secondary Piping Parallel PipingFor ALL Other Modes Hydronic Primary/Secondary Mode Choosing the Mode for your Application Mechanical aquastat in a domestic hot water storage tankMode 5 Primary secondary piping with outdoor reset Advanced Topics Staging ModeDifferential Boiler Target Temperature Boiler Minimum Boil MINBoiler Maximum Boil MAX Pump OperationSetpoint Operation Outdoor Reset OperationDedicated Domestic Hot Water Typical Gas Train Configuration Operating the Burner and Set Up Advanced Programming ModeSet Up for 0 to 2500 Feet Altitude External Boiler OperationShutting Down the Copper Brute High Altitude Adjustment and Set UpTo Restart the Copper Brute System Maintenance MaintenanceAppliance Maintenance Component Description Temperature Control Flow Switch Ignition Controls IgnitorsBradford White Corp Trouble Shooting Troubleshooting the Temperature Control Troubleshooting Copper Brute ControlsCopper Brute II 500 Troubleshooting Error Codes Replacement Parts Parts ListSee Figures 35 Heat Exchanger Components Electrical Components Gas Train Components Burner Manifold Assy, 4 Burners, Left, LP For reference Internal Components Copper Brute II Hydronic Electrical Components H2214401F
Related manuals
Manual 44 pages 23.82 Kb