Bradford-White Corp BWCH, BWCV, Copper Brute II Hydronic Boiler Gas Supply and Piping, 61-91m

Page 13

COPPER BRUTE II (500 - 2000)

Page 13

 

 

 

 

SECTION 3.

Gas Supply and Piping

3.1Gas Supply and Piping

Gas piping should be supported by suitable

hangers or floor stands, not by the appliance.

The Copper Brute II’s gas train allows the user to pipe the gas from either the right side or the left side of the unit. As shipped, the right side of the gas train is capped off, and there is a manual valve on the left side. If desired, the manual valve on the left side of the gas train may be moved to the right side, and the cap on the right side may be moved to the left.

Review the following instructions before proceeding with the installation.

1.Verify that the appliance is fitted for the proper type of gas by checking the rating plate. Copper

Brute II appliances are equipped to operate at elevations up to 10,000 feet (3050m). Copper

Brute II appliances may be adjusted to operate properly at altitudes above 2500 feet (see Section 6.5.2) and the input will be reduced if the heating value of the gas supply is below sea level values.

2.The maximum inlet gas pressure must not exceed 13" w.c. (3.2kPa). The minimum inlet gas pressure is 5" w.c. (1.2kPa).

3.Refer to Table 7, size supply.

4.Run gas supply line in accordance with all applicable codes.

5.Locate and install manual shutoff valves in accordance with state and local requirements.

6.A sediment trap must be provided upstream of the gas controls.

7.All threaded joints should be coated with piping compound resistant to action of liquefied petroleum gas.

8.The appliance and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.45kpa).

9.The unit must be isolated from the gas supply system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.45kpa).

10.The appliance and its gas connection must be leak tested before placing it in operation.

11.Purge all air from gas lines.

WARNING

Do not use open flame to check for leaks. An open flame could lead to explosion, which could result in property damage, serious injury or death.

NOTE: The Copper Brute II appliance and all other gas appliances sharing the gas supply line must be firing at maximum capacity to properly measure the inlet supply pressure. The pressure can be measured at the supply pressure port on the gas valve. Low gas pressure could be an indication of an undersized gas meter, undersized gas supply lines and/or an obstructed gas supply line.

 

 

DISTANCE FROM GAS METER

 

 

SIZE AND

 

OR LAST STAGE REGULATOR

 

 

0-100'

0-31m

100-200'

31-61m

200-300'

61-91m

GAS TYPE

500 natural

1-1/2"

3.8cm

2"

5.1cm

2"

5.1cm

500 propane

1"

2.5cm

1-1/2"

3.8cm

1-1/2"

3.8cm

750 natural

2"

5.1cm

2"

5.1cm

2-1/2"

6.4cm

750 propane

1-1/2"

3.8cm

1-1/2"

3.8cm

2"

5.1cm

1000 natural

2"

5.1cm

2-1/2"

6.4cm

3"

7.6cm

1000 propane

1-1/2"

3.8cm

2"

5.1cm

2-1/2"

6.4cm

1250 natural

2-1/2"

6.4cm

2-1/2"

6.4cm

3"

7.6cm

1250 propane

2"

5.1cm

2"

5.1cm

2-1/2"

6.4cm

1500 natural

2-1/2"

6.4cm

3"

7.6cm

3"

7.6cm

1500 propane

2"

5.1cm

2-1/2"

6.4cm

2-1/2"

6.4cm

1750 natural

2-1/2"

6.4cm

3"

7.6cm

3"

7.6cm

1750 propane

2"

5.1cm

2-1/2"

6.4cm

2-1/2"

6.4cm

2000 natural

3"

7.6cm

3"

7.6cm

3-1/2"

8.9cm

2000 propane

2-1/2"

6.4cm

2-1/2"

6.4cm

3"

7.6cm

Notes:

1.These figures are based on 1/2" (0.12kPa) water column pressure drop.

2.Check supply pressure and local code requirements before proceeding with work. 3.Pipe fittings must be considered when determining gas pipe sizing.

Table 7. Gas Piping Size.

Image 13
Contents Copper Brute Table of Contents Trouble Shooting MaintenanceReplacement Parts Operating InstructionsIntroduction General InformationModel Identification Dimensions WarrantyLocating the Appliance Dimensional Data Inches 91cm horizontally Combustion Air Venting and Combustion AirCombustion Air From Room Intake Combustion AirVent Categories VentingCategory I Vent Common Venting SystemsCombustion Air and Vent Through Side Wall Category III Vent Locating Vent & Combustion Air TerminalsSide Wall Vent Terminal Side Wall Combustion Air TerminalVent Terminals for Outdoor Units Common Vent Test BoilersVertical Vent Terminal Vertical Combustion Air Terminal61-91m Gas Supply and Piping4A.1 Heating System Piping Hot Supply Connections Boiler Water Connections Copper Brute II Boiler4A.2 Cold Water Make-Up Boiler 4A.3 Water Flow Requirements BoilerHydronic Piping Multiple Boilers, Primary Secondary System Hydronic Piping Multiple Boilers, Low Temperature System Hydronic Piping One Boiler, Multi-Temperature System Hydronic Piping Primary-Secondary, Reverse-Return Boiler CIRC. Pump Sized for Flow Through Boiler 4B.1 Water System Piping Water Heater Water Connections Copper Brute II Water Heater4B.2 Hot Water Supply Piping Water Heater 4B.3 Water Flow Requirements Water HeaterSupply 4B.5 Freeze Protection Water HeaterWater Heater Piping Multiple Heaters, One Tank Water Heater Piping Multiple Heaters, Multiple Tanks Temperature Control Main PowerElectrical Connections Field Wiring Panel Avertissement External Staging Control WiringCopper Brute II 500 750 Ladder Diagram Copper Brute II 1000 Ladder Diagram Copper Brute II 1250 2000 Ladder Diagram Copper Brute II 500 1000 Wiring Schematic Copper Brute II 1250 1500 Wiring Schematic Copper Brute II 1750 2000 Wiring Schematic Terminal designations are as indicated Field Wiring for Modes 1 Avertissement Sequence of Operation Operating InstructionsFilling the Boiler System Choosing the Mode Programming the Temperature ControlSystem Piping Primary Secondary Piping Parallel PipingFor ALL Other Modes Hydronic Primary/Secondary Mode Mechanical aquastat in a domestic hot water storage tank Choosing the Mode for your ApplicationMode 5 Primary secondary piping with outdoor reset Advanced Topics Staging ModeDifferential Boiler Minimum Boil MIN Boiler Target TemperatureBoiler Maximum Boil MAX Pump OperationSetpoint Operation Outdoor Reset OperationDedicated Domestic Hot Water Typical Gas Train Configuration Advanced Programming Mode Operating the Burner and Set UpSet Up for 0 to 2500 Feet Altitude External Boiler OperationShutting Down the Copper Brute High Altitude Adjustment and Set UpTo Restart the Copper Brute System Maintenance MaintenanceAppliance Maintenance Component Description Flow Switch Temperature ControlIgnition Controls IgnitorsBradford White Corp Trouble Shooting Troubleshooting Copper Brute Controls Troubleshooting the Temperature ControlCopper Brute II 500 Troubleshooting Error Codes Parts List Replacement PartsSee Figures 35 Heat Exchanger Components Electrical Components Gas Train Components Burner Manifold Assy, 4 Burners, Left, LP For reference Internal Components Copper Brute II Hydronic Electrical Components H2214401F
Related manuals
Manual 44 pages 23.82 Kb