Cornelius 000 PLUS Not Form Sufficient ICE, Wiring Diagram, Condenser FAN Motor, Not Operating

Page 39

Trouble

 

Probable Cause

 

Remedy

COMPRESSOR OPERATES

E.

Inoperative control board. No

E.

Check LED’s on control board to

CONTINUOUSLY BUT DOES

 

output from board to

 

see if they are modulating. Check

NOT FORM SUFFICIENT ICE

 

solenoids.

 

for 24V output to pulse

BANK (con’t).

 

 

 

modulating expansion valve (see

 

 

 

 

WIRING DIAGRAM).

 

 

 

 

If control board green LED is on

 

 

 

 

and yellow LED Is flashing; but no

 

 

 

 

24V output, replace board.

CONDENSER FAN MOTOR

A.

Blown power circuit fuse.

A.

Replace power circuit fuse.

NOT OPERATING

 

 

 

 

 

B.

Fan blade obstructed.

B.

Remove obstruction.

 

C.

Inoperative condenser fan

C.

Replace condenser fan motor.

 

 

motor.

 

 

 

D.

Compressor contactor

D.

Replace compressor contactor.

 

 

inoperable.

 

 

AGITATOR MOTOR NOT

A.

Agitator motor propeller

A.

Remove obstruction.

OPERATING.

 

obstructed.

 

 

 

B.

Low voltage.

B.

Voltage must be at least 208 volts

 

 

 

 

at compressor terminals when

 

 

 

 

compressor is trying to start.

 

C.

Loose, disconnected, or

C. Tighten connections or replace

 

 

broken wiring.

 

broken wiring.

 

D.

Inoperative agitator motor.

D.

Replace agitator motor.

 

 

 

 

 

35

300614000

Image 39 Contents
This Document Contains Important Information AURORAR10,000 Plus Cooling UnitTable of Contents Table of Contents cont’d Water Pump Motor Operates but Water Pump does not Pump Cooling Unit CO2 Inlet Line CO2 GAS Check ValveWATER-TO-SYRUP ‘RATIO’OF Dispensed Drink TOO LOW or TOO Dispensed Product Produces Foam AS IT Leaves DispensingCooling Unit Description General DescriptionCooling Unit Data System Theory of Operation Flow Diagram Typical Installation Cooling Unit Unpacking and InspectionIdentification of LOOSE-SHIPPED Parts Selecting LocationPlacing Cooling Unit in Location Installing Remote Condenser Coil and FAN ASS’YInstalling Cooling Unit Remote Condenser Coil and FAN ASS’YConnecting Electrical Power Circuit to Cooling Unit Cooling Unit factory warranty Connecting Plain Water Inlet Supply Line to Cooling UnitConnecting CO2 Inlet Supply Line to Cooling Unit Preparing Cooling Unit for Operation Placing Cooling Unit in Operating PositionOperation Service internal components or electrical wiringAdjusting WATER-TO-SYRUP ‘‘RATIO’’ of Dispensed Product Dispensing Station AdjustmentsInstalling Line Identification Label Adjusting Water Flow RateOperating Controls Cooling Unit Refrigeration Power SwitchCooling Unit Carbonator Motor Switch Cooling Unit Circulating Motor SwitchReplenishing CO2 Supply AdjustmentsCleaning and Sanitizing Daily PRE-OPERATION CheckCooling Unit AIR Intake and Exhaust Filters Cooling Unit MaintenanceCooling Unit Carbonator Maintenance Sanitizing Syrup SystemsCleaning CO2 GAS Check Valves Remote Condenser Coil and FAN ASS’Y MaintenancePeriodic Inspection Periodic CleaningCleaning Cooling Unit AIR Intake and Exhaust Filters Preparing Cooling Unit for SHIPPING, STORING, or RelocatingChanging ICE Water Bath Remote Condenser Coil and FAN Assembly MaintenanceSee Figures 2 Parts Identification Lubrication Primary CO2 RegulatorSecondary CO2 Regulators Daily Cleaning of Unit Water Flow RateWATER-TO-SYRUP ‘‘RATIO’’OF Dispensed Product Wash Syrup Systems Sanitizing POST-MIX Syrup SystemsFlush Syrup Systems Sanitize Syrup SystemsWater Flush Syrup Systems Purge Water OUT of Syrup Systems Restore Operation CO2 GAS Check Valve Replenishing Syrup SupplyCleaning CO2 System GAS Check Valves Syrup Flavor ChangeCooling Unit CO2 Inlet Line CO2 GAS Check Valve 300614000 Wiring Diagram LOW or TOO High AdjustmentWATER-TO-SYRUP ‘RATIO’ Dispensed Drink TOO Only Carbonated Water a Dispensed Product Carbonation TOO LOW Comes OUT Dispensing Valve Clear But Foams in CUPWarm Product Being Only Carbonated WaterOnly Syrup Dispensed Carbonator MotorOperates but Water Operate Refrigeration PowerTemperature Sensing Water Pump MotorCompressor Operates Continuously but doesNot Form Sufficient ICE Bank Not Operating Wiring DiagramNot Form Sufficient ICE Condenser FAN MotorWarranty This page Left Blank Intentionally One Cornelius Place Anoka, Minnesota 612 800