Cornelius 000 PLUS, 10 Lubrication, Primary CO2 Regulator, Secondary CO2 Regulators

Page 25

8.Wipe each part with clean lint-free cloth. Inspect each part, especially the ball, for burrs, nicks, corrosion, deterioration, and other damage. Discard ball seat and any damaged or suspicious parts and replace with new parts during reassemble.

9.Reassemble check valves as shown in Figure 6. ALWAYS install new ball seat (QUAD RING) (P/N 312418-000.

NOTE: Make sure when assembling check valves together, check valve female end with white tapered gasket inside, is on inlet side of double liquid check valve assembly.

10.Assemble check valves together. DO NOT OVERTIGHTEN.

11.Install double liquid check valve assembly in plain water line connected between plain water cooling coil and carbonated water tank.

12.Repeat preceding steps 6 through 11 to service other double liquid check valve in other plain water line connected between plain water cooling coil and carbonated water tank.

13.Turn carbonator CO2 regulator adjusting screw to the right (clockwise) until its gage indicates pressure setting observed in step 3 preceding.

14.Open shutoff valve in plain water inlet supply line.

15.Restore electrical power to Cooling Unit at disconnect switch.

16.Dispense carbonated water at dispensing station and allow carbonator to cycle on and off. Check for water leaks and repair if evident.

17.Disconnect electrical power from Cooling Unit at disconnect switch.

18.Install Unit top cover and secure with two screws.

19.Restore electrical power to Cooling Unit at disconnect switch.

LUBRICATION

The carbonator water pump and the carbonated water circulating pump motor bearings must be oiled periodically, refer to oiling instructions on the motors. DO NOT OVER OIL.

ADJUSTMENTS

NOTE: To readjust CO2 regulator to a lower setting loosen adjusting screw lock nut, then turn screw to the left (counterclockwise) until pressure gage reads 5-psi lower than new setting will be. Turn adjusting screw to the right (clockwise) until gage registers new setting, then tighten lock nut.

PRIMARY CO2 REGULATOR

(see Figure 2).

Adjust primary CO2 regulator on CO2 cylinder to a minimum nominal setting of 120-psi or 24-psi higher than highest setting required by the secondary CO2 regulators. Loosen CO2 regulator adjusting screw locknut. Turn adjusting screw to the right (clockwise) until regulator gage registers nominal 120-psi, then tighten adjusting screw locknut.

SECONDARY CO2 REGULATORS

(see Figure 2).

Carbonator Secondary CO2 Regulator.

Adjust carbonator secondary CO2 regulator to a nominal 90-psi. Loosen CO2 regulator adjusting screw locknut. Turn adjusting screw to the right (clockwise) until regulator gage registers nominal 90-psi, then tighten adjusting screw locknut. CO2 PRESSURE TO CARBONATORS MUST NOT EXCEED 125-PSIG.

21

300614000

Image 25
Contents This Document Contains Important Information AURORAR10,000 Plus Cooling UnitTable of Contents Table of Contents cont’d WATER-TO-SYRUP ‘RATIO’OF Dispensed Drink TOO LOW or TOO Cooling Unit CO2 Inlet Line CO2 GAS Check ValveDispensed Product Produces Foam AS IT Leaves Dispensing Water Pump Motor Operates but Water Pump does not PumpCooling Unit Description General DescriptionCooling Unit Data System Theory of Operation Flow Diagram Typical Installation Identification of LOOSE-SHIPPED Parts Unpacking and InspectionSelecting Location Cooling UnitInstalling Cooling Unit Installing Remote Condenser Coil and FAN ASS’YRemote Condenser Coil and FAN ASS’Y Placing Cooling Unit in LocationConnecting Electrical Power Circuit to Cooling Unit Cooling Unit factory warranty Connecting Plain Water Inlet Supply Line to Cooling UnitConnecting CO2 Inlet Supply Line to Cooling Unit Preparing Cooling Unit for Operation Placing Cooling Unit in Operating PositionOperation Service internal components or electrical wiringInstalling Line Identification Label Dispensing Station AdjustmentsAdjusting Water Flow Rate Adjusting WATER-TO-SYRUP ‘‘RATIO’’ of Dispensed ProductCooling Unit Carbonator Motor Switch Cooling Unit Refrigeration Power SwitchCooling Unit Circulating Motor Switch Operating ControlsCleaning and Sanitizing AdjustmentsDaily PRE-OPERATION Check Replenishing CO2 SupplyCooling Unit Carbonator Maintenance Cooling Unit MaintenanceSanitizing Syrup Systems Cooling Unit AIR Intake and Exhaust FiltersCleaning CO2 GAS Check Valves Remote Condenser Coil and FAN ASS’Y MaintenanceCleaning Cooling Unit AIR Intake and Exhaust Filters Periodic CleaningPreparing Cooling Unit for SHIPPING, STORING, or Relocating Periodic InspectionChanging ICE Water Bath Remote Condenser Coil and FAN Assembly MaintenanceSee Figures 2 Parts Identification Primary CO2 Regulator LubricationSecondary CO2 Regulators Water Flow Rate Daily Cleaning of UnitWATER-TO-SYRUP ‘‘RATIO’’OF Dispensed Product Wash Syrup Systems Sanitizing POST-MIX Syrup SystemsSanitize Syrup Systems Flush Syrup SystemsWater Flush Syrup Systems Purge Water OUT of Syrup Systems Restore Operation CO2 GAS Check Valve Replenishing Syrup SupplySyrup Flavor Change Cleaning CO2 System GAS Check ValvesCooling Unit CO2 Inlet Line CO2 GAS Check Valve 300614000 Wiring Diagram WATER-TO-SYRUP ‘RATIO’ AdjustmentDispensed Drink TOO LOW or TOO HighCarbonation TOO LOW Dispensed ProductComes OUT Dispensing Valve Clear But Foams in CUP Only Carbonated Water aOnly Syrup Dispensed Only Carbonated WaterCarbonator Motor Warm Product BeingTemperature Sensing Operate Refrigeration PowerWater Pump Motor Operates but WaterContinuously but does Compressor OperatesNot Form Sufficient ICE Bank Not Form Sufficient ICE Wiring DiagramCondenser FAN Motor Not OperatingWarranty This page Left Blank Intentionally One Cornelius Place Anoka, Minnesota 612 800
Related manuals
Manual 52 pages 8.37 Kb

000 PLUS, 10 specifications

Cornelius 10,000 PLUS is a pioneering innovation in the beverage dispensing industry, designed to cater to the evolving needs of commercial establishments. This advanced system combines state-of-the-art technology with user-friendly features, making it a standout choice for restaurants, cafes, and bars aiming to enhance their beverage service.

One of the main features of the Cornelius 10,000 PLUS is its impressive capacity. With the ability to dispense a wide variety of beverages, including soft drinks, cocktails, and craft beers, the system supports a large volume of service, perfect for high-demand environments. The modular design allows for easy expansion, enabling businesses to add additional flavors or beverages as needed without major overhauls.

The technology behind the Cornelius 10,000 PLUS is equally impressive. It utilizes advanced cooling technology to ensure that beverages are served at the optimal temperature, enhancing the customer experience. The integrated touchless dispensing mechanism minimizes waste and ensures a hygienic experience, addressing growing concerns about cleanliness in food service environments. This technology also improves speed, allowing staff to serve customers more efficiently.

Another key characteristic of the Cornelius 10,000 PLUS is its digital integration capabilities. The system can be connected to a central management platform that tracks sales, inventory levels, and maintenance needs in real-time. This allows operators to optimize their beverage offerings based on customer preferences and reduces downtime through proactive maintenance alerts.

In addition to its performance features, the Cornelius 10,000 PLUS is designed with sustainability in mind. The system employs energy-efficient practices, reducing its environmental footprint while lowering operational costs. The materials used in construction are durable yet eco-friendly, ensuring longevity and less waste.

Overall, the Cornelius 10,000 PLUS stands out as an essential tool for any business looking to elevate its beverage service. With its combination of high capacity, cutting-edge technology, and sustainability features, it not only meets the demands of today’s fast-paced service environments but also positions establishments for future growth and success.