Configuration and Firmware Update
Selected MAX firmware file
Description field for selected Kit file
Firmware download status
Device and System Number must match the Device and System values listed in the Workspace window
FIG. 39 Send to NetLinx Device dialog (showing MAX unit’s firmware updated via IP)
11.Click the Reboot Device checkbox to reboot the MAX unit after the firmware update process is complete.
12.Click Send to begin the transfer. The file transfer progress is indicated on the
Download of the last Kit file component can take a few minutes to complete. DO NOT terminate this upload process until all components have completely been installed and the device reboots. During this process, the LCD will show FW LOADING.
13.Click Close once the download process is complete.
14.
If the connection fails to establish, a Connection Failed dialog appears. Try selecting a different IP Address if communication fails.
Press the Retry button to reconnect using the same communication parameters. Press the Change button to alter your communication parameters and repeat steps 2 thru 12.