Site Preparation (UPS and XR) – Operating Environment
Recommended current protection
AC output
customer.
Dual/single |
|
|
|
|
|
|
mains | Connection | 10kVA | 15kVA | 20kVA | 30kVA | Notes |
configuration |
|
|
|
|
|
|
|
|
|
|
|
|
|
Single | Mains/bypass | 35A breaker | 60A breaker | 80A breaker | 125A breaker |
|
| input | (30 kAIC) | (30 kAIC) | (30 kAIC) | (30 kAIC) |
|
|
|
|
|
|
|
|
Dual | Mains input | 35A breaker | 60A breaker | 80A breaker | 125A breaker | 1,2 |
|
| (30 kAIC) | (30 kAIC) | (30 kAIC) | (30 kAIC) |
|
|
|
|
|
|
|
|
Dual | Bypass input | 35A breaker | 60A breaker | 80A breaker | 125A breaker | 1,2 |
|
| (30 kAIC) | (30 kAIC) | (30 kAIC) | (30 kAIC) |
|
|
|
|
|
|
|
|
Any | Output | 35A fast- | 60A fast- | 80A fast- | 125A fast- | 3,4 |
|
| acting class | acting class | acting class | acting class |
|
|
| J fuse | J fuse | J fuse | J fuse |
|
|
|
|
|
|
|
|
Note 1:
If the available fault current of the installation is below 30kA, a lower
Note 2:
For breaker settings, refer to below table listing available overload currents.
Note 3:
If the available fault current of the installation is less than 1200A for the 10kVA and 15kVA UPS sizes, and below 2300A for the 20kVA and 30kVA UPS sizes, a breaker (of the same value as for the bypass input) can be used.
Note 4:
Recommended maximum rating of a
AIS® 3000 | 19 |