Electrical Installation – System-Electrical Information

Electrical Installation – System-Electrical Information

Source connections

WARNING!

The UPS must be supplied from a 208Y/120V 4W + GND 60Hz source.

CAUTION!

Verify clockwise phase-rotation (L1, L2, L3) and make sure a neutral connection is present.

For recommended source connections, see The Site Preparation section.

CAUTION!

The installation must comply with all local and national codes.

Refer to NEC Articles 310-15, 310-16 for further information.

30

AIS® 3000 10-30kVA, 208V, Site Preparation and Installation Manual – 990-1957

Page 38
Image 38