APC 3000 Minimum setting of breakers for 10kVA UPS, Minimum setting of breakers for 15kVA UPS

Models: 3000

1 58
Download 58 pages 30.91 Kb
Page 28
Image 28

Site Preparation (UPS and XR) – Operating Environment

Minimum setting of breakers for 10kVA UPS

Overload

Mains input

Bypass input

Output

Duration

Notes

Event

 

 

 

 

 

 

 

 

 

 

 

Internal fault

2kA

1.7kA

14kA

<10ms

1

 

 

 

 

 

 

800%

223A

223A

500ms

 

overload

 

 

 

 

 

bypass

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

150%

42A

30s

 

overload

 

 

 

 

 

normal/battery

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

125%

35A

60s

 

overload

 

 

 

 

 

normal/battery

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

Continuously

34A

31A

31A

 

 

 

 

 

 

 

Note 1: For the output value, the short-circuit-level is indicated.

Minimum setting of breakers for 15kVA UPS

Overload

Mains input

Bypass input

Output

Duration

Notes

Event

 

 

 

 

 

 

 

 

 

 

 

Internal fault

2.5kA

2.1kA

14kA

<10ms

1

 

 

 

 

 

 

800%

333A

333A

500ms

 

overload

 

 

 

 

 

bypass

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

150%

63A

30s

 

overload

 

 

 

 

 

normal/battery

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

125%

52A

60s

 

overload

 

 

 

 

 

normal/battery

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

Continuously

51A

46A

46A

 

 

 

 

 

 

 

Note 1: For the output value, the short-circuit-level is indicated

20

AIS® 3000 10-30kVA, 208V, Site Preparation and Installation Manual – 990-1957

Page 28
Image 28