Site Preparation (UPS and XR) – Operating Environment
Minimum setting of breakers for 10kVA UPS
Overload | Mains input | Bypass input | Output | Duration | Notes | |
Event | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
Internal fault | 2kA | 1.7kA | 14kA | <10ms | 1 | |
|
|
|
|
|
| |
800% | – | 223A | 223A | 500ms |
| |
overload |
|
|
|
|
| |
bypass |
|
|
|
|
| |
operation |
|
|
|
|
| |
|
|
|
|
|
| |
150% | – | – | 42A | 30s |
| |
overload |
|
|
|
|
| |
normal/battery |
|
|
|
|
| |
operation |
|
|
|
|
| |
|
|
|
|
|
| |
125% | – | – | 35A | 60s |
| |
overload |
|
|
|
|
| |
normal/battery |
|
|
|
|
| |
operation |
|
|
|
|
| |
|
|
|
|
|
| |
Continuously | 34A | 31A | 31A | ∞ |
| |
|
|
|
|
|
|
Note 1: For the output value, the
Minimum setting of breakers for 15kVA UPS
Overload | Mains input | Bypass input | Output | Duration | Notes | |
Event | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
Internal fault | 2.5kA | 2.1kA | 14kA | <10ms | 1 | |
|
|
|
|
|
| |
800% | – | 333A | 333A | 500ms |
| |
overload |
|
|
|
|
| |
bypass |
|
|
|
|
| |
operation |
|
|
|
|
| |
|
|
|
|
|
| |
150% | – | – | 63A | 30s |
| |
overload |
|
|
|
|
| |
normal/battery |
|
|
|
|
| |
operation |
|
|
|
|
| |
|
|
|
|
|
| |
125% | – | – | 52A | 60s |
| |
overload |
|
|
|
|
| |
normal/battery |
|
|
|
|
| |
operation |
|
|
|
|
| |
|
|
|
|
|
| |
Continuously | 51A | 46A | 46A | ∞ |
| |
|
|
|
|
|
|
Note 1: For the output value, the
20 | AIS® 3000 |