System-Electrical Information

System-Electrical Information

WARNING!

All electrical power and power control wiring must be installed by a qualified electrician, and must comply with local and national regulations for maximum power rating.

UPS ratings

10 kVA

15 kVA

20kVA

30 kVA

8 kW

12 kW

16 kW

24 kW

 

 

 

 

 

 

Input voltage / Bypass voltage (V)

3-phase

3-phase

3phase

3-phase

 

208Y/

208Y/

208Y/

208Y/

 

120V

120V

120V

120V

 

 

 

 

 

Input current (nominal, per phase) (A)

24.6

36.9

49.3

73.9

 

 

 

 

 

Maximum input current per phase (continuous, at

27.1

40.6

54.2

81.3

minimum mains voltage)

 

 

 

 

 

 

 

 

 

Input current protection for mains source or single

3x35

3x60

3x80

3x125

mains supply (external to UPS, not supplied) (A)

 

 

 

 

 

 

 

 

 

Input current protection for bypass source in dual mains

35

60

80

125

configuration (external to UPS, not supplied) (A)

 

 

 

 

 

 

 

 

 

Input frequency (Hz) range

40-70

40-70

40-70

40-70

 

 

 

 

 

Output voltage (on line). (V)

120/208

120/208

120/208

120/208

Minimum and maximum values (+/- 1%)

 

 

 

 

 

 

 

 

 

Output current (nominal, per phase) (A)

27.8

43.3

55.5

83.3

 

 

 

 

 

Maximum output current

30.5

45.8

51.1

91.6

(in bypass only at 110% overload per phase)

 

 

 

 

 

 

 

 

 

Bypass input current (A)

30.5

45.8

51.1

91.6

(in bypass only at 110% overload, per phase)

 

 

 

 

 

 

 

 

 

Neutral output current (with 100% switch mode load)

48.1

74.9

96.0

144.1

(A)

 

 

 

 

 

 

 

 

 

Output current protection (external to UPS, not

40

60

80

125

supplied) (A)

 

 

 

 

 

 

 

 

 

Output frequency range (Hz)

50/60

50/60

50/60

50/60

 

 

 

 

 

DC overcurrent protection and disconnect switch for

23

35

46

69

external safety:

 

 

 

 

DC voltage rating of the battery supply

+/- 192

+/- 192

+/- 192

+/- 192

Maximum available short-circuit current

10 kA

10 kA

10 kA

10 kA

 

 

 

 

 