APC 3000  Attach the Conduit Box bottom to the Enclosure, using 4 M4x13 screws

Models: 3000

1 58
Download 58 pages 30.91 Kb
Page 41
Image 41
Attach the Conduit Box bottom to the Enclosure, using (4) M4x13 screws.

Electrical Installation – Input/Output Wiring – Single Mains (default)

Punch 2 holes in the marked areas of the Conduit Box bottom to fit the size of the conduit pipes.

Attach the Conduit Box bottom to the Enclosure, using (4) M4x13 screws.

Install conduit pipes in the Conduit Box.

Run cables through the conduit pipes and the bottom of the Conduit Box, guides cables up into the input/output area.

Install the top part of the Conduit Box to the Enclosure.

Neutral



N

N

Input

 

L1



 

cables

L2

 

 

 

L3

 

Output



 

L2

Batt+

cables

 

 

 

 

 

L1

 

N

 

 

 

Batt—

 

 

 

 

Ground



L3

cables

 

Plate covering cable termination area



Attach input cable lugs on L1, L2 and L3 input busbars (left side in the UPS), using the provided M6 hex screws. Attach output cable lugs on L1, L2 and L3 output busbars, using the provided M6 hex screws. Attach N x 2 where shown, using the provided hex screws.

Attach Ground x 2 where shown, using the provided hex screws.

Reinstall the Plate, following reversed deinstallation procedures.

AIS® 3000 10-30kVA, 208V, Site Preparation and Installation Manual – 990-1957

33

Page 41
Image 41
APC 3000 installation manual  Attach the Conduit Box bottom to the Enclosure, using 4 M4x13 screws