Input/Output Wiring – Single Mains (default)
The UPS is designed for both single (default) and dual mains installations. Carry out the Total Power Off Procedure, and follow the below steps to install the UPS in a
The illustrations show a 20.59in/523mm Enclosure, but installation procedures are identical for 13.85in/352mm Enclosures).
Wiring procedure - single mains
N | N |
Conduit box |
| ||
(top part) |
|
| |
|
| ||
Conduit box |
| ||
(bottom part) | |||
|
|
| Conduit box |
| (top part) | |
|
| |
|
| |
| ||
| EPO | |
|
| |
|
| Conduit |
Output | Input |
MBP Conduit
Loosen the (6) M4x13 screws from the plate covering the cable termination area, and remove.
Loosen the (2) M4x13 screws from the top part of the Conduit Box. Loosen the 3 M4x13 attaching it to the bottom part (2 screws in a 13.85in/352mm Enclosure) and remove.
Loosen the (4) M4x13 screws (2 each side) from the bottom part of the Conduit Box and remove.
32 | AIS® 3000 |