Site Preparation (UPS and XR) – Operating Environment
Minimum setting of breakers for 20kVA UPS
Overload | Mains input | Bypass input | Output | Duration | Notes | |
Event | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
Internal fault | 4 kA | 3.4kA | 14 kA | <10ms | 1 | |
|
|
|
|
|
| |
800% | – | 444A | 444A | 500ms |
| |
overload |
|
|
|
|
| |
bypass |
|
|
|
|
| |
operation |
|
|
|
|
| |
|
|
|
|
|
| |
150% | – | – | 84A | 30s |
| |
overload |
|
|
|
|
| |
normal/battery |
|
|
|
|
| |
operation |
|
|
|
|
| |
|
|
|
|
|
| |
125% | – | – | 70A | 60s |
| |
overload |
|
|
|
|
| |
normal/battery |
|
|
|
|
| |
operation |
|
|
|
|
| |
|
|
|
|
|
| |
Continuously | 68A | 62A | 62A | ∞ |
| |
|
|
|
|
|
|
Note 1: For the output value, the
Minimum setting of breakers for 30kVA UPS
Overload | Mains input | Bypass input | Output | Duration | Notes | |
Event | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
Internal fault | 5 kA | 4.2 kA | 14 kA | <10 ms | 1 | |
|
|
|
|
|
| |
800% | – | 667A | 667A | 500ms |
| |
overload |
|
|
|
|
| |
bypass |
|
|
|
|
| |
operation |
|
|
|
|
| |
|
|
|
|
|
| |
150% | – | – | 125A | 30s |
| |
overload |
|
|
|
|
| |
normal/battery |
|
|
|
|
| |
operation |
|
|
|
|
| |
|
|
|
|
|
| |
125% | – | – | 105A | 60s |
| |
overload |
|
|
|
|
| |
normal/battery |
|
|
|
|
| |
operation |
|
|
|
|
| |
|
|
|
|
|
| |
Continuously | 102A | 92A | 92A | ∞ |
| |
|
|
|
|
|
|
Note 1: For the output value, the
AIS® 3000 | 21 |