Site Preparation (UPS and XR) – Operating Environment

Minimum setting of breakers for 20kVA UPS

Overload

Mains input

Bypass input

Output

Duration

Notes

Event

 

 

 

 

 

 

 

 

 

 

 

Internal fault

4 kA

3.4kA

14 kA

<10ms

1

 

 

 

 

 

 

800%

444A

444A

500ms

 

overload

 

 

 

 

 

bypass

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

150%

84A

30s

 

overload

 

 

 

 

 

normal/battery

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

125%

70A

60s

 

overload

 

 

 

 

 

normal/battery

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

Continuously

68A

62A

62A

 

 

 

 

 

 

 

Note 1: For the output value, the short-circuit-level is indicated.

Minimum setting of breakers for 30kVA UPS

Overload

Mains input

Bypass input

Output

Duration

Notes

Event

 

 

 

 

 

 

 

 

 

 

 

Internal fault

5 kA

4.2 kA

14 kA

<10 ms

1

 

 

 

 

 

 

800%

667A

667A

500ms

 

overload

 

 

 

 

 

bypass

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

150%

125A

30s

 

overload

 

 

 

 

 

normal/battery

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

125%

105A

60s

 

overload

 

 

 

 

 

normal/battery

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

Continuously

102A

92A

92A

 

 

 

 

 

 

 

Note 1: For the output value, the short-circuit level is indicated.

AIS® 3000 10-30kVA, 208V, Site Preparation and Installation Manual – 990-1957

21

Page 29
Image 29