Floor Anchoring (option)
Floor anchoring is an option. If your installation does not include this option, proceed to the Front Panel Installation section.
Floor anchoring of stand-alone systems
In seismic areas, it is recommended that the installation be bolted to the floor, and that the batteries be secured in the Enclosure by the Battery Securing Brackets.
For floor anchoring, use the 2 transport brackets that were used to secure the UPS to the pallet during transport.
BATTERY UNIT | BATTERY UNIT |
|
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT | BATTERY UNIT |
|
BATTERY UNIT
BATTERY UNIT
Floor Anchoring Bracket
| BATTERY UNIT | BATTERY UNIT |
|
| |
|
| BATTERY UNIT |
|
| BATTERY UNIT |
| ||
|
| |
| ||
|
|
Align the 4 holes in the bottom angle of the Floor Anchoring Bracket on either side of the UPS to the
Floor anchoring procedures identical for both 13.85in/352mm and 20.59in/523 mm UPS Enclosures.
See Floor Anchoring Preparation section and install a minimum of 4 anchors on each Enclosure (minimum size: M8) where shown, following the specifications provided by the manufacturer.