APC 3000 Wiring Verification Procedure, Mains Input, Bypass Input for dual mains installations

Models: 3000

1 58
Download 58 pages 30.91 Kb
Page 52
Image 52
Wiring Verification Procedure

Wiring Verification Procedure

Do not connect batteries in the UPS.

Use following procedure to verify that the UPS has been wired properly:

51. If your installation includes an XR Enclosure, make sure that the DC breaker (if available) is in the OFF position and that both 125A fuses are removed from the

XR Enclosure.

52. Check that the power wiring is torqued to 45 lbf.in/5Nm.

53. If your installation includes an XR Enclosure, remount the 125A fuses in the XR

Enclosure and check that the DC breaker (if available) on the XR Enclosure is in the ON position.

54. Apply utility power to the system input and measure the voltage at the input terminal block. Record voltages between:

Mains Input:

L1 and N: _________ L2 and N: ________ L3 and N: _______

Bypass Input (for dual mains installations):

L1 and N: _________ L2 and N: ________ L3 and N: _______

Measured voltage must be between 96 and 130. If not, STOP! Verify correct wiring (correct location of N) from the power source to the input wiring connections.

55. Check that the display is powered up.

56. Select the Status Menu on the display, and check that all input voltages are present.

57. Verify L1, L2, L3 clockwise phase rotation using a phase-rotation meter.

58. Test the EPO switch. The system should shut down completely. If not, check the connections and the EPO switch to ensure that they are installed and functioning

correctly. For installations with XR Battery Enclosures, the DC disconnect should

trip to the OFF position at the EPO test (if applicable).

59. Successful completion of steps 1 through 5 indicates that the UPS wiring is correctly installed and functioning correctly. Turn off breakers and switches and

shut down utility power to the system input. See Total-Power-OffProcedure.

510. Please leave a wiring diagram on site for service / technical support personnel.

44

AIS® 3000 10-30kVA, 208V, Site Preparation and Installation Manual – 990-1957

Page 52
Image 52
APC 3000 installation manual Wiring Verification Procedure, Mains Input, Bypass Input for dual mains installations