General Charge Setting
The general charge setting is set to 100% as default.
From the Display it is possible to adjust the charge levels to 75%, 50%, 25%, 10% and 0%.
If the charge limit input is active (J106, pins 7,8) the UPS will reduce the maximum General Charge effect (100%) to the programmed value.
See XR Enclosure, MBP, and Generator Control Wiring for overview of J106.
Charge setting procedure
From the main menu of the display, select
Selector |
|
| Control | Logging |
Arrow |
|
| Status | Display |
|
|
| Setup | Diags |
|
|
| ||
|
|
| Accessories | Help |
|
|
|
|
|
Main Menu
Select System, and press ENTER
Use the arrow keys to get to Gen.Chrg: 100%, and press ENTER.
Selector |
|
| Slew | rate: | 1.00 | Hz/s |
Arrow |
|
| Gen.Chrg: | 100% |
| |
|
|
| ||||
|
|
| ||||
|
|
| Cyclic Chrg. Off |
| ||
|
|
| Auto | Start: Off |
| |
|
|
|
|
|
|
|
An arrow will appear to the left of Gen.Chrg. Use the UP arrow on the display to go to the desired level of charge effect. Select ENTER.
Now, when the charge limit input is active, the UPS will charge to the new setting.
40 | AIS® 3000 |