General Charge Setting

General Charge Setting

The general charge setting is set to 100% as default.

From the Display it is possible to adjust the charge levels to 75%, 50%, 25%, 10% and 0%.

If the charge limit input is active (J106, pins 7,8) the UPS will reduce the maximum General Charge effect (100%) to the programmed value.

See XR Enclosure, MBP, and Generator Control Wiring for overview of J106.

Charge setting procedure

From the main menu of the display, select Set-up, and press ENTER.

Selector

 

 

Control

Logging

Arrow

 

 

Status

Display

 

 

 

Setup

Diags

 

 

 

 

 

 

Accessories

Help

 

 

 

 

 

Main Menu

Select System, and press ENTER

Use the arrow keys to get to Gen.Chrg: 100%, and press ENTER.

Selector

 

 

Slew

rate:

1.00

Hz/s

Arrow

 

 

Gen.Chrg:

100%

 

 

 

 

 

 

 

 

 

 

Cyclic Chrg. Off

 

 

 

 

Auto

Start: Off

 

 

 

 

 

 

 

 

An arrow will appear to the left of Gen.Chrg. Use the UP arrow on the display to go to the desired level of charge effect. Select ENTER.

Now, when the charge limit input is active, the UPS will charge to the new setting.