APC UPS control system manual 198, On OFF

Models: UPS control system

1 233
Download 233 pages 42.59 Kb
Page 199
Image 199

It looks bizarre and ugly, but is easily parsed. The # is some kind of marker/ident character. Skip it. The rest fits this form:

Command character - use this to select the value

Locale - use ’b’ to find out what yours is (the last character), ’4’ applies to all

Number of choices - ’4’ means there are 4 possibilities coming up

Choice length - ’3’ means they are all 3 chars long

Matrix-UPS models have ## between each grouping for some reason. Here is an example broken out to be more readable:

CMD

DFO

RSP FSZ FVL

 

 

 

u

D

4

3

127

130

133

136

u

M

4

3

229

234

239

224

u

A

4

3

108

110

112

114

u

I

4

3

253

257

261

265

l

D

4

3

106

103

100

097

l

M

4

3

177

172

168

182

l

A

4

3

092

090

088

086

l

I

4

3

208

204

200

196

e

4

4

2

00

15

50

90

o

D

1

3

115

 

 

 

o

J

1

3

100

 

 

 

o

I

1

3

230

240

220

225

o

M

1

3

208

 

 

 

s

4

4

1

H

M

L

L

q

4

4

2

02

05

07

10

p

4

4

3

020

180

300

600

k

4

4

1

0

T

L

N

r

4

4

3

000

060

180

300

E

4

4

3

336

168

ON OFF

CMD

== UPSlink Command.

 

 

 

u

= upper

transfer voltage

 

l

= lower

transfer voltage

 

e

= return threshold

 

 

o

= output voltage

 

 

 

s

= sensitivity

 

 

 

p

= shutdown grace delay

 

q

= low battery warning

 

k

= alarm

delay

 

 

 

r

= wakeup delay

 

 

 

E

= self test

interval

 

198

Page 199
Image 199
APC UPS control system manual 198, On OFF