APC UPS control system manual Apcaccess eprom

Models: UPS control system

1 233
Download 233 pages 42.59 Kb
Page 75
Image 75

LOADPCT

: 11.4

Percent Load Capacity

BATTV

: 27.7 Volts

BCHARGE

: 100.0

Percent

MBATTCHG : 5 Percent

TIMELEFT : 112.0

Minutes

MINTIMEL : 3 Minutes

SENSE

: Low

 

DWAKE

: 060 Seconds

DSHUTD

: 180 Seconds

LOTRANS

: 204.0

Volts

HITRANS

: 253.0

Volts

RETPCT

: 050.0

Percent

STATFLAG : 0x08 Status Flag

STATUS

: ONLINE

 

ITEMP

: 29.2 C Internal

ALARMDEL : Low Battery

LASTXFER : U command or Self Test

SELFTEST : NO

STESTI

: 336

DLOWBATT : 02 Minutes

DIPSW

: 0x00 Dip Switch

REG1

: 0x00 Register 1

REG2

: 0x00 Register 2

REG3

: 0x00 Register 3

MANDATE

: 01/05/99

SERIALNO : GS9902009459

BATTDATE : 01/05/99

NOMOUTV

: 230.0

NOMBATTV : 24.0

HUMIDITY : N/A

AMBTEMP

: N/A

EXTBATTS : 0

BADBATTS : N/A

FIRMWARE : 60.11.I

APCMODEL : IWI

END APC : Fri Dec 03 12:34:33 CET 1999

For the various smaller, cheaper APC USB UPSes, such as the CS, ES, ..., you will get much of the information that is presented above, but not all of it. For example, you will not get MAXLINEV, MINLINEV, LINEFREQ,

... and in particular, the LOADPCT will be zero when you are running on mains. LOADPCT will display when the UPS is on batteries. You must remember that the non-SmartUPSes are much simpler (and less expensive) and therefore produce less information.

apcaccess eprom:

The eprom command line option for apcaccess allows you to examine the current values of your UPS’ EPROM as well as to know the permit-